Notifier ACPS-2406 User manual

Addressable Charger/
Power Supply
ACPS-2406
Manual
B
PN 51304:B ECN 03-366
Document 51304
09/02/2003 Rev:

2ACPS-2406 51304:B 09/02/2003
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of
smoke detectors, heat detectors, manual pull stations, audible
warning devices, and a fire alarm control panel with remote
notification capability—can provide early warning of a develop-
ing fire. Such a system, however, does not assure protection
against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec-
tors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72-1999 (NFPA 72-1999),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use of
System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emer-
gency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are
designed to provide early warning against fire, they do not
guarantee warning or protection against fire. A fire alarm sys-
tem may not provide timely or adequate warning, or simply
may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building.
A second-floor detector, for example, may not sense a first-
floor or basement fire.
Particles of combustion or “smoke” from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of “smoke” present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ion-
izing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different
ways and are often unpredictable in their growth, neither type
of detector is necessarily best and a given type of detector
may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predeter-
mined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire pro-
tection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the sys-
tem for the connection of alarm transmission wiring, communi-
cations, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crip-
pling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medica-
tion. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsi-
bility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically com-
patible with the control panel. It is essential to use only equip-
ment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against tele-
phone line failure, backup radio transmission systems are rec-
ommended.
The most common cause of fire alarm malfunction is inade-
quate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA stan-
dards. At a minimum, the requirements of Chapter 7 of NFPA
72-1999 shall be followed. Environments with large amounts
of dust, dirt or high air velocity require more frequent mainte-
nance. A maintenance agreement should be arranged
through the local manufacturer's representative. Maintenance
should be scheduled monthly or as required by National and/
or local fire codes and should be performed by authorized pro-
fessional fire alarm installers only. Adequate written records of
all inspections should be kept.
Precau-L-4-2003.fm

ACPS-2406 51304:B 09/02/2003 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. The control unit and asso-
ciated equipment may be damaged by removing and/or insert-
ing cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72-1999 Chapter 7
after any programming operation or change in site-specific
software. Reacceptance testing is required after any change,
addition or deletion of system components, or after any modifi-
cation, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software func-
tions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvert-
ently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50
devices, must also be tested and proper system operation ver-
ified.
This system meets NFPA requirements for operation at 0°C
to 49°C (32°F to 120°F) and at a relative humidity (noncon-
densing) of 85% at 30°C (86°F) per NFPA, and 93% ± 2% at
32°C ± 2°C (89.6°F ± 1.1°F) per ULC. However, the useful life
of the system's standby batteries and the electronic compo-
nents may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and all peripherals be installed in an environment with
a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indi-
cating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to light-
ning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility. Overhead or outside
aerial wiring is not recommended, due to an increased sus-
ceptibility to nearby lightning strikes. Consult with the Techni-
cal Assistance Center if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifi-
cations, verify that they will not interfere with battery, trans-
former, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced ter-
minal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are removed
from the body. Use static-suppressive packaging to protect
electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation
by authorized personnel.
Precau-L-4-2003.fm
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment in
a residential area is likely to cause interference, in which
case the user will be required to correct the interference
at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Cana-
dian Department of Communications.
Le present appareil numerique n'emet pas de bruits radi-
oelectriques depassant les limites applicables aux appa-
reils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
AWACS™, HARSH™, and VeriFire™ are trademarks, and FlashScan® and VIEW®are registered trademarks of NOTIFIER. Acclimate™,Filtrex™, and
Pinnacle™ are trademarks of System Sensor. NION™ is a trademark of NIS. NIS™ and Notifier Integrated Systems™ are trademarks and NOTIFIER® is a
registered trademark of Fire•Lite Alarms, Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a
registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. LEXAN® is a registered
trademark of GE Plastics, a subsidiary of General Electric Company.

4ACPS-2406 51304:B 09/02/2003
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any com-
ments or suggestions about our online Help or printed manual, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
Please note this email address is for documentation feedback only. If you have any technical
issues, please contact Technical Services.

Table of Contents
ACPS-2406 PN 51304:B:09/02/2003 5
Section 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Installation Standards and Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Board Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Section 2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
In a CAB-3 Series Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
In a BB-25 Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
In a CAB-PS1 Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Section 3 Configuring the ACPS-2406 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
DIP Switch Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Determining Address Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Setting the Base Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Panel Programming Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Panel Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Software Type ID Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Dual Stage Alert/Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Selecting Dual Stage Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Addressing in Dual Stage Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Dual Stage Panel Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Section 4 Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
NAC Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
General Purpose Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Style B (Class B) Initiating Device Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Section 5 Power Supply Calculations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
DC Current Draw Calculations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Battery Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Table of Contents
6ACPS-2406 PN 51304:B 09/02/2003

