Notifier APS-6R User manual

PN 50702:B2 ECN 03-147
Auxiliary Power Supply
APS-6R
Instruction Manual
Document 50702
4/14/03 Rev: B2
www.PDF-Zoo.com
firealarmresources.com

2 PN 50702:B2 4/14/03
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control panel
with remote notification capability—can provide early
warning of a developing fire. Such a system, however,
does not assure protection against property damage or
loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise fol-
lowing the recommendations of the current edition of the
National Fire Protection Association Standard 72-1999
(NFPA 72-1999), manufacturer's recommendations,
State and local codes, and the recommendations con-
tained in the Guide for Proper Use of System Smoke
Detectors, which is made available at no charge to all
installing dealers. A study by the Federal Emergency
Management Agency (an agency of the United States
government) indicated that smoke detectors may not go
off in as many as 35% of all fires. While fire alarm sys-
tems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire.
A fire alarm system may not provide timely or adequate
warning, or simply may not function, for a variety of rea-
sons:
Smoke detectors may not sense fire where smoke can-
not reach the detectors such as in chimneys, in or
behind walls, on roofs, or on the other side of closed
doors. Smoke detectors also may not sense a fire on
another level or floor of a building. A second-floor detec-
tor, for example, may not sense a first-floor or basement
fire.
Particles of combustion or “smoke” from a develop-
ing fire may not reach the sensing chambers of smoke
detectors because:
• Barriers such as closed or partially closed doors,
walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not
reach the ceiling or upper walls where detectors are
located.
• Smoke particles may be blown away from detectors
by air outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of “smoke” present may be insufficient to
alarm smoke detectors. Smoke detectors are designed
to alarm at various levels of smoke density. If such den-
sity levels are not created by a developing fire at the
location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have
sensing limitations. Detectors that have photoelectronic
sensing chambers tend to detect smoldering fires better
than flaming fires, which have little visible smoke.
Detectors that have ionizing-type sensing chambers
tend to detect fast-flaming fires better than smoldering
fires. Because fires develop in different ways and are
often unpredictable in their growth, neither type of
detector is necessarily best and a given type of detector
may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide ade-
quate warning of fires caused by arson, children playing
with matches (especially in bedrooms), smoking in bed,
and violent explosions (caused by escaping gas,
improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion
and alarm only when heat on their sensors increases at
a predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in
the same room as the control panel and in rooms used
by the system for the connection of alarm transmission
wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may dam-
age the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert
people with a disability or those who have recently con-
sumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause sei-
zures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or com-
prehend the meaning of the signal. It is the property
owner's responsibility to conduct fire drills and other
training exercise to make people aware of fire alarm
signals and instruct them on the proper reaction to
alarm signals.
• In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electri-
cal power. If AC power fails, the system will operate
from standby batteries only for a specified time and only
if the batteries have been properly maintained and
replaced regularly.
Equipment used in the system may not be technically
compatible with the control panel. It is essential to use
only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from
a premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmis-
sion systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards. At a minimum, the
requirements of Chapter 7 of NFPA 72-1999 shall be fol-
lowed. Environments with large amounts of dust, dirt or
high air velocity require more frequent maintenance. A
maintenance agreement should be arranged through
the local manufacturer's representative. Maintenance
should be scheduled monthly or as required by National
and/or local fire codes and should be performed by
authorized professional fire alarm installers only. Ade-
quate written records of all inspections should be kept.
Precau-S-4-2003.fm
www.PDF-Zoo.com
firealarmresources.com

