MultiSerialInterfaceforNOTIFIERAMSeriesControlPanels
MOD-PRT-M CEIA660
FEATURES
Multi‐addressinterfaceforNOTIFIERAMSeries
controlpanels(fireandgas);providesaserialoutput
with7wiresforprinterandfourserialoutputwith3
wiresCEI‐ABI/MODBUSsuitableforsupervision
systemconnection,asNotiNet2000andEuroNet.
Printeroutputperforms3printingmodes:
on‐line
log
system
INSTALLATION
MOD‐PRT‐Minterfaceisdesignedandrealizedtobe
installedinsideAMSeriescontrolpanelsornearby
(max.lengthofserialcables=15mt).Removepower
supplybeforeproceedingwithelectricalconnection.
FUNCTIONING
MOD‐PRT‐Minterface,afterAMSeriescontorlpanel
serialconnection,acquiresdatathroughanalignment.
DuringthisalignmenttheLEDflahsesaccordingto
cycle2secondsoff,0.1secondson(greenlight);the
printandserialCHANNELsA,B,CandDareblocked.
NewprogrammingcarriedoutonAMcontrolpanel,if
any,automaticallywillsetanewalignment.Oncethe
alignmentiscompleted,theinterfacestartssaving
eventsintononvolatilememory–thememory
capacityis4096events.MOD‐PRT‐Minterfacesaves
foreachserialCHANNEL(printer,serialA,B,C,D)the
IDofthelastsenteventandincaseofcommunication
stopitrestartsfromthepointofinterruption.To
eliminatethespooledeventsforalltheCHANNELs,
pushRSTbuttonformorethan5seconds,theLEDL1
isswitchedofffor2secondsandthenitbecomes
greenlighted.
COMMUNICATIONINTERRUPTIONWITHAM
CONTROLPANEL
ThecommunicationinterruptionwithAMSeries
controlpanelisnotifiedbyquickflashinggreenLED.
Everycommunicationinterruptionwillstartanew
MOD‐PRT‐Malignment.
ON‐LINEPRINT
On‐lineprintisapre‐setmodeoffunctioning(fixed
greenLED).Thesavedeventsaresenttotheprinter,
startingfromlastprintedevent,assoonastheprinter
CHANNELisconnected.
LOGPRINT
Thisfunctionmodeallowsprintingthelast1000
eventssavedintoMOD‐PRT‐M.Tocarryoutthelog
print,pushRSTbutton(withLEDL1fixedgreenlighted
orquickflashing)formorethan2secondsuntilthe
LEDL1turnsintofixedredlighted,thenreleasethe
buttonandpushitagainforlessthan2seconds;the
LEDL1turnsintoquickredflashingandtheprint
starts.
SYSTEMPRINT
Thisfunctionmodeallowsprintingthelistofsensors
(withrelatedchambervaluein%),inputandoutput
modules.
Tocarryoutthesystemprint,pushRSTbutton(with
LEDL1fixedgreenlighted)formorethan2seconds
untiltheLEDL1turnsintofixedredlighted,then
releasethebuttonandpushitagainformorethan2
secondsuntiltheLEDL1turnsintoslowyellow
flashing;oncethealignmentiscompletedtheLED
turnsintoquickyellowflashingandtheprintstarts
PRINTINTERRUPTION
Tointerruptthelogorsystemprintandreturntoon‐
linemode,pushRSTbutton,theLEDL1turnsinto
fixedgreed.
WhentheLEDisfixedredoryellowandtheprintwill
notstartwithin10seconds,MOD‐PRT‐Minterfacewill
automaticallyreturntoon‐linemodeandtheLEDis
fixedgreen.
CHANNELSA,B,C,D
TheserialCHANNELsaretransparent.
ForeachCHANNELitispossibletoselect
communicationprotocolCEI‐ABIorMODBUSandthe
connectionin232or485.
DuringMOD‐PRT‐MorCHANNELsalignmentevery
commandisignored.
TheCHANNELscancarryoutthealignment
simultaneously.
ForanyCHANNEL,aftertherelatedalignment,only
neweventwillbesent.
DuringthealignmenttheLEDsflashaccordingtocycle
2secondsoff,on,off,onasquicksequence:
GreenforCHANNELsA‐C
RedforCHANNELsB‐D
YellowforCHANNELsA+B–C+D
TECHNICALDATA
Power 9‐30Vcc
Max.Currentat12V 325mA
Max.Currentat24V 175mA
Temperaturerange ‐10+50
C
Dimensions 170X150X30 mm