Features Introduction
ACPS-2406 PN 51304:B 09/02/2003 7
Section 1 Introduction
The ACPS-2406 is an auxiliary addressable power supply and battery charger with 24 VDC
outputs. It operates in FlashScan® or CLIP (Classic Interface Protocol) mode, and has built-in
strobe synchronization. It may be configured to drive four Notification Appliance Circuits or,
alternately, may be configured to provide four-wire detector power or general purpose power.
1.1 Features
• Addressable by any FlashScan® or CLIP FACP (Fire Alarm Control Panel)
• Strobe/NAC Synchronization with System Sensor SpectrAlert™* Series horns and strobes, or
Gentex or Wheelock horns and strobes. (Use only devices from the same manufacturer in each
system).
*SpectrAlert is a registered trademark of System Sensor
• NAC synchronization with UZC-256 (Universal Zone Coder)
• Provides four coded or non-coded NACs that share 6.0 A of output power, or, configured
differently, will supply 5.0 A of four-wire detector power or general purpose power
• Power-limited outputs
• Charges 7 to 25 AH batteries
• Auxiliary +24 VDC @ 0.5 A output for use within the same cabinet
• Isolated Signaling Line Circuit (SLC) interface
• Brownout detection
• Battery/battery charger supervision
• AC loss detection and AC loss delay reporting
• Selectable Ground Fault Detection
• Occupies between five and 13 addresses on an SLC, depending on configuration
• Canadian Two-stage with Temporal Pattern for Evacuation
1.2 Specifications
• Primary (AC) Power - TB1
• ACPS-2406 - 110-120 VAC 50/60 Hz input, 2.7 A maximum
24 VDC output voltage regulated and power-limited
• Output Circuits - TB4, TB5, TB6
• 2.5 A maximum for any one output circuit
• 5.0 A (continuous), 6.0 A during an alarm (1 hour UL rating)
•Auxiliary Power Output - J1 - 24 VDC @ 0.5 A, for use within the same cabinet. When this
output is used for an installation, the maximum load current available at Output #4 (TB6-3 and
TB6-4) will become 2.0 A maximum.
•Secondary Power (Battery) Charging Circuit - TB2, TB3 - lead-acid battery charger which
will charge 7 to 25 AH batteries. Maximum charger current - 1.1 A
• Wheelock synchronization devices are compatible with ACPS-2406 software greater than
#ACPS1.3, together with Revision L or higher of the ACPS-2406 PC board. (Figure 1.1 on
page 10 for revision location.)

Introduction Installation Standards and Codes
8ACPS-2406 PN 51304:B 09/02/2003
• Utilizes wire sizes 12-18 AWG (3.25-.75 mm2)
• Average SLC current is 1.0 mA. The maximum resistance of the SLC wiring from any device
to the FACP should not exceed 40/50 Ohms (50 Ohms for the LIB-200A and LIB-400). SLC
data is transmitted between 24.0 VDC, 5 VDC and 0 VDC at approximately 3.33k baud.
• Battery fuse (F2) 15A, 3AB
• Line Drop: 2.4 VDC max. to last device
1.3 Installation Standards and Codes
The ACPS-2406 complies with the following standards:
NFPA 72 National Fire Alarm Code
Underwriters Laboratories:
• UL 864 Standard for Control Units for Fire Alarm Systems
In addition, the installer should be familiar with the following standards:
• NEC Article 300 Wiring Methods
• NEC Article 760 Fire Protective Signaling Systems
• Applicable Local and State Building Codes
• Requirements of the Local Authority Having Jurisdiction

Related Documentation Introduction
ACPS-2406 PN 51304:B 09/02/2003 9
1.4 Related Documentation
To obtain a complete understanding of specific features of the ACPS-2406, or to become familiar
with functions in general, make use of the documentation listed in Table 1.1
Table 1.1 Related Documentation
1.5 Board Layout
The ACPS-2406 board layout is illustrated in Figure 1.1. A second figure below the board layout
illustrates the positions of the LEDs.
Title Document Number
NFS-3030 Fire Alarm Control Panel 51330, 51344, 51345
NFS-640 Fire Alarm Control Panel 51332, 51333, 51334
AM2020/AFP-1010 Fire Alarm Control Panel 15088
AFP-100 Analog Fire Panel 51010
AFP-200 Analog Fire Panel 15511
AFP-300/AFP-400 Analog Fire Panel 50253, 50259, 50260
AFC-600 Analog Fire Control Panel 51031, 51032, 51033
UZC-256 (Universal Zone Coder) Installation Guide 15216
CAB-3 Series Installation Instructions 15330
CAB-PS1 Cabinet 51400
BB-25 Cabinet Installation Instructions 50898
XPIQ Audio Transponder 51013
SLC Wiring Instruction Manual 51253
Annunciator Control System 15842
ACM-8R Annunciator Control Module 15342
Annunciator Fixed Module 15048
LCD-80 Manual 15037
LDM Series Lamp Driver Annunciator 15885
Voice Alarm System Manual 51252
Device Compatibility Document 15378
UZC-256 Universal Zone Coder 15216
UZC-256 Programming 15976
UDACT Manual (Universal Digital Alarm Communicator) 50050
XP Transponders 15888
XP5 Series Transponders 50786
RM-1 Series Microphone 51138
AFAWS 50705
INA Intelligent Network Annunciator 15092