PN 50702:B2 4/14/03 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can
be connected to the fire alarm control panel. Discon-
nect all sources of power before servicing. Control unit
and associated equipment may be damaged by remov-
ing and/or inserting cards, modules, or interconnecting
cables while the unit is energized. Do not attempt to
install, service, or operate this unit until this manual is
read and understood.
CAUTION - System Reacceptance Test after Soft-
ware Changes. To ensure proper system operation, this
product must be tested in accordance with NFPA 72-
1999 Chapter 7 after any programming operation or
change in site-specific software. Reacceptance testing
is required after any change, addition or deletion of sys-
tem components, or after any modification, repair or
adjustment to system hardware or wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be
100% tested. In addition, to ensure that other operations
are not inadvertently affected, at least 10% of initiating
devices that are not directly affected by the change, up
to a maximum of 50 devices, must also be tested and
proper system operation verified.
This system meets NFPA requirements for operation at
0°C to 49°C (32° F to 120° F) and at a relative humidity
(noncondensing) of 85% at 30°C (86°F) per NFPA, and
93%+ 2% at 32°C + 2°C (89.6°F + 1.1°F) per ULC.
However, the useful life of the system's standby batter-
ies and the electronic components may be adversely
affected by extreme temperature ranges and humidity.
Therefore, it is recommended that this system and all
peripherals be installed in an environment with a nomi-
nal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate
more than a 10% I.R. drop from the specified device
voltage.
Like all solid state electronic devices, this system
may operate erratically or can be damaged when sub-
jected to lightning-induced transients. Although no sys-
tem is completely immune from lightning transients and
interferences, proper grounding will reduce susceptibil-
ity. Overhead or outside aerial wiring is not recom-
mended, due to an increased susceptibility to nearby
lightning strikes. Consult with the Technical Services
Department if any problems are anticipated or encoun-
tered.
Disconnect AC power and batteries prior to removing
or inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When pos-
sible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit
board location.
Do not tighten screw terminals more than 9 in-lbs.
Overtightening may damage threads, resulting in
reduced terminal contact pressure and difficulty with
screw terminal removal.
Though designed to last many years, system compo-
nents can fail at any time. This system contains static-
sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that
static charges are removed from the body. Use static-
suppressive packaging to protect electronic assemblies
removed from the unit.
Follow the instructions in the installation, operating,
and programming manuals. These instructions must be
followed to avoid damage to the control panel and asso-
ciated equipment. FACP operation and reliability
depend upon proper installation by authorized person-
nel.
Precau-S-4-2003.fm
FCC Warning
WARNING: This equipment generates, uses, and
can radiate radio frequency energy and if not
installed and used in accordance with the instruction
manual, may cause interference to radio communi-
cations. It has been tested and found to comply with
the limits for class A computing device pursuant to
Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against
such interference when operated in a commercial
environment. Operation of this equipment in a resi-
dential area is likely to cause interference, in which
case the user will be required to correct the interfer-
ence at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital appa-
ratus set out in the Radio Interference Regulations of
the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables
aux appareils numeriques de la classe A prescrites
dans le Reglement sur le brouillage radioelectrique
edicte par le ministere des Communications du
Canada.
Acclimate Plus™, AWACS™, HARSH™, NOTI•FIRE•NET™, ONYX™, and VeriFire™ are
trademarks, and FlashScan® and VIEW®are registered trademarks of NOTIFIER. NION™ and
UniNet™ are trademarks of NIS. NIS™ and Notifier Integrated Systems™ are trademarks and
NOTIFIER® is a registered trademark of Fire•Lite Alarms, Inc. Echelon® is a registered trademark
and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of
Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft
Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric
Company.
www.PDF-Zoo.com
firealarmresources.com

4 PN 50702:B2 4/14/03
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and
accurate. If you have any comments or suggestions about our online
Help or printed manual, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed material)
• Brief description of content you think should be improved or
corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
TechPubs@fla-whq.com
Please note this email address is for documentation feedback only. If
you have any technical issues, please contact Technical Services.
www.PDF-Zoo.com
firealarmresources.com

Table of Contents
PN 50702:B2 4/14/03 5
Section 1 Overview ...................................................................................................7
Introduction .........................................................................................7
Description ..........................................................................................7
Specifications ......................................................................................9
Section 2 Installation .............................................................................................11
Introduction ....................................................................................... 11
Mounting in CAB-3/CAB-4 Series Cabinets ....................................12
Instructions for mounting: .......................................................12
Chassis Mounting .....................................................................12
Wiring the APS-6R ...........................................................................13
Field Wiring an APS-6R ...........................................................13
Connecting Multiple APS-6R Power Supplies .........................15
Wiring Applications ..........................................................................16
Connecting the APS-6R to an ICM/ICE Module .....................16
Supplying Power to a Control Module .....................................17
Configuring the APS-6R ...................................................................18
Servicing the APS-6R .......................................................................19
Appendix A AFP-200 .............................................................................................20
Mounting an APS-6R to an AFP-200 Backbox ................................20
Connecting the APS-6R to an AFP-200 Power Supply ....................21
Appendix B AFP-300/AFP-400 ............................................................................22
Mounting an APS-6R in a CAB-400AA Backbox ...........................22
Connecting the APS-6R to an MPS-400 ...........................................23
Appendix C AFC-600 ............................................................................................24
Mounting an APS-6R in a CAB-600AA Backbox ...........................24
Connecting the APS-6R to an MPS-6 ...............................................24
Appendix D System 500 .........................................................................................25
Mounting an APS-6R in a CAB-500 Backbox .................................25
Connecting the APS-6R to an MPS-24BRB .....................................25
Appendix E System 5000, AM2020/AFP-1010 ....................................................26
Mounting an APS-6R in a System 5000, AM2020 or AFP-1010 ....26
Connecting the APS-6R to an MPS-24A ..........................................26
Connecting the APS-6R to an MPS-24BRB .....................................26
Appendix F NFS-640 .............................................................................................27
Mounting an APS-6R in a Chassis ...................................................27
Connecting the APS-6R to an NFS-640 ...........................................27
Appendix G NFS-3030 ..........................................................................................28
Mounting an APS-6R in a Chassis ...................................................28
Connecting to the AMPS-24 and CPU-3030 ....................................28
www.PDF-Zoo.com
firealarmresources.com

