nvent ERICO SRF N Series User manual

2
|
nVent.com/ERICO
Table of Contents
1 INTRODUCTION ........................................................................................................................................................................ 3
2 WARNING.................................................................................................................................................................................. 3
3 INSTALLATION CAUTIONS........................................................................................................................................................ 4
4 IDENTIFY THE DISTRIBUTION SYSTEM .................................................................................................................................... 5
5 MOUNTING THE SRF................................................................................................................................................................. 8
6 OPTIMISING PERFORMANCE ................................................................................................................................................... 9
7 SERVICING AND TROUBLESHOOTING .................................................................................................................................... 16
8 BACKPLANE MODELS............................................................................................................................................................. 18
9 SCHEMATIC DIAGRAMS ......................................................................................................................................................... 18
10 PHYSICAL DIMENSIONS ....................................................................................................................................................... 19

nVent.com/ERICO
|
3
Installation and Operating Instructions
nVent ERICO Surge Reduction Filters (SRFs)from nVent
incorporate high energy clamping devices and special filtering
circuitry. SRFs are installed in series with the circuit, usually at
the point of entry to the building or structure. They are available
in single or three-phase configurations for load currents from
63A to 800A per phase.
The purpose of an SRF is to filter and protect against lightning
induced transients. The SRF provides a clean, filtered supply of
electricity to all output connected equipment when installed in
accordance with the manufacturers ' instructions.
Protection is achieved via a three stage circuit. This includes
the internal nVent ERICO Spark Gap unit as the primary surge
diverter, a purpose designed low pass filter network and a
secondary Transient Discriminating (TD)diversion stage to
further clamp the transient energy to safe levels. This allows
the SRF to:
• Provide filtering to the clamped waveform in order to reduce
the rate of voltage rise.
• Provide a secondary stage of surge diversion to protect
equipment from transients which may be induced onto the
SRF output cables or be caused by the load itself.
The use of this combination of technologies provides the
benefits of high surge capability, low let through voltage
and considerably reduced dv/dt. This applies to both surge
performance and over-voltage withstand from short and long
duration high-energy surges.
1 INTRODUCTION
HAZARDOUS VOLTAGES EXIST WITHIN THE SRF ENCLOSURE.
THIS UNIT SHOULD BE INSTALLED & SERVICED ONLY
BY QUALIFIED PERSONNEL AND IN ACCORDANCE WITH
RELEVANT NATIONAL ELECTRICAL & SAFETY CODES. ALL
INSTRUCTIONS MUST BE FOLLOWED TO ENSURE CORRECT
AND SAFE OPERATION OF THE SRF.
• Over-current and short-circuit protection must be provided to
protect the SRF and associated wiring if a fault develops. The
over-current protection should be installed in such a manner as
to provide a means of isolating the SRF from the main supply.
This unit contains overvoltage protection components and
may be damaged by installation resistance testing.
• SRFs contain capacitors. Disconnect power at least
1 minute prior to opening door. Check voltage prior to
working on SRF internals.
• SRFs must be connected to a low impedance earth ()
for correct operation.
• SRFs must be installed in accordance with ALL relevant
national electrical and safety codes.
• The power supply to the SRF should always be turned off
(and locked)before the door is opened for any purpose.
• Check all SRF terminals for tight connections.
(Some terminals may become loose during transport).
• Ensure all input and output cabling, once installed is
tightened to the correct torque settings (see table 2).
• Do not disconnect upstream Earth or Neutral connections
supplying the SRF while power is still applied, as this may
damage the SRF or load.
• No combustible items should be stored within the SRF
during operation.
• Do not leave this manual inside the SRF after applying power
to the SRF. Retain this manual for future reference.
• Failure to heed instructions or warnings may result
in personnel injury, equipment damage or ineffective
transient protection.
2 WARNING