Introduction Board Layout
10 ACPS-2406 PN 51304:B 09/02/2003
Figure 1.1 The ACPS-2406 Board Layout
D54
D73
HOT NEUTRAL EARTH
D74
D47
TB5TB6TB8
TB1
TB3
TB2
TB4
D40 D32
D66
OU TPU T 1 4 WI R E
OU TPU T 2 4 W IR E
OUTPUT 3OUTPUT 4
SUP+ SUP-
UZC
+24 V CO MM +24 V RET U RN+24 V CO MM +24 V RET U RN
+24 V COMM +24 V COMM
SLCA SLCB
+ - + -
D67
F2
D68 D69
D70 D71
D72
D81
BATT IN BATT OUT BATT IN BATT OUT
OPTIONSOPTIONS
D75
+
+
__
87654 32187654321
ACPS-2406PCA
Rev _____
D54
D73
D74
D47 D40 D32
D66 D67
F2
D68 D69
D70 D71
D72
D81
OPTIONSOPTIONS
D75
8 765 432 187654321
CAUTION!
HIGHVOLTAGE
JP2 - Ground Fault
Disable - Cut this
jumper to disable
ground fault
detection.
Auxiliary Power
Supply
Rotary Switch
JP6
AC
SLC A
SLC B
-
-
+
+
UZCSUP +
-
NEUT
EARTH GROUND
BAT OUT
+
-
+
-
BAT OUT
BAT IN
BAT IN
+
Output 1
NAC 1
NAC 2
NAC 3
NAC 4
Locations of LED Indicators
Refer to Table 1.2 for
Indicator Descriptions
TRBL (Pulse-coded)
BAT/CHG
UC FAILURE
AC
GROUND FAULT
NAC 1 Activated
NAC 2 Activated
NAC 3 Activated
NAC 4 Activated
SLCTXA
SLCRXA
Battery Fuse
-
+
-
+
Output 2
-
+
-
+ OUT 4
-OUT 4
+OUT 3
-OUT 3
MONITOR
Flash Memory
SW2 DIP
Switches
SW3 DIP
Switches
Output 4
Output 3
Snap-on
cover for
TB1
terminals
Out 1
Out 1 4-Wire
Out 1 4-Wire
Out 2
Out 2 4-Wire
Out 2 4-Wire
UZCSUPRET Class A
Class A
Refer to Figure
3.1 and Table 3.1
Refer to Figure
3.1 and Table 3.1
acps6cplt.CDR
acps6brdtop.CDR
J1 +
-
1{
Coded input
(UZC or
synch. signal)
ACPS-2406PCA revision #
(handwritten on board)

LED Indicators Introduction
ACPS-2406 PN 51304:B 09/02/2003 11
1.6 LED Indicators
There are 16 LEDs that indicate various conditions and troubles. The following table lists and
describes each.
Table 1.2 LED Indicators
Reference LED Name Color Description
D19 GND FLT Yellow Illuminates when a ground fault is detected on any NAC,
battery lead, or 24-volt output.
D32 NAC 1 Activated Green Illuminates when NAC 1 is activated.
D40 NAC 2 Activated Green Illuminates when NAC 2 is activated.
D47 NAC 3 Activated Green Illuminates when NAC 3 is activated.
D54 NAC 4 Activated Green Illuminates when NAC 4 is activated.
D81 MONITOR Green Blinks steadily during normal polling process. Shuts off
when there is a monitor trouble.
D66 NAC 1 Green Glows steadily when communication is established with the
FACP. Blinks steadily during normal polling process.
D67 NAC 2 Green Glows steadily when communication is established with the
FACP. Blinks steadily during normal polling process.
D68 NAC 3 Green Glows steadily when communication is established with the
FACP. Blinks steadily during normal polling process.
D69 NAC 4 Green Glows steadily when communication is established with the
FACP. Blinks steadily during normal polling process.
D70 TRBL Yellow Illuminates when one of the following troubles occur: brownout;
+38 volt supply supervison; invalid address.
Blinks once, pauses, then blinks again, repeating this pattern for
brownout trouble.
Blinks twice, pauses, then blinks twice again, repeating this
pattern for +38 volt supply failure.
Blinks three times, pauses, then blinks three times again, repeating
this pattern. Panel programming does not match DIP Switch
settings.
D71 BAT/CHG Yellow Illuminates when there is a battery or charger trouble.
D72 UCFAILURE Yellow Illuminates if the microcontroller fails.
D75 AC Green Illuminates when there is AC power.
D73 SLCRXA Green Illuminates when data is transmitted on the SLC.
D74 SLCTXA Green Illuminates when data is received from the SLC.