6 PN 50702:B2 4/14/03
www.PDF-Zoo.com
firealarmresources.com

Section 1 Overview
PN 50702:B2 4/14/03 7
Section 1 Overview
Introduction
This document contains information for installing, servicing, and
configuring the APS-6R Auxiliary Power Supply. The table below
contains a list of document sources for supplemental information:
Table 1 Supplemental Documentation
Description
The APS-6R Auxiliary Power Supply is a 150W cabinet-mounted
power supply, designed to power devices that require filtered,
regulated, non-resettable power, such as XP Transponder modules,
Notification Appliance Circuit Modules and Control Modules. The
APS-6R provides three 24 VDC (filtered) output circuits.
Figure 1 APS-6R Auxilliary Power Supply
Control Panels Refer to... Part Number
NFS-3030 NFS-3030 Installation Manual 51330
NFS-640 NFS-640 Installation Manual 51332
System 500 System 500 Manual 15019
System 5000 System 5000 Manual 15583
AFP-200 AFP-200 Instruction Manual 15511
AFP-300/AFP-400 AFP-300/AFP-400 Installation Manual 50253
AFC-600 AFC-600 Installation Manual 51031
AM2020/AFP-1010 AM2020/AFP-1010 Manual 15088
XPIQ Transponder XPIQ Manual 51013
XP Series Transponder XP Series Manual 15888
XP5 Series Transponder XP5 Series Manual 50786
All Notifier Device Compatibility Document 15378
APS-6Risoview.cdr
APS-6R
with Cover
APS-6Rnocover.cdr
Control
board
Main Board
www.PDF-Zoo.com
firealarmresources.com

Section 1 Overview
8 PN 50702:B2 4/14/03
The figures below identify the features of the APS-6R power supply:
Figure 2 APS-6R Control Board
Figure 3 APS-6R Main Board
J2
J9
J3
J1
TB2
TB3
TB1
JP3
JP2
Fuse F1 for AC protection
(4A, 3AG, slow blow)
Three 24 VDC output circuits
One (1) non power-limited
Two (2) power-limited
(Refer to Figure 5 on page
page 14 for more specific
information on output circuits)
Trouble In (J4) - Trouble Out (J3)
“P” style connectors for internal cabinet
connections
LED Status Indicators:
Green LED – Indicates AC power on
Yellow LED – Indicates loss of AC or
battery
Fuse F2 for battery protection
(10A, 3AG, slow blow) Jumpers JP2 and JP3 for selecting
8-hour or 16-hour delay for AC loss
reporting. Default is immediate. See
Page 18 in "Configuring the APS-6R".
APS-6Rsidebrd.cdr
JP1
Jumper JP1 for selecting AC input voltage
(120 VAC default). See Page 18 in "Configuring the APS-6R".
WARNING: HIGH VOLTAGE. For 240 VAC operation,
cut JP1 before connecting power.
APS-6Rboard.cdr
www.PDF-Zoo.com
firealarmresources.com