4
|
nVent.com/ERICO
Installation and Operating Instructions
• Transient protection devices are usually rated to protect
against non-repetitive pulses from sources such as direct or
induced lightning energy.
• They are not designed to provide protection against repeated
cyclic anomalies such as those caused by motor speed
control notching (variable speed controls, etc).
• SRFs are not designed to provide protection against
sustained over-voltage conditions where the supply voltage
exceeds, for an extended period of time, the nominal rating of
the protection equipment. i.e continuous over-voltages from
poorly regulated generators or distribution systems.
• Smaller power generation equipment does not always
conform to the same standards of voltage regulation that
is in place for mains power reticulation. A large number of
smaller or cheaper generators have a voltage waveform that
approximates 240Vrms (often poorly regulated), but more
importantly, which often contains significant higher order
harmonics and may exhibit a peak voltage on each half cycle
far in excess of the normal 340V (peak). Such machines
are usually capacitive excitation induction generators, as
opposed to synchronous generators. The problem is usually
increased when the generator is lightly loaded.
• Harmonic voltages may also be present in distribution
systems that do not feature generators. This is normally
where non-linear loads are used, such as UPSs, rectifiers,
switch-mode power supplies and motor speed controls. The
harmonic voltages may have peak voltages in excess of the
protective clamping voltages, causing problems such as
excessive heat build up. Because the harmonic waveforms
contain higher order frequencies, capacitive leakage currents
may increase to above prescribed limits and shorten the
life of the SRF. It should be noted that in sites with large
harmonic voltage distortion, the SRF capacitance may
dramatically affect the power factor.
• Seek the manufacturers ' advice before installing any SRF
into a circuit which features a total harmonic voltage ratio
above 5%.
• With large transients, significant energy may be passed by
the SRF diverters back to the source or to earth. This may,
under some circumstances, cause upstream earth leakage
circuit breakers or residual current devices (ELCBs & RCDs)
to nuisance trip. Where possible, these devices should be
installed after the SRF in order to reduce this possibility.
• Transient protection devices often have minimum
requirements for upstream fusing to ensure proper operation.
See section 6.1 for fusing requirements.
• By-pass switches are not recommended to be used with
SRFs as they compromise the protection offered. The
connection of the by-pass switch compromises the input to
output separation requirement by bringing the SRF input
and output wiring into close proximity at the switch.
3 INSTALLATION CAUTIONS
Figure 1. Seek specialist advice with the above installations.
SRF
SRF
SRF
SRF SRF
ELCB
or
RCD
NON PREFERRED NON PREFERRED PREFERRED
AVOID UPSTREAM EARTH LEAKAGE CIRCUIT BREAKERS
(ELCB’S) OR RESIDUAL CURRENT DEVICES (RCD’S)
BYPASS SWITCHES
BYPASS SWITCHES COMPROMISE PROTECTION
AVOID REPETITIVE VOLTAGES IN EXCESS OF SRF RATING AVOID HIGH HARMONIC VOLTAGES
276 Vrms
Or
276 Vrms
276 Vrms
240 Vrms
240 Vrms
GENERATOR
GENERATOR
GENERATOR GENERATOR
SRF SRF
MAINS / GENERATOR CHANGE OVER SWITCH CONNECTION

nVent.com/ERICO
|
5
Installation and Operating Instructions
A number of different power distribution systems are employed
in various countries around the world. It is important to
identify the distribution system in use prior to installation of
the SRF, and confirm that the SRF is the model recommended
by the manufacturer for that distribution system. To identify
the distribution system in use, consult reputable and
knowledgeable sources such as:
• The local power supply authority
• Local electrical engineers
• Applicable regulatory bodies or standards associations
Alternatively, confirm the type of distribution system used by
personal inspection. By visually tracing the neutral and earthing
conductors from the load equipment or sub-distribution
point back to the point of entry (and perhaps to the supply
transformer), the type of distribution system should be
identifiable with the aid of the following diagrams (figures 2-6).
These are prescribed in local regulations and describe the
relationship between the source, exposed or conductive parts
of the installation and earth. Amongst these, the TN-C, TN-S,
TN-C-S and TT systems are most commonly encountered.
Note that supplies such as those used in industry and mining
may often use a different distribution system to that of the local
supply authority.
4 IDENTIFY THE DISTRIBUTION SYSTEM
Regulations differ between countries. Check compliance with appropiate authorities
Figure 2. TN-C system: In this system, the neutral and protective earth conductor combine in a single conductor
throughout. All exposed conductive parts are connected to the PEN conductor.

