Notifier MOD-PRT-M User manual

MultiSerialInterfaceforNOTIFIERAMSeriesControlPanels
MOD-PRT-M CEIA660
FEATURES
Multi‐addressinterfaceforNOTIFIERAMSeries
controlpanels(fireandgas);providesaserialoutput
with7wiresforprinterandfourserialoutputwith3
wiresCEI‐ABI/MODBUSsuitableforsupervision
systemconnection,asNotiNet2000andEuroNet.
Printeroutputperforms3printingmodes:
on‐line
log
system
INSTALLATION
MOD‐PRT‐Minterfaceisdesignedandrealizedtobe
installedinsideAMSeriescontrolpanelsornearby
(max.lengthofserialcables=15mt).Removepower
supplybeforeproceedingwithelectricalconnection.
FUNCTIONING
MOD‐PRT‐Minterface,afterAMSeriescontorlpanel
serialconnection,acquiresdatathroughanalignment.
DuringthisalignmenttheLEDflahsesaccordingto
cycle2secondsoff,0.1secondson(greenlight);the
printandserialCHANNELsA,B,CandDareblocked.
NewprogrammingcarriedoutonAMcontrolpanel,if
any,automaticallywillsetanewalignment.Oncethe
alignmentiscompleted,theinterfacestartssaving
eventsintononvolatilememory–thememory
capacityis4096events.MOD‐PRT‐Minterfacesaves
foreachserialCHANNEL(printer,serialA,B,C,D)the
IDofthelastsenteventandincaseofcommunication
stopitrestartsfromthepointofinterruption.To
eliminatethespooledeventsforalltheCHANNELs,
pushRSTbuttonformorethan5seconds,theLEDL1
isswitchedofffor2secondsandthenitbecomes
greenlighted.
COMMUNICATIONINTERRUPTIONWITHAM
CONTROLPANEL
ThecommunicationinterruptionwithAMSeries
controlpanelisnotifiedbyquickflashinggreenLED.
Everycommunicationinterruptionwillstartanew
MOD‐PRT‐Malignment.
ON‐LINEPRINT
On‐lineprintisapre‐setmodeoffunctioning(fixed
greenLED).Thesavedeventsaresenttotheprinter,
startingfromlastprintedevent,assoonastheprinter
CHANNELisconnected.
LOGPRINT
Thisfunctionmodeallowsprintingthelast1000
eventssavedintoMOD‐PRT‐M.Tocarryoutthelog
print,pushRSTbutton(withLEDL1fixedgreenlighted
orquickflashing)formorethan2secondsuntilthe
LEDL1turnsintofixedredlighted,thenreleasethe
buttonandpushitagainforlessthan2seconds;the
LEDL1turnsintoquickredflashingandtheprint
starts.
SYSTEMPRINT
Thisfunctionmodeallowsprintingthelistofsensors
(withrelatedchambervaluein%),inputandoutput
modules.
Tocarryoutthesystemprint,pushRSTbutton(with
LEDL1fixedgreenlighted)formorethan2seconds
untiltheLEDL1turnsintofixedredlighted,then
releasethebuttonandpushitagainformorethan2
secondsuntiltheLEDL1turnsintoslowyellow
flashing;oncethealignmentiscompletedtheLED
turnsintoquickyellowflashingandtheprintstarts
PRINTINTERRUPTION
Tointerruptthelogorsystemprintandreturntoon‐
linemode,pushRSTbutton,theLEDL1turnsinto
fixedgreed.
WhentheLEDisfixedredoryellowandtheprintwill
notstartwithin10seconds,MOD‐PRT‐Minterfacewill
automaticallyreturntoon‐linemodeandtheLEDis
fixedgreen.
CHANNELSA,B,C,D
TheserialCHANNELsaretransparent.
ForeachCHANNELitispossibletoselect
communicationprotocolCEI‐ABIorMODBUSandthe
connectionin232or485.
DuringMOD‐PRT‐MorCHANNELsalignmentevery
commandisignored.
TheCHANNELscancarryoutthealignment
simultaneously.
ForanyCHANNEL,aftertherelatedalignment,only
neweventwillbesent.
DuringthealignmenttheLEDsflashaccordingtocycle
2secondsoff,on,off,onasquicksequence:
GreenforCHANNELsA‐C
RedforCHANNELsB‐D
YellowforCHANNELsA+B–C+D
TECHNICALDATA
Power 9‐30Vcc
Max.Currentat12V 325mA
Max.Currentat24V 175mA
Temperaturerange ‐10+50
°
C
Dimensions 170X150X30 mm