Section 1 Overview
PN 50702:B2 4/14/03 9
Specifications
The APS-6R is compatible with the NFS-3030, NFS-640, AM2020,
AFP-1010, AFC-600, AFP-400, AFP-300, AFP-200, System 5000,
and System 500 control panels. Specifications for the APS-6R are:
Table 2 APS-6R Specifications
Electrical Specifications
AC Primary Input Power
Wire Size: #14 AWG with
600 VAC insulation
120 VAC, 60 Hz, 2.5 A
240 VAC, 50 Hz, 1.2 A
24 VDC Secondary Input Power
(lead-acid batteries only)
25 mA DC standby current
16 mA DC standby current (with AC fail delay
operating)
Note: The APS-6R is not equipped with a battery charger. Batteries are charged
by the system power supply.
24 VDC output power
Circuit 1
Circuit 2
Circuit 3
Total 6 A (4 A continuous)
3 A @24 VDC power-limited (+10, –15%)
3 A @24 VDC power-limited (+10, –15%)
6 A @24 VDC non power-limited (+10, –15%)
Fuses
F1 (AC supervision)
F2 (battery supervision)
250 VAC, 4A, 3 AG, slow blow
32 VAC, 10 A, 3 AG, slow blow
Trouble supervision bus
J3 output
J4 input
Note: J3 and J4 can be
interchanged.
Form A contact (open collector)
Form A contact (open collector)
Loss of AC Indication Immediate indication (default)
8 or 16 hour delay
Mechanical Specifications
Size of APS-6R Inches:6.09 x 4.23. x 2.92 (mm:154.7 x 107.4 x 74.2)
Cabinets for mounting CAB-3/CAB-4 Series for NFS-3030, NFS-640,
AM2020, AFP-1010, AFC-600, AFP-300,
AFP-400, and System 5000 control panels.
CAB-400AA for AFP-300 and AFP-400 control
panels; accepts one APS-6R.
CAB-600AA for AFC-600 control panels;
accepts one APS-6R.
AFP-200 backbox; accepts one APS-6R.
CAB-500 Can mount one APS-6R.
Note: An optional module (such as an ICM) without an expansion card can mount above
an APS-6R in a CHS-4 Series chassis, a CAB-500, CAB-600AA and a CAB-400AA.
www.PDF-Zoo.com
firealarmresources.com

Section 1 Overview
10 PN 50702:B2 4/14/03
Parts Kit
A parts kit is included for use in assembling and mounting the
APS-6R. It consists of the following items:
Quantity Description Part No.
1 AC Power connector cover 02183
2 #6-32 1.25 in. (10 mm) long, .25
in. (2mm) hex standoff
42026
2 #6-32 self-tapping screw 38118
1 Trouble supervision cable 71033
www.PDF-Zoo.com
firealarmresources.com

Section 2 Installation
PN 50702:B2 4/14/03 11
Section 2 Installation
WARNING: Use extreme caution when working with the
APS-6R. High voltage and AC line-connected circuits are
present. Turn off and remove all power sources. To reduce
the risk of electric shock make sure to properly ground the
unit.
Introduction
This section contains instructions for mounting, wiring, configuring
and servicing the APS-6R.
Installation topics covered in detail:
Additional information regarding installation may be found in the
appendices.
!
Topic Refer to...
Mounting to a CAB-3/CAB-4
Series Cabinet
Page 12 in "Mounting in
CAB-3/CAB-4 Series
Cabinets"
Field Wiring Page 13 in "Field Wiring an
APS-6R"
Wiring Multiple APS-6Rs Page 15 in "Connecting
Multiple APS-6R Power
Supplies"
Connecting to an ICM/ICE Page 16 in "Connecting the
APS-6R to an ICM/ICE
Module"
Powering a Control Module Page 17 in "Supplying
Power to a Control Module"
Configuring Page 18 in "Configuring the
APS-6R"
Servicing Page 19 in "Servicing the
APS-6R"
www.PDF-Zoo.com
firealarmresources.com

Section 2 Installation
12 PN 50702:B2 4/14/03
Mounting in CAB-3/CAB-4 Series Cabinets
This section contains instructions for the installation of the Auxiliary
Power Supply into a CAB-3/CAB-4 Series cabinet.
These cabinets use a CHS-4 Series chassis to mount the APS-6R.
Instructions for mounting:
Chassis Mounting
The illustration below shows an APS-6R being mounted in a CHS-4L
chassis. Mounting in any CHS-4 Series chassis is accomplished in the
same way.
Figure 4 Mounting an APS-6R to a CHS-4L Chassis
Step Action
1 Remove plastic cover from APS-6R.
2 If 240 VAC is to be used, cut JP1 jumper at this time. See instructions and
high voltage warning on Page 18 in "Configuring the APS-6R".
3 Place the APS-6R onto the mounting studs of the chassis (Figure 4 on page 12).
4 Insert a standoff through each of the printed circuit board mounting holes,
threading each standoff to the mounting studs on the chassis. Use #6-32
hex standoffs, 1.25 in. (32 mm) long.
5 Tighten the standoffs until the APS-6R is securely fastened to the chassis.
6 Reinstall the plastic chassis cover.
Mounting Studs
CHS-4L Chassis
Standoff
(2 places)
APS-6R
Assembly
APS-6R to CHS-4L.cdr
www.PDF-Zoo.com
firealarmresources.com