6
|
nVent.com/ERICO
Installation and Operating Instructions
Figure 3. TN-S system: In this system, a separate neutral and protective earth conductor are run
throughout. The protective PE conductor can be the metalic sheath of the power distribution cable or separate conduc-
tor. All exposed conductive parts of the installation are conducted to this PE conductor.
Figure 4. TN-C-S system: In this system, a separate neutral and protective earth functions combine in a single PEN
conductor. This system is also known as a Multiple Earthed (MEN) system and the protective conductor is referred to as
the combined neutral earth (CNE) conductor The supply PEN conductor is earthed at a number of points throughout the
network and generally as close to the consumer 's point of entry as possible. All exposed conductive parts are connected to
the CNE conductor.
4 IDENTIFY THE DISTRIBUTION SYSTEM

nVent.com/ERICO
|
7
Installation and Operating Instructions
nVent ERICO Critec SRFs provide protection for equipment on
TN-C, TN-S, TN-C-S and TT single and three phase systems when
selected, installed and earthed in the specified manner.
The diagrams are provided as a guide to identifying and
distinguishing the distribution system in use. Metering,
over-current protection, and other details have not been shown.
The SRFs are designed to be used in distribution systems that
provide a separate earth and neutral connection. SRFs should
not be used in IT distribution systems. (Refer Figure 7)
As electrical wiring and safety regulations differ from country
to country, it is important to ensure that the installation
complies with all regulations applicable to the location.
Please seek further assistance if uncertain.
Regulations differ between countries. Check compliance with appropiate authorities.
Regulations differ between countries. Check compliance with appropiate authorities.
Figure 5. TT system: A system having one point of the source of energy earthed and the exposed conductive parts of the installa-
tion connected to independent earthed electrodes.
Figure 6. IT system: A system having no direct connection between live parts and earth, but having all exposed conductive parts of
the installation connected to independent earthed electrodes. nVent ERICO Critec Surge Reduction Filters should NOT be used in IT
systems without specialist advice.
4 IDENTIFY THE DISTRIBUTION SYSTEM

8
|
nVent.com/ERICO
Installation and Operating Instructions
5 MOUNTING THE SRF
Before mounting the SRF, refer to Table 3 (weights and
dimensions on last page of this manual)which provides
dimensions and unit weights. Ensure that appropriate lifting
equipment is used when installing the larger SRFs. When
installing the SRF, consideration should be given to future
service needs. Ensure that clear view of the status indicators
is provided. The SRFs should be mounted away from other
electrical apparatus (300mm minimum)and in a position that
avoids close proximity to combustible materials.
The SRFs are designed to be wall mounted. Mounting brackets
(as shown in Figure 7)are supplied. The internal backplane may
be removed to facilitate wall mounting. Carefully disconnect the
wiring going to the front door LED before removing backplane.
The cabling and upstream over-current protection requirements
and all instructions provided in this manual, should be taken into
consideration before mounting the SRF.
To preserve the IP rating, SRF units from 63A to 250 A must
be installed in accordance with figure 9 and section 6.2.
• Larger SRF units from 500A to 800A are ventilated and
should be mounted in a dust and moisture-free, ventilated
environment.
• All SRFs should be installed in a dry, well-ventilated area.
Avoid sites subject to moisture ingress.
• SRFs are not intended for use in harsh or corrosive
environments.
Where the SRF is to be enclosed in a switch board cubicle,
models are available without the enclosure. These backplane
units are denoted by the model number suffix 'BP '.
SUITABLE WALL
ANCHORING
SEE TABLE 3 FOR
MOUNTING DIMENSIONS
WASHER
INTERNAL NUTS
BRACKET
BRACKET. INSTALLER TO PROVIDE
SUITABLE ANCHOR BOLT
Figure 7a. Typical mounting arrangement for wall mounted nVent ERICO Critec Surge Reduction Filters (63A to 250A).
Figure 7b: Typical mounting arrangement (500A to 800A).