WIRING
JP1 Power
1Positive+12/24V
2Negative
JP2PRINTER
MOD‐PRT‐M9pin25pin
1GND57
2RTS85
3N.U.NotUsedNotUsed
4DSR420
5CTS74
6RX32
7TX23
6bridgewith46bridgewith20
JP3CHANNEL
A
232485
1RXL
2GNDGND
3TXH
JP4CHANNEL
B
232485
1RXL
2GNDGND
3TXH
JP5 232AMOLDAMNEW
1RX4Tx 2Tx
2GND6GND5GND
3TX5Rx3Rx
JP5 485AMOLDAMNEW
1L11H 7H
2GND6GND5GND
3H7L6L
JP6CHANNEL
C232485
1RXL
2GNDGND
3TXH
JP7CHANNEL
D232485
1RXL
DIPSWITCH
DS1 Setting OFFfor CEI‐ABIandONforMODBUS
1ConfigurationJP3–CHANNELA
2ConfigurationJP4–CHANNELB
3ConfigurationJP6–CHANNELC
4ConfigurationJP7–CHANNELD
DS2 ENABLINGMODBUSCOMMANDS(ON)
1ConfigurationJP3–CHANNELA
2ConfigurationJP4–CHANNELB
3ConfigurationJP6–CHANNELC
4ConfigurationJP7–CHANNELD
DS3 Rerserved
JUMPER
GROUP P3 ConfigurationJP3–CHANNELA
GROUP P4 ConfigurationJP4–CHANNELB
GROUP P5 ConfigurationJP5–AMInpunt
GROUP P6 ConfigurationJP6–CHANNELC
GROUP P7 ConfigurationJP7–CHANNELD
a485endofline
b‐c 1‐2485 line
2‐3232 line
PA Reserved–Alwasyleaveinserted
PB Reserved–Alwasyleaveopen
PC Reserved–Alwasyleaveopen
PU Reserved–Alwasyleaveopen
SIGNALLING
L1/L2 Power +Communication
ON 24Vpresence
OFF 24Vfault
Green Communication OK
Greenfastblink TamperingCom.AM
Green 1pulse /2”OFF AlignmentMOD‐PRT‐M
L1
Red1pulse/2”OFF AlignmentCEI‐ABIA
Yello1pulse/2”OFF AlignmentCEI‐ABIB
Red1pulse/Yellow1pulse/2”OFFAlignmentCEI‐ABIA+B
Red fix Printhistorylogwait
Redfastblink Printhistorylog
Yellowfix Printsystemwait
Yellowslowblink Alignmentchambervalue
YellowfastblinkPrintsystem
L2
Red1pulse/2”OFF AlignmentCEI‐ABIC
Yellow1pulse /2”OFF AlignmentCEI‐ABID
Red1pulse/Yellow1pulse/2”OFF AlignmentCEI‐ABIC+D
BUTTON
RST ‐EventsDelete
‐Printselection
‐Systemprintselection
SW1 Rererved
PRINTERCONFIGURATION
FlowControlHardware
Buadrate9600
DataBit8
ParityNO
Sto
p
Bit1


NOTIFIER ITALIA S.r.l.
MILANO - ITALY Tel. +39 – 02 – 51 897.1
Fax. +39 – 02 – 51 897.30
EQUIPPEDPRINTER
CBLE
AMSeriescontrolpanels
withSIB‐OEMboard
JP3JP4JP6JP7
Serialoutputsforsupervisionsystems(ex:Notinet,Euronet,supervisionand
MODBUS).
PossibilitytoselectforeachCHANNELthecommunicationprotocolCEI‐ABIor
MODBUSandtypeofconnectionin232or485.