Section 2 Installation
PN 50702:B2 4/14/03 13
Wiring the APS-6R
This section contains instructions for wiring the APS-6R as follows:
• Typical field wiring from an APS-6R to a control panel and
optional devices.
• Wiring multiple APS-6R power supplies.
Field Wiring an APS-6R
J1 and J2 can be used in place of TB2 when the APS-6R is powering
internal modules (such as an ICM/ICE or XP6-C) with compatible
connectors.
Output Circuit 3 (J9) can be used as a source of power for the XPIQ
Audio Transponder only.
Note: When using the J9 connector do not use the J2 connector. This
will satisfy the 0.25 (6.35mm) requirement for separation between
power-limited and nonpower-limited circuits.
Primary and Secondary Power Connections - See appendix for your
specific system information.
CAUTION: When finished wiring AC connections, install
the press-fit terminal block cover over TB1 AC
connections.
CAUTION: To maintain proper supervision, APS-6Rs
used to power Panel Circuits, such as the ICM/ICE, must
be connected to the same batteries as the main power
supply. Failure to do so may result in improper operation.
!
www.PDF-Zoo.com
firealarmresources.com

Section 2 Installation
14 PN 50702:B2 4/14/03
.
Figure 5 Typical Wiring for an APS-6R
J2
J9
J3
J1
TB2
TB3
TB1
JP3
JP2
TB2:
Output Circuit 1
TB1 - Primary Power:
120 VAC or 240 VAC.
TB3 - Secondary Power: 24 VDC batteries.
Trouble Bus In/Out
TB2:
Output Circuit 2
Earth Ground - Connects to chassis or EARTH
ground terminal on main power supply. If 2 or
more units are connected, secondary units
connect to earth ground on the previous
APS-6R in the chain.
APS
-
6R
s
id
e
b
r
d
.c
d
r
BATT (+)
BATT (–)
HOT
NEUTRAL
EARTH
J9:Output Circuit 3 - Non Power-limited, 6 A @24 VDC (+10, –15%)
+
–
+
–
- + J1:Output Circuit 1
J2:Output Circuit 2
- + - +
(Refer to the caution above this illustration
about secondary power and supervision)
Output Circuit 2
(J2 and TB2):
Power-limited
3 A @24 VDC
(+10, –15%)
Output Circuit 1
(J1 and TB2):
Power-limited
3 A @24 VDC
(+10, –15%)
See Page 18 in
"Configuring the
APS-6R".
www.PDF-Zoo.com
firealarmresources.com

Section 2 Installation
PN 50702:B2 4/14/03 15
Connecting Multiple APS-6R Power Supplies
Typical trouble bus connections for multiple APS-6R power supplies
using trouble connectors J3 and J4.
Use Cable 71033 for all wiring.
See appendix on your system for specific “Trouble Input” connection.
Note: J3 and J4 can be interchanged.
Figure 6 Trouble Bus Connections for Multiple APS-6R
Configurations
J2
J9
J3
J1
TB2
JP3JP2
J2
J9
J3
J1
TB2
JP3JP2
J2
J9
J3
J1
TB2
JP3JP2
To trouble input on main power
supply or control panel
First APS-6R Last APS-6R
APS-6Rmultiple3.cdr
Connect power
as shown in
Figure 5
www.PDF-Zoo.com
firealarmresources.com

Section 2 Installation
16 PN 50702:B2 4/14/03
Wiring Applications
This section contains instructions for wiring the APS-6R assembly as
follows:
• Connecting the APS-6R to an ICM/ICE module
• Supplying notification appliance power to a control module
Connecting the APS-6R to an ICM/ICE Module
All four (4) NACs on the ICM are powered from the APS-6R output
circuit 2 (J2) and the four (4) NACs on the ICE are powered from
circuit 1 (J1). The NACs share the total 3A available from each circuit.
Typical connections for wiring:
Figure 7 Typical APS-6R Wiring to an ICM/ICE Module
J65 J
J65 J
J2
J9
J3
J1
TB2
JP3
JP2
ICM
ICE
Auxiliary Power
Harness
PN 71091
Black
Blue
Blue
Black
APS-6R
APS-6Ricm.cdr
www.PDF-Zoo.com
firealarmresources.com