nVent.com/ERICO
|
9
Installation and Operating Instructions
6 OPTIMISING PERFORMANCE
6.1 FUSING
6.2 CABLING
The protection equipment must be earthed and installed in
accordance with all relevant national electrical and safety
standards. The term "point of entry " protection, is a general
descriptive concept of zonal boundary protection, as detailed
in standards such as IEC 62305. Some local wiring regulations
may allow the protection equipment to be mounted directly
at the point of entry, while other countries require protection
equipment to be installed after the metering or main circuit
isolators or over-current protection.
The following installation points require attention to ensure that
optimal protection is provided by the protection equipment. This
information is provided as a guide only. Compliance with local
electrical and safety regulations must be ensured.
Over-current and short-circuit protection must be provided
in order to protect the SRF and associated wiring if a fault
develops. The over-current protection should be installed in such
a manner as to provide a means of isolating the SRF from the
mains supply. This is an important safety consideration.
The SRF N-Series SRFs do not incorporate overcurrent
protection. Upstream fusing or circuit breakers MUST be
installed. The amperage of this upstream overcurrent protection
must not exceed the load current rating of the SRF. For example,
the SRF25ON filter should be installed with upstream protection
rated at less than or equal to 250A. The load current rating of
the filter is noted on the Ratings Label on the inside of the SRF
enclosure door (and duplicated on the external side surface of
the enclosure).
The cabling and earth wires connected to the filter input should
always be run separately, with a minimum clearance of 300mm
between them and all other cables or sensitive equipment
(as shown in Figure 8 ). The input cable and earth wire will carry
the transient energy, while the protected output cable can be
considered to be a "clean filtered " supply.
By separating these cables, any incoming transients will not be
induced from the input cables onto nearby clean cables. This
clearance will reduce the possibility of arc-over from input to
output cables. Where cables need to run closer together due
to space restrictions, input and output cables should cross at
right angles and not be installed parallel to each other. Cabling
should be sized in accordance with all relevant wiring standards
to ensure that the full load current can be safely supplied. All
cabling or busbars connected to the protection equipment
should be securely anchored to prevent undue stress being
applied to input/output terminals.
Input and output terminal requirements are detailed in Table 2.
The input and output earth connections connect together on
the backplane earthing stud. This earthing stud provides the
function of connecting these earths together for continuity, and
also the functional electrical earthing of the SRF, together with
the safety earthing of the SRF enclosure. The 250A to 800A
SRFs have cable tie holes in the backplane to allow the incoming
and outgoing earth cables to be secured to the backplane
(see Figure 9).
• Cable glands (of an appropriate design)must be used for all
input and output cables to preserve the IP rating of the 63A to
250A SRFs.
• To protect input and output cabling insulation from sharp
edges around the cable entry holes suitable cable glands or
grommets must be installed.

10
|
nVent.com/ERICO
Filter rating Phase and Neutral Terminals Earth Terminal
Termination Method Size Torque Termination Method Size Torque
63A Screw Terminal Block 10 to 35 mm28.5 N.m Backplane Stud 1 x M8 8.5 N.m
125A Screw Terminal Block 25 to 120 mm219 N.m Backplane Stud 1 x M8 8.5 N.m
250A Screw Terminal Block 25 to 120 mm219 N.m Backplane Stud 1 x M8 8.5 N.m
500A Stud Terminal Block 1 x M10 30 N.m Backplane Stud 1 x M10 17 N.m
800A Stud Terminal Block 2 x M10 30 N.m Backplane Stud 1 x M10 17 N.m
SINGLE PHASE (63A - 125A)
SRF
300 mm
300 mm 300 mm
INPUT
LINE
OUTPUT
LOAD
“Clean”
protected
wiring
Keep cables
and equipment
away from this area
Safe area
Hazardous area
Figure 8. Maintaining clearance between input and other cabling.
Table 2. Termination details for SRFs
6.2 CABLING
Installation and Operating Instructions