Installation In a CAB-3 Series Cabinet
12 ACPS-2406 PN 51304:B 09/02/2003
Section 2 Installation
WARNING:High Voltages Present
Use extreme caution when working with the ACPS-2406. High voltage and AC line-connected
circuits are present in this power supply. Turn off and remove all power sources. To reduce
the risk of electric shock, make sure to properly ground the ACPS-2406.
Install the snap-on cover for TB1 after wiring.
2.1 In a CAB-3 Series Cabinet
The ACPS-2406 mounts in the lower left or lower right of CAB-3 Series enclosure. It will also
mount in a CHS-6 chassis, requiring the left two of the three chassis spaces, or in a CHS-PS
chassis, where it must be installed in the right half.
Figure 2.1 Mounting in a CAB-3 Series Cabinet
2.2 In a BB-25 Cabinet
The ACPS-2406 mounts in the left side of a
BB-25 cabinet. Two 7 to 25 amp-hour
batteries fit into the right side of the cabinet.
!
D54
D73
HOT NEUTRAL EARTH
D74
D47
TB5TB6TB8
TB1
TB3
TB2
TB4
D40 D32
D66
OUTPUT 1 4 WIREOUTPUT 2 4 WIREOUTP U T 3OUTP UT 4
SUP+ SUP-
UZC
+24V COMM +24V RETUR N+24V COMM +24VRETURN
+24VCOMM +24V COMM
SLCA SLCB
+ - + -
D67
F2
D68 D69
D70 D71
D72
D81
BATT IN BAT T OU T BATT IN B AT T O U T
OPTIONSOPTIONS
D75
+
+
__
8765432187654321
D54
D73
HOT NEUTRAL EARTH
D74
D47
TB5TB 6TB8
TB1
TB3
TB2
TB4
D40 D3 2
D66
OUTPUT 1 4 WIREOUTPUT 2 4 WIREOUTPUT 3OU TP U T 4
SUP+ SUP-
UZC
+24V COMM +24V RETUR N+24V COMM +24V RETURN
+24V COMM +2 4V COMM
SLCA SLCB
+ - + -
D67
F2
D68 D69
D70 D71
D72
D81
BATT IN BAT T OU T BATT IN B AT T O UT
OPTIONSOPTION S
D75
+
+
__
8765432187654321
D54
D73
HOT NEUTRAL EARTH
D74
D47
TB5TB6TB8
TB1
TB3
TB2
TB4
D40 D32
D66
OU TPUT 1 4 W IREOUT P UT 2 4 W IR EOUTPUT 3OUTPUT 4
SUP + SU P-
UZC
+24V COMM +24V RE TURN
+24VC OMM +24 V RE TURN+24V COMM +24V COMM
SLC A SLCB
+ - + -
D67
F2
D68 D69
D70 D71
D72
D81
BA T T IN B AT T O UT BA TT IN B A TT O UT
OPTIONSOPTIONS
D75
+
+
__
876543218765432 1
D54
D73
HOT NEU TR AL EART H
D74
D47
TB5TB6TB8
TB1
TB3
TB2
TB4
D40 D32
D66
OUT PUT 1 4 W IR EOUT P UT 2 4 W IR EO U T P U T 3OU TPUT 4
SUP+ S U P-
UZC
+24VC OMM +24 V RE TURN
+24V C OMM +24V RE TURN+24V COM M +24V CO MM
SLCA SLC B
+ - + -
D67
F2
D68 D69
D70 D71
D72
D81
BATT IN BATT O UT BATT IN BATT O UT
OPTIONSOPTIONS
D75
+
+
__
876 543 2187 65 43 2 1
Fasten the power
supply to the chassis
with hex nuts at these
positions
CHS-6 Chassis
CHS-PS Chassis
Fasten the power
supply to the chassis
with hex nuts at these
positions
CAB-3 Series Cabinet
The ACPS-2406 can fit in either
the lower left or lower right of
any CAB-3 Series cabinet.
Lower left
installation:
Slide the
power supply
chassis onto
the raised
cutouts on the
backbox
Lower right
installation:
Fasten the
power supply
to the backbox
with thread-
forming
screws.
acps6cab3.CDR
acps6chsps.CDR acps6chs6.CDR
D54
D73
D74
F2
OPTIONSOPTIONS
8765432187654321
Figure 2.2 Mounting in a BB-25 Cabinet
Fasten the power supply to the backbox
with screws (self-threading) at these
positions.
acps6bb25.CDR

In a CAB-PS1 Cabinet Installation
ACPS-2406 PN 51304:B 09/02/2003 13
2.3 In a CAB-PS1 Cabinet
The ACPS-2406 mounts in a CAB-PS1
cabinet. Two seven amp-hour batteries fit
into the bottom of this cabinet along with the
ACPS-2406. The chassis is fastened to the
two top right studs with two hex nuts.
2.4 Wiring
The terminal block and pin connections are illustrated in Figure 1.1.
Power-limited wiring must remain separated from nonpower-limited wiring by at least 0.25 in.
(6.4 mm), and must enter an enclosure through different knockouts. Samples for configuring
power-limited and nonpower-limited wiring in three different cabinets are shown in Figure 2.4,
Figure 2.5, and Figure 2.6.
Figure 2.4 BB-25 Cabinet: Power-limited Wiring Example, with Two Battery Wiring
D54
D73
HOT NEUTRAL EARTH
D74
D47
TB5TB6TB8
TB1
TB3
TB2
TB4
D40 D32
D66
OUTPUT 1 4 WIRE
OUTPUT 2 4 W IREOUTPUT 3OUTPUT 4
SUP+ SUP-
UZC
+24VCOMM +24V RETURN+24V COM M+2 4V R ETURN
+24V COMM + 24V COMM
SLCA SLCB
+ - + -
D67
F2
D68 D69
D70 D71
D72
D81
BATT IN BATTOUT B ATTIN BATT OUT
OPTIONSOPTIONS
D75
+
+
__
87654 32 18765 432 1
Fasten the
ACPS-2406
chassis to the
backbox
using the
studs with
hex nuts at
these
positions.
Figure 2.3 CAB-PS1 Mounting
acps6cabps1.CDR
D54
D73
D74
+24V COMM +24V RETURN+24V COMM +2 4V RETURN+ - + -
F2
OPTIONSOPTIONS
8765432187654321
++
TB1: AC Primary
Power Wiring -
nonpower-limited
and supervised.
Output Circuit Wiring - Power-limited
Supervised except for TB6: UZCSUP+, UZCSUPRET-
acps6pwrlmtd.CDR
TB2: Non power-limited and supervised