Section 2 Installation
PN 50702:B2 4/14/03 17
Supplying Power to a Control Module
The circuit is power-limited.
Typical connections for wiring:
Figure 8 Typical APS-6R Wiring to a Control Module
Refer to relevant control module installation documents for specific
wiring instructions.
J2
J9
J3
J1
TB2
JP3
JP2
8910
11
12
13
14
150
1
2
3
4
567
89
0
1
2
3
4
567
TENS
ONES
LOOP
LOOP
A
DDRESS
A
DDRESS
8
9
7
6
5
9
8
7
6
5
0
1
2
3
4
4
3
2
1
0
TENS
ONES
89
0
1
2
3
4
567
8910
11
12
13
14
15
0
1
2
3
4
567
SLC loop
To next device
on SLC loop
APS-6Rfcm.cdr
NAC
www.PDF-Zoo.com
firealarmresources.com

Section 2 Installation
18 PN 50702:B2 4/14/03
Configuring the APS-6R
The APS-6R may be configured for the following:
• 8-hour delay for reporting loss of AC: cut jumper JP2.
• 16-hour delay for reporting loss of AC: cut jumper JP2 and JP3.
• 240 VAC operation: See WARNING below. Cut jumper JP1
before applying power.
The figure below illustrates the location of the jumpers:
Figure 9 Configuring the APS-6R
JP1
J2
J9
J3
J1
TB2
JP3
JP2
JP3 JP2
JP1
APS-6Rconfig.cdr
WARNING: HIGH VOLTAGE!
Cut JP1 before applying power
for 240 VAC operation.
www.PDF-Zoo.com
firealarmresources.com

Section 2 Installation
PN 50702:B2 4/14/03 19
Servicing the APS-6R
The only serviceable components on the APS-6R are fuses F1 and F2.
If a fuse fails, replace it with a fuse of the same type and rating:
•F1 AC protection - 4A, 3 AG
•F2 Battery protection - 10A, 3 AG
To replace either fuse remove the vertical APS-6R control board as
follows:
1. Turn off and remove all power sources.
2. Remove plastic cover.
3. Remove the two retaining screws securing control board.
4. Unplug the control PC board from the connectors.
5. Replace fuses as required.
6. Reinstall board in reverse order, install plastic cover and connect all
power.
The figure below illustrates the location of the fuses.
Figure 10 Servicing the APS-6R
J2
J9
J3
J1
TB2
JP3
JP2
F2 Fuse
Retaining Screw (typ)
F1 Fuse
Connector (typ)
APS-6Rservice.cdr
Main Circuit Board
www.PDF-Zoo.com
firealarmresources.com

APPENDIX A - AFP-200
20 PN 50702:B2 4/14/03
APPENDIX A - AFP-200
Mounting an APS-6R to an AFP-200 Backbox
The Auxiliary Power Supply is mounted in the bottom of the backbox.
Note: If an APS-6R is installed in the backbox, the batteries must be
installed in a separate battery box, such as the BB-17. The battery box
must be located within 20 feet (6 meters) of the enclosure containing
the control panel and all connections must be contained in conduit.
To mount the APS-6R, follow these instructions:
Figure 11 Mounting the APS-6R to an AFP-200 Backbox
Step Action
1 Remove plastic cover from APS-6R.
2 If 240 VAC is to be used, cut JP1 jumper at this time. See
instructions and high voltage warning on Page 18 in "Configuring
the APS-6R".
3 Locate the mounting holes in the AFP-200 backbox. Insert a self-
tapping screw through each of the APS-6R mounting slots.
4 Position the APS-6R in line with the holes in the AFP-200 backbox;
then, thread the self-tapping screws until the APS-6R is securely
fastened to the AFP-200 backbox.
6 Reinstall the plastic chassis cover.
APS-6R
Assembly
AFP-200
Backbox
APS-6R to AFP-200.cdr
Self-tapping screws
(2 places)
www.PDF-Zoo.com
firealarmresources.com
Other manuals for APS-6R
1
Table of contents
Other Notifier Power Supply manuals
Popular Power Supply manuals by other brands

Vanair
Vanair AIR N ARC RELIANT 300 Series Operations manual & parts list

Tripp Lite
Tripp Lite AGSM5396 Series Application guidelines

Heath Zenith
Heath Zenith SP-2718 Operation manual

KEPCO
KEPCO MAT 6-100 Operator's manual

Meanwell
Meanwell PWR-40-24 user manual

B+K precision
B+K precision 1601 instruction manual