12
|
nVent.com/ERICO
6.3 OUTPUT DISTRIBUTION
As the output of the SRF is considered to be a "clean filtered
" supply it should not be subjected to situations where further
transients can be introduced. The "clean " supply should
not be run external to the facility, ie to provide power to an
external building or tower lighting. From the aspect of transient
protection to do so would create possible points of entry for
transient energy to the protected zone.
A similar scenario exists where the output of the SRF is fed
to an electrically "noisy " load. Any transients developed by this
load may also be fed to other equipment connected to the
same supply.
Electrically noisy equipment should ideally be supplied from
a separate SRF and all cabling should be run in isolation
to other cables.
SRF
RIGHT
RIGHT
SRF
ALTERNATIVE CONNECTION
AIRCRAFT
WARNING LIGHT
AIRCRAFT
WARNING LIGHT
AIRCRAFT
WARNING LIGHT
PREFERRED CONNECTION
REVERSE CONNECTED SRF
INCORRECT CONNECTION
WRONG
WRONG
SRF
SRF SRF
RIGHT
SRF
Figure 10. Isolation of sensitive equipment from noisy sources.
Installation and Operating Instructions

nVent.com/ERICO
|
13
6.4 EARTHING
The earths for all site equipment should be integrated
(preferably deploying a single point earthing approach)and an
equipotential earth plane should be created. Integral to this is
the elimination of earth loops. It is common, but incorrect from
the point of lightning protection for there to be separate earths
for various services, ie electricity mains, telephone. computer
equipment and other building services.
For sites where the interconnection of these earths is
difficult, either for practical or regulatory reasons, the use
of a Potential Equalisation Clamp (PEC)is recommended.
The PEC behaves as an open circuit under normal operation,
but under surge conditions it activates to effectively clamp
individual points together.
The effectiveness of an SRF is intimately related to the
impedance presented by the earthing system to which it is
connected. A low impedance route to the earth is required (less
). This can be achieved by ensuring that the earth
electrode system at the site presents a low surge impedance
with respect to the ground. Additionally, the interconnecting
cabling must be of adequate cross sectional area and be routed
to provide as short and direct a path as is practical.
The earth conductor for the SRF should be sized according
to local regulations but with a minimum size of 6mm2, Every
attempt should be made to limit the cable length to under 5
metres. By selecting the most direct route, with the minimum
possible number of bends to the earth point or internal earth
bar, the risk of side flashing and excessive voltage rise across
the equipment is reduced. Figure 14 depicts the correct earthing
concept as described above.
ALL POWER AND
DATA CABLES
ENTER OR LEAVE
THE BUILDING
ON THE
SAME SIDE
(TO AVOID
EARTH LOOPS)
Figure 11. Preferred approach to equipotential bonding.
Installation and Operating Instructions

14
|
nVent.com/ERICO
6.5 CONNECTION OF ALARM CIRCUITS
6.6 INSTALLATION ARRANGEMENT FOR AUSTRALIAN MEN SYSTEMS
The SRF secondary surge diverters are continuously monitored
and their internal protection status is identified by the green LED
on each phase blue secondary Unit (SRFSUAC for phase 1, and
SRFSU on phases 2 and 3 if present).
Reduction in surge handling capacity activates a set of voltage
free alarm contacts which can be used to shut down the load or
to activate an external warning.
When mains voltage is applied to the SRF and the surge
diverters are fully functional, the alarm contacts will be in the
energized or normal state. The NC contact will be in short circuit
with the COM contact. Should the surge handling capacity
fall to below the alarm threshold, these contacts will be in the
de-energised or alarm state and the NO contact will be in short
circuit with the COM contact.
The contacts are "Fail-Safe ' in that, if power to the unit fails, the
contacts will revert to the de-energised or alarm state.
The alarm contacts should only be connected by an
appropriately qualified person owing to the possibility of mains
voltage being present in the SRF cabinet. Care should be taken
to route the alarm wiring away from the input circuit and any
other current-carrying conductors.
Alarm contact ratings:
• 5A @250VAC
• 54 @ 30 VDC
• 4kV Isolation
See section 7 "Servicing and Trouble Shooting " for further
information.
Under Australian Standards classification, SRFs are considered
a piece of equipment to be connected to the mains supply. They
are not intended for use as switchboards, distribution boards or
other equipment. As these devices are classified as "electrical
equipment AS 3000 Wiring Regulations apply to the installation
and operation of the units.
AS 3000 specifies minimum requirements for electrical
equipment that is connected to switch boards or distribution
boards. For a point of entry application in the multiple earth
neutral (MEN)distribution system, the SRF equipment should
be installed as close as possible after the MEN point and after
both the main disconnect switch/over-current protector and any
metering equipment. The SRF therefore, may not be installed at
the physical "point of entry " of the mains power to the building.
It must be earthed and installed in accordance with all other
applicable electrical and safety standards. As the protection
equipment is hardwired, the installation must be inspected by
an appropriately authorized electrical authority official prior
to commissioning.
Figure 12. Typical connection detail for SRF point of entry installation in MEN system.
Installation and Operating Instructions