Installation Wiring
14 ACPS-2406 PN 51304:B 09/02/2003
Figure 2.5 CAB-3 Cabinet: Power-limited Wiring Example
Figure 2.6 CAB-PS1 Cabinet: Power-limited Wiring Example
TB1 - With all power sources off, connect primary AC power to the “AC” and “NEUT” terminals,
and ground the ACPS-2406 at the “EARTH GROUND” terminal.
D54
D73
HOT NEU TRAL EARTH
D74
D47
TB5TB6TB 8
TB1
TB3
TB2
TB4
D40 D32
D66
OUTPUT 1 4 W IR E
O UT P U T 2 4 WIREOUTPUT 3
OUTPUT 4
SUP+ SUP-
UZC
+24V COMM +24VRETURN+24V COMM +24VRETURN
+24V COMM +24VCOMM
SLCA SLCB
+ - + -
D67
F2
D68 D69
D70 D71
D72
D81
BAT T I N B A T T O U T BAT T IN B A T TO U T
OPTIONSOPTIONS
D75
+
+
__
8765432187654321
Output Circuit Wiring -
Power-limited
Supervised except for
TB6: UZCSUP+, UZCSUPRET-
TB1: AC Primary
Power Wiring -
nonpower-limited
and supervised.
acps6cab3wiring.CDR
D54
D73
HOT NEUTRAL EARTH
D74
D47
TB5TB6TB8
TB1
TB3
TB2
TB4
D40 D3 2
D66
OUTPUT 1 4 WIRE
OUTP UT 2 4 WIREOUTPUT 3OUTPUT 4
SUP+ SU P-
UZC
+24V COMM+24V RETURN+24VCOMM +24V RETURN
+24V COMM+24V COMM
SLCA SLCB
+ - + -
D67
F2
D68 D69
D70 D71
D72
D81
BATT IN BATT OUT BATTIN BATT OUT
OPTIONSOPTIONS
D75
+
+
__
87 65 4 32187654321
TB1: AC
Primary Power
Wiring -
nonpower-limited
and supervised.
Output Circuit Wiring - Power-limited
Supervised except for TB6: UZCSUP+, UZCSUPRET-
Two 12V, 7AH lead acid batteries will
fit into the CAB-PS1 enclosure with the
ACPS-2406. Do not use the
ACPS-2406 with batteries rated at
lower than 7 AH.
ACPS6CABPS1wiring.cdr
TB2: Non power-limited and supervised

Wiring Installation
ACPS-2406 PN 51304:B 09/02/2003 15
.
WARNING: Install the snap-on cover for TB1
after wiring. Refer to Figure 2.7 for cover
installation
TB2, TB3 - The lead-acid battery charger will charge 7 to 25 AH batteries. Connect two batteries
to these terminals as illustrated in Figure 2.4. Leave the battery interconnect cables disconnected
until after system power-up.
TB4, TB5, TB6 - Outputs 1 through 4 and UZC-256 connections. With all power sources off,
connect wiring. Refer to Section Four of this manual for applications suggestions. Outputs 1
through 4 share 6.0 A of output power when configured as NACs, or 5.0 A of 24VDC detector
power or general purpose power.
TB8 - SLC Wiring. Connect to panel Signaling Line Circuit.
J1 - Auxiliary power connection, 0.50A, +24VDC, unsupervised output for connection within the
same cabinet. When this output is used for an installation, the maximum load current available at
Output #4 (TB6-3 and TB6-4) will be reduced to 2.0 A maximum.
To determine battery requirements, refer to Section 5 of this manual.
CAUTION !
HIGH VOLTAGE
Figure 2.7 Installing the TB1 Snap-on Cove
r
CAUTION!
HIGHVOLTAGE
TB1
Press fit the snap-on cover over TB1
after AC power has been connected.
Snap-on cover
accover.CDR
accovinst.CDR
!

Configuring the ACPS-2406 DIP Switch Configuration
16 ACPS-2406 PN 51304:B 09/02/2003
Section 3 Configuring the ACPS-2406
3.1 DIP Switch Configuration
Programming at the ACPS-2406 is done by configuring two sets of DIP switches, SW2 and SW3. SW3 is
a set of mode selection switches for output circuits one through four, as well as AC Loss, AC Delay, settings
for coded NAC patterns, Canadian Trouble Reporting, and Dual Stage operation. SW2 is a set of switches
with various mode options for the output circuits, as well as settings for Signal Silence, strobe
synchronization type, and battery charger. Setting these 16 switches in different configurations will provide
various options as described in Table 3.1.
SW2 and SW3 are horizontally aligned on the ACPS-2406 board just above the metal case which
covers the bottom half of the power supply. To place a switch in the OFF position, depress the end
of the switch closest to the metal case. To place a switch in the ON position, depress the end of the
switch farthest from the metal case. Refer to Figure 3.1 below for an illustration of the OFF and
ON positions. Table 3.1 describes the ACPS-2406 DIP Switch settings.
Figure 3.1 Setting a DIP Switch
Note: DIP Switch settings should be changed only while the ACPS-2406 is powered down.
OPTION S
OPTION S
87654321
87654321
OFF
1 2 3 4 5 6 7 8
SW3
SW2
Switch 1 is OFF. The
end of the switch near the
metal case has been
depressed.
Metal
Case
Switches 2 through 8 are
ON. The end of the
switch farthest from the
metal case has been
depressed.
Metal Case
acps6DIPs.CDR
acps6DIPon.CDR