nVent.com/ERICO
|
15
6.7 SRFS ON SUB-CIRCUITS
Where SRFs are installed to protect equipment on a particular
sub-circuit, it is strongly recommended that additional
protection be installed at the power point of entry. Primary shunt
protection at the point of entry should be used to divert the peak
surge currents away from the sub-circuit. This will reduce the
risk of cross-coupling of transients onto adjacent circuits and
will reduce the risk of flashover between the locally grounded
chassis and the earth circuit.
Figure 13 details the role of point of entry protection in these
instances. The cables supplying the input to the SRF and the
connection to the earthing system will carry a proportion of the
surge energy which has been let through the primary
point-of-entry protector.
Care should be taken therefore, in the routing of these cables to
ensure that this energy will not couple onto adjacent circuits.
In some instances it will be necessary to provide a separate
earth electrode for the SRF (subject to compliance with
relevant wiring regulations), particularly where the filter is to be
installed on a sub-circuit some distance from the existing earth
electrode. In this instance, the new electrode should be located
as near as possible to the SRF. This secondary electrode must
be electrically bonded to the existing earthing system via the
most direct route possible, using flat copper tape, and should
be buried to an appropriate depth.
This earthing arrangement is depicted in Figure 13. If a
secondary earth cannot be installed, or the earth impedance
special care must be taken. The risk of flashover between the
locally grounded chassis and the earth circuit may exist.
Careful attention must be paid to equipotential bonding of
the protected equipment.
Figure14. Earthing of an SRF remote from MEN point. Subject to compliance with relevant national stan-
dards). Care is needed ro avoid earth loops within protected environment.
Figure13. Operation of primary shunt protection and SRFs on sub-circuit
Installation and Operating Instructions

16
|
nVent.com/ERICO
7 SERVICING AND TROUBLESHOOTING
HAZARDOUS VOLTAGES EXIST WITHIN THE SRF ENCLOSURE.
THE SRF SHOULD ONLY BE SERVICED BY QUALIFIED
PERSONNEL, IN ACCORDANCE WITH RELEVANT NATIONAL
ELECTRICAL & SAFETY CODES.
Do not disconnect upstream earth or neutral connections
supplying the SRF while power is applied to the unit, as this
may damage the SRF or load.
Only replace the primary spark gaps or secondary TDS surge
diverters with an identical type.
Voltage-free alarm contacts are activated should the secondary
protection status fall below a pre-determined level.
The SRFs are essentially maintenance free, although periodic
inspection is recommended to ensure that the ventilation
louvres (where fitted)do not become clogged with dust.
INITIAL POWER CHECK
All indicators, alarms and surge counters (where fitted)should
be checked on a regular basis.
Should any of the display indicators fail to illuminate, check for
the following conditions:
• Is power available to the SRF?
• Check the input voltage by measuring the voltage between
active and neutral
• Has the upstream circuit breaker or fuse tripped?
INDICATORS
If power is being supplied to the SRF and the indicators still
fail to all correctly illuminate, then it is possible that either the
primary Spark Gap or secondary TDS devices have exhausted
their surge capacity. In such circumstances, the particular
devices should be replaced as a matter of urgency as they are
no longer providing optimum protection.
PRIMARY SPARK GAPS
With power correctly supplied, the Phase Spark Gaps should have
their green LEDs illuminated. Note that in the 250A to 800A SRFs,
these Spark Gaps are supplied via Spark Gap Fuses. If power is
correctly applied, and a Phase Spark Gap does not have its LED
illuminated, check the adjacent fuse. If the fuse has operated
(blown)it needs to be replaced. If the fuse is still in good order, the
Spark Gap needs to be replaced. Blown fuses may be temporarily
replaced with a 125A 22mm x 58mm gG Fuse. Note that this fuse
will not allow the full rated surge current to be diverted by the
associated Spark Gap. The correct replacement fuse should be
obtained from nVent as soon as possible.
Note that the N-E Spark Gap does not have an LED.
SECONDARY UNITS
The Secondary Units are blue in colour and contain the
secondary shunt diverter module and the filter capacitance
(see Figure yy). They are fed from individual 20A fuses. The
Phase 1 Secondary Unit is fitted with the Alarm Contacts, and it
is marked as SRFSUAC. On three phase units, the Phase 2 and
Phase 3 Secondary Units are marked as SRFSU. The status of
each SRFSUAC and SRFSU unit is indicated by the green LED
included on each. A correctly powered and operating SRF will
have all Secondary Unit LEDs illuminated green.
A Secondary Unit LED that is not illuminated indicates one of
the following:
• A blown Secondary Unit Fuse (replace Fuse)
• A failed Diverter Module (replace Module)
• An SRFSU or SRFSUAC internal failure (replace SRFSU or
SRFSUAC unit)
Troubleshooting proceeds in the order indicated here:
1)Check fuses for continuity, and replace blown fuses with 20A
10mm x 38mm gG fuses.
2)Check Diverter Module indicator flags. These should appear
as the textured window, with a faint grey/red tinge. Any window
showing a bright red colour should be replaced. Modules may
be gripped with the fingers and pulled straight out, away from
the Secondary Unit. Replace with an identical module obtained
from nVent.
3)Where all fuses and modules have been checked as OK,
then the affected Secondary Unit itself needs replacing
(ie the SRFSUAC or SRFSU unit).
Phase 1
SRFSUAC
LED Status
Phase 2
SRFSU LED
status
Phase 3
SRFSU LED
Status
Diagnosis
Green Green Green All OK
Extinguished Green Green Replace Phase 1
SRFSUAC unit
Extinguished Extinguished Green Replace Phase 2*
SRFSU unit
Extinguished Green Extinguished Replace Phase 3*
SRFSU unit
*It is possible that both the Phase 1 SRFSU and Phase 2
(or 3)SRFSU units are faulty in this circumstance, but the
above diagnosis is more likely.
Obtain the correct model Secondary Unit (SRFSUAC or SRFSU)
from nVent and wire in to replace the faulty unit. Exercise care
when replacing the wiring to ensure the resulting wiring is
correct. It may be useful to take a photograph before removing
the faulty unit.
FRONT DOOR LED INDICATOR
This indicator will be illuminated green if all Secondary Units
are indicating correctly.
Installation and Operating Instructions

nVent.com/ERICO
|
17
7 SERVICING AND TROUBLESHOOTING
N-E SPARK GAP
PHASE
SPARK
GAPS
PHASE 2
SRFSU
UNIT
PHASE 3
SRFSU
UNIT
SPARK GAP FUSES (250A TO 800A MODELS)
PHASE 1 SRFSUAC UNIT
PHASE 1 SRFSUAC UNIT
SRF3500N
SECONDARY UNIT FUSES
N-E SPARK GAP
PHASE 1 SPARK GAP
SECONDARY UNIT FUSE
SRF163N
GREEN
STATUS
INDICATING
LED
DIVERTER
MODULE
STATUS
INDICATING
FLAG
ALARM CONTACTS
(ON SRFSUAC ONLY )
FIGURE YY- SECONDARY UNITS ( SRFSUAC AND SRFSU)
Installation and Operating Instructions

18
|
nVent.com/ERICO
8 BACKPLANE MODELS
9 SCHEMATIC DIAGRAMS
This document details the installation procedure for our current
range of standard SRFs.
Backplane units are also available, and are denoted by 'BP ' as
a suffix to the model number. These units are supplied without
the proprietary enclosure and are intended to be mounted in a
customer 's provided switchboard.
SINGLE-PHASE SRF MODELS
FUSE
SECONDARY UNIT
SG
PRIMARY
DIVERTER
SG
DIVERTER
TD
SECONDARY
DIVERTER
INPUT/LINE OUTPUT/LOAD
A
N
A
L
C
L
N
E E
Installation and Operating Instructions