DIP Switch Configuration Configuring the ACPS-2406
ACPS-2406 PN 51304:B 09/02/2003 17
Table 3.1 DIP Switch Settings
Switch SW3 ON OFF
3.1* Output Circuit 1 = 24 VDC, non-supervised Output Circuit 1 =NAC
3.2* Output Circuit 2 = 24 VDC, non-supervised Output Circuit 2 = NAC
3.3* Output Circuit 3 = 24 VDC, non-supervised Output Circuit 3 = NAC
3.4* Output Circuit 4 = 24 VDC, non-supervised Output Circuit 4 = NAC
3.5, 3.6 3.5 OFF, 3.6 OFF = US AC Delay OFF
3.5 OFF, 3.6 ON = US 8 hour AC Delay
3.5 ON, 3.6 OFF = US 16 hour AC Delay
3.5 ON, 3.6 ON = Canadian Trouble Reporting
3.7, 3.8 3.7 3.8 Below: Coded or Non-coded as defined by SW2.1, 2.2, 2.3, 2.4
CODED NON-CODED
ON ON March Time (120 ppm) Output will synchronize to a non-coded input at the UZC
connections of TB6: or use SW2.6 or 2.7 settings.
ON OFF Dual Stage** Invalid Condition - When Dual Stage is selected, all outputs
are forced to coded.
OFF OFF Temporal Pattern Output will synchronize to a non-coded input at the UZC
connections of TB6: or use SW2.6 or 2.7 settings.
OFF ON Follow the UZC Universal Zone Coder
Signal at the UZC connections of TB6
Non-coded outputs will use the protocol selected by SW2.6
and 2.7.***
* Use these switches in conjunction with switches 2.1, 2.2, 2.3, and 2.4 to further define the NAC or 24 VDC circuit.
** Canadian Dual Stage must have DIP Switches 3.5 and 3.6 set to ON (Canadian Trouble Reporting), and Output Circuits 1-4 must be set to NAC.
***CAUTION: FOR NON-CODED MASTER/SLAVE OPERATION: when a non-coded signal is supplied to the UZC connections of
TB6, the same protocol must also be programmed at the slave ACPS-2406 (using SW2.6 and SW2.7) as programmed at the master
ACPS-2406. This will ensure operation of all non-coded outputs of the slave ACPS-2406 should signal loss occur of the synchronization
input (UZC connections) at TB6.
Switch SW2 ON OFF
2.1 Output Circuit 1 is:
• coded, if configured as NAC with SW3.1
• resettable, if configured as 24VDC power
circuit with SW3.1
Output Circuit 1 is:
• noncoded, if configured as NAC with SW3.1
• nonresettable, if configured as 24VDC power
circuit with SW3.1
2.2 Output Circuit 2 is:
• coded, if configured as NAC with SW3.2
• resettable, if configured as 24VDC power
circuit with SW3.2
Output Circuit 2 is:
• noncoded, if configured as NAC with SW3.2
• nonresettable, if configured as 24VDC power
circuit with SW3.2
2.3 Output Circuit 3 is:
• coded, if configured as NAC with SW3.3
• resettable, if configured as 24VDC power
circuit with SW3.3
Output Circuit 3 is:
• noncoded, if configured as NAC with SW3.3
• nonresettable, if configured as 24VDC power
circuit with SW3.3
2.4 Output Circuit 4 is:
• coded, if configured as NAC with SW3.4
• resettable, if configured as 24VDC power
circuit with SW3.4
Output Circuit 4 is:
• noncoded, if configured as NAC with SW3.4
• nonresettable, if configured as 24VDC power
circuit with SW3.4
2.5 Electronic Signal Silence* No Electronic Signal Silence
2.6, 2.7 Strobe Synchronization Type**
2.6 ON, 2.7 ON = Wheelock
2.6 ON, 2.7 OFF = Gentex
2.6 OFF, 2.7 ON = System Sensor
2.6 OFF, 2.7 OFF = No synchronization
2.8 Disable Battery Charger Enable Battery Charger
*The FACP requires the addition of one virtual address when this option is used. This extra address is specifically for Electronic Signal
Silence only and should be configured in the panel as a “silenceable output”, activated by CBE. The Electronic Signal Silence option is an
“all or none” option and is used with Gentex, System Sensor and Wheelock synchronized devices; all addressed NACs will silence when
this option is activated. When synchronized strobes are used, the horns will mute, but the strobes will remain active.
**Strobe Synchronization only works with non-coded NACs.
Note: AM2020/AFP-1010 - Do not use PWRC Type Code for any ACPS-2406 address.

Configuring the ACPS-2406 Addressing
18 ACPS-2406 PN 51304:B 09/02/2003
The DIP Switch configurations chosen determine the ACPS-2406 address consumption. Refer to
Table 3.2 through Table 3.7 for illustrations of the DIP Switch/address consumption relationship.
3.2 Addressing
The installer must set aside sequential SLC addresses (an address block) equal to the number of
addresses that will be consumed by the ACPS-2406. Determing the size of the address block and
setting the SLC base address is described in this section.
Determining Address Consumption
An ACPS-2406 can occupy an address block of 5, 6, 8, 9, 12, or 13 addresses on an SLC, depending on the
configuration of ACPS-2406 DIP Switches. Table 3.2 through Table 3.7 below detail the DIP Switch/
address consumption relationship. Compare the actual DIP Switch settings with the tables: a match will
give the total number of SLC addresses necessary for the address block.
Refer to “Setting the Base Address” for information on the SLC Base Address.
Table 3.2 DIP Switch Settings Resulting in 5 Addresses Consumed
Table 3.3 DIP Switch Settings Resulting in 6 Addresses Consumed
DIP
Switch DIP Switch Setting ACPS-2406 Addresses Selected
by DIP Switch Settings at Left ACPS-2406 Addresses SLC
Address
SW3.1 ON or OFF ✔1.Monitor General B*
SW3.2 ON or OFF ✔2. ACPS-2406 Output #1 B + 1
SW3.3 ON or OFF ✔3. ACPS-2406 Output #2 B + 2
SW3.4 ON or OFF ✔4. ACPS-2406 Output #3 B + 3
SW3.5 Any combination except 3.5 ON, 3.6 ON
(Canadian Trouble Reporting)
✔5. ACPS-2406 Output #4 B + 4
SW3.6
Not selected.
6. Signal Silence Address
SW3.7 Any combination except 3.7 ON, 3.8 OFF
(Dual Stage)
7. Monitor AC Fail (Canada only)
SW3.8 8. Monitor Battery (Canada only)
9. Monitor Earth Fault (Canada only)
SW2.1 ON or OFF 10. Dual Stage Output #1
SW2.2 ON or OFF 11. Dual Stage Output #2
SW2.3 ON or OFF 12. Dual Stage Output #3
SW2.4 ON or OFF 13. Dual Stage Output #4
SW2.5 OFF Total: 5 Addresses
Assign 5 sequential SLC
addresses for this DIP Switch
configuration.
*B =SLC
Base
Address
SW2.6 ON or OFF
SW2.7 ON or OFF
SW2.8 ON or OFF
DIP
Switch DIP Switch Setting ACPS-2406 Addresses Selected
by DIP Switch Settings at Left ACPS-2406 Addresses SLC
Address
SW3.1 ON or OFF ✔1.Monitor General B*
SW3.2 ON or OFF ✔2. ACPS-2406 Output #1 B + 1
SW3.3 ON or OFF ✔3. ACPS-2406 Output #2 B + 2
SW3.4 ON or OFF ✔4. ACPS-2406 Output #3 B + 3
SW3.5 Any combination except 3.5 ON, 3.6 ON
(Canadian Trouble Reporting)
✔5. ACPS-2406 Output #4 B + 4
SW3.6 ✔6. Signal Silence Address B + 5
SW3.7 Any combination except 3.7 ON, 3.8 OFF
(Dual Stage)
Not selected.
7. Monitor AC Fail (Canada only)
SW3.8 8. Monitor Battery (Canada only)
9. Monitor Earth Fault (Canada only)
SW2.1 ON or OFF 10. Dual Stage Output #1
SW2.2 ON or OFF 11. Dual Stage Output #2
SW2.3 ON or OFF 12. Dual Stage Output #3
SW2.4 ON or OFF 13. Dual Stage Output #4
SW2.5 ON Total: 6 Addresses
Assign 6 sequential SLC
addresses for this DIP Switch
configuration.
*B = SLC
Base
Address
SW2.6 ON or OFF
SW2.7 ON or OFF
SW2.8 ON or OFF

Addressing Configuring the ACPS-2406
ACPS-2406 PN 51304:B 09/02/2003 19
Table 3.4 DIP Switch Settings Resulting in 8 Addresses Consumed
Table 3.5 DIP Switch Settings Resulting in 9 Addresses Consumed
Table 3.6 DIP Switch Settings Resulting in 12 Addresses Consumed
DIP
Switch DIP Switch Setting ACPS-2406 Addresses Selected
by DIP Switch Settings at Left ACPS-2406 Addresses SLC
Address
SW3.1 ON or OFF ✔1.Monitor General B*
SW3.2 ON or OFF ✔2. ACPS-2406 Output #1 B + 1
SW3.3 ON or OFF ✔3. ACPS-2406 Output #2 B + 2
SW3.4 ON or OFF ✔4. ACPS-2406 Output #3 B + 3
SW3.5 3.5 ON, 3.6 ON (Canadian Trouble
Reporting)
✔5. ACPS-2406 Output #4 B + 4
SW3.6 Not selected. 6. Signal Silence Address
SW3.7 Any combination except 3.7 ON, 3.8 OFF
(Dual Stage)
✔7. Monitor AC Fail (Canada only) B + 5
SW3.8 ✔8. Monitor Battery (Canada only) B + 6
✔9. Monitor Earth Fault (Canada only) B + 7
SW2.1 ON or OFF
Not selected.
10. Dual Stage Output #1
SW2.2 ON or OFF 11. Dual Stage Output #2
SW2.3 ON or OFF 12. Dual Stage Output #3
SW2.4 ON or OFF 13. Dual Stage Output #4
SW2.5 OFF Total: 8 Addresses
Assign 8 sequential SLC
addresses for this DIP Switch
configuration.
*B = SLC
Base
Address
SW2.6 ON or OFF
SW2.7 ON or OFF
SW2.8 ON or OFF
DIP
Switch DIP Switch Setting ACPS-2406 Addresses Selected
by DIP Switch Settings at Left ACPS-2406 Addresses SLC
Address
SW3.1 ON or OFF ✔1.Monitor General B*
SW3.2 ON or OFF ✔2. ACPS-2406 Output #1 B + 1
SW3.3 ON or OFF ✔3. ACPS-2406 Output #2 B + 2
SW3.4 ON or OFF ✔4. ACPS-2406 Output #3 B + 3
SW3.5 3.5 ON, 3.6 ON (Canadian Trouble
Reporting)
✔5. ACPS-2406 Output #4 B + 4
SW3.6 ✔6. Signal Silence Address B + 5
SW3.7 Any combination except 3.7 ON, 3.8 OFF
(Dual Stage)
✔7. Monitor AC Fail (Canada only) B + 6
SW3.8 ✔8. Monitor Battery (Canada only) B + 7
✔9. Monitor Earth Fault (Canada only) B + 8
SW2.1 ON or OFF
Not selected.
10. Dual Stage Output #1
SW2.2 ON or OFF 11. Dual Stage Output #2
SW2.3 ON or OFF 12. Dual Stage Output #3
SW2.4 ON or OFF 13. Dual Stage Output #4
SW2.5 ON Total:9 Addresses
Assign 9 sequential SLC
addresses for this DIP Switch
configuration.
*B = SLC
Base
Address
SW2.6 ON or OFF
SW2.7 ON or OFF
SW2.8 ON or OFF
DIP
Switch DIP Switch Setting ACPS-2406 Addresses Selected
by DIP Switch Settings at Left ACPS-2406 Addresses SLC
Address
SW3.1 ON or OFF ✔1.Monitor General B*
SW3.2 ON or OFF ✔2. ACPS-2406 Output #1 B + 1
SW3.3 ON or OFF ✔3. ACPS-2406 Output #2 B + 2
SW3.4 ON or OFF ✔4. ACPS-2406 Output #3 B + 3
SW3.5 3.5 ON, 3.6 ON (Canadian Trouble
Reporting)
✔5. ACPS-2406 Output #4 B + 4
SW3.6 Not selected. 6. Signal Silence Address
SW3.7 3.7 ON, 3.8 OFF (Dual Stage) ✔7. Monitor AC Fail (Canada only) B + 5
SW3.8 ✔8. Monitor Battery (Canada only) B + 6
✔9. Monitor Earth Fault (Canada only) B + 7
SW2.1 ON or OFF ✔10. Dual Stage Output #1 B + 8
SW2.2 ON or OFF ✔11. Dual Stage Output #2 B + 9
SW2.3 ON or OFF ✔12. Dual Stage Output #3 B + 10
SW2.4 ON or OFF ✔13. Dual Stage Output #4 B + 11
SW2.5 OFF Total:12 Addresses
Assign 12 sequential SLC
addresses for this DIP Switch
configuration.
*B = SLC
Base
Address
SW2.6 ON or OFF
SW2.7 ON or OFF
SW2.8 ON or OFF

Configuring the ACPS-2406 Addressing
20 ACPS-2406 PN 51304:B 09/02/2003
Table 3.7 DIP Switch Settings Resulting in 13 Addresses Consumed
Setting the Base Address
The combined rotary switch (SW1) and address jumper (JP6) settings select the base address, the
first address of the block of SLC addresses used. The address block will begin at a number that
ends in zero or five depending on the settings, and extend beyond that number to fulfill the
ACPS-2406 address requirements. All addresses included in the address block must be
programmed points at the FACP whether or not the output points are actually used.
Note: The lowest base address for the ACPS-2406 is 05. Do not set the FACP addresses 00 through 04 for the ACPS-2406.
The Rotary Switch
The rotary switch SW1 determines the address decade. Each number on the dial represents the ten
addresses of a decade. Turning the arrow until it points at a number selects that number’s decade.
For example:
Pointing the arrow at the 1 selects the “one” address decade, beginning at 10.
Pointing the arrow at the 12 selects the “twelve” address decade, beginning at 120.
JP6
The three pins of JP6 are used in conjunction with a shunt plug to further define the addresses.
They select the number that ends with zero or five in the decade defined by the rotary switch.
Placing the shunt plug over the two pins closest to the 0 selects the number with zero at the end as
the first address. Placing the shunt plug over the two pins closest to the 5 selects the number with
five at the end as the first address.
DIP
Switch DIP Switch Setting ACPS-2406 Addresses Selected
by DIP Switch Settings at Left ACPS-2406 Addresses SLC
Address
SW3.1 ON or OFF ✔1.Monitor General B*
SW3.2 ON or OFF ✔2. ACPS-2406 Output #1 B + 1
SW3.3 ON or OFF ✔3. ACPS-2406 Output #2 B + 2
SW3.4 ON or OFF ✔4. ACPS-2406 Output #3 B + 3
SW3.5 3.5 ON, 3.6 ON (Canadian Trouble
Reporting)
✔5. ACPS-2406 Output #4 B + 4
SW3.6 ✔6. Signal Silence Address B + 5
SW3.7 3.7 ON, 3.8 OFF (Dual Stage) ✔7. Monitor AC Fail (Canada only) B + 6
SW3.8 ✔8. Monitor Battery (Canada only) B + 7
✔9. Monitor Earth Fault (Canada only) B + 8
SW2.1 ON or OFF ✔10. Dual Stage Output #1 B + 9
SW2.2 ON or OFF ✔11. Dual Stage Output #2 B + 10
SW2.3 ON or OFF ✔12. Dual Stage Output #3 B + 11
SW2.4 ON or OFF ✔13. Dual Stage Output #4 B + 12
SW2.5 ON Total:13 Addresses
Assign 13 sequential SLC
addresses for this DIP Switch
configuration.
*B =SLC
Base
Address
SW2.6 ON or OFF
SW2.7 ON or OFF
SW2.8 ON or OFF
S1W
1
0
5
7
8
62
3
4
9
11
10 14
12 13
15
S1W
1
0
5
7
8
62
3
4
9
11
10 14
12 13
15
rotarysw.CDR
Other manuals for ACPS-2406
1
Table of contents
Other Notifier Power Supply manuals
Popular Power Supply manuals by other brands

Osram
Osram OPTOTRONIC OT Wi 35/220-240/400 D NFC CA L manual

Delta Elektronika
Delta Elektronika SM15K Series quick start

Radient RC
Radient RC Reaktor Series owner's manual

Fisher Scientific
Fisher Scientific Midi300V/4 instruction manual

OCZ
OCZ OCZ500SXS - MECHANICAL DRAWING Mechanical drawing

Solar Stik
Solar Stik G-BOSS E LIGHT Operation and maintenance manual