nVent.com/ERICO
|
19
10 PHYSICAL DIMENSIONS
Note – Enclosures typically come with a gland plate on the
bottom, but not on the top. Simply punch the entry and exit holes
at the location that best suits the installation circumstances.
The single phase models will generally be punched completely
within the bottom gland plate, while the three phase models will
have the inputs punched on the top surface and the outputs on
the bottom surface. See Section 6.2 Cabling.
SRF Model Enclosure Size (mm)Mounting (mm)
W H D X1 X2 Y1 Y2 Fastener
Diameter
Weight
(Kg)
SRF163N 400 300 200 360 470 260 370 10 10.3
SRF125N 400 300 200 360 470 260 370 10 12.3
5RF363N 400 500 200 360 470 460 570 10 17.7
SRF3125N 400 500 200 360 470 460 570 10 21.6
SRF325ON 600 800 200 560 670 760 870 10 41.7
SRF3500N 800 1000 300 760 876 960 1076 10 76.6
SRF3800N 800 1200 300 760 876 1160 1276 10 97.2
D
H
Y2
Y1
W
X1
X2
Table 3. Physical Dimensions and Weights
Installation and Operating Instructions

4
Power Protection TVSS Device
Communications Line Protection Device
Ground Electrode
Power
Distribution Panel
Telephone Main
Distribution Frame
PCS,
Radio &
Telemetry
Equipment
Power Ground
AC Transformer
Sub Station
Overhead
Distribution
Voltage
Transmission
Lines
Telephone Lines
Direct Lightning Strike
nVent ERICO SYSTEM 3000
Active Lightning
Protection System
1Capture the
lightning
strike
3Dissipate Energy
into the Grounding
System
Low Impedance Ground
using at copper radials and
Ground Enhancement Material
Inspection Well
2Safely Convey
Energy to
Ground
5Protect Incoming
AC Power
Feeders
IS
File
Server
PABX
Inverter
Rectier
Batteries
Ground
Potential
Equalization Bonding
TVSS
Remote
Data
Terminal
Sub-Distribution
Board
Bond All Ground
Points Together
Printer
Billing
Computer
Signal Control
Lines
Induced Surge
Because lightning protection, grounding,
equipotential bonding and surge
protection are all interdependent
technologies, reliable protection of
structures and operations demands an
integrated system approach.
nVent ERICO SYSTEM 3000
Active Lightning Protection System
nVent ERICO SYSTEM 2000
Conventional Lightning
Protection System
6Protect Low Voltage
Data/Telecommunications
Circuits
1
4
2
5
3
6
Capture
the Lightning
Strike
Protect
Low Voltage Data
Telecommunications
Circuits
Safely
Convey Energy
to Ground
Protect Incoming
AC Power Feeders
Bond All Ground
Points Together
Dissipate Energy
into the Grounding
System
Our powerful portfolio of brands:
CADDY ERICO HOFFMAN RAYCHEM SCHROFF TRACER
WARNING: nVent products shall be installed and used only as indicated in nVent 's product instruction sheets and training materials. Instruction sheets are available at nVent.com/ERICO and from your nVent customer service representative.
Improper installation, misuse, misapplication or other failure to completely follow nVent 's instructions and warnings may cause product malfunction, property damage, serious bodily injury and/or death, and void your warranty.
© nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specifications without notice.
ERICO-IM-IP8344-SRFNSERIES-EN-1905 IP8344_C nVent.com/ERICO
|
20
The Six Point Plan of Protection from nVent ERICO
This manual suits for next models
7
Table of contents
Other nvent Industrial Electrical manuals
Popular Industrial Electrical manuals by other brands

Murata
Murata GRM1885C2A121GA01 Series Reference sheet

Murata
Murata GQM22M5C2H110GB01 Series Reference sheet

Murata
Murata GRM0335C1H5R6CA01 Series Reference sheet

Murata
Murata GRM1887U1H182JA01 Series Reference sheet

Murata
Murata GRM155R61E472KA01 Series Reference sheet

MEWOI
MEWOI MEWOI-PTS600 user manual

Moeller
Moeller VHI-NZM 10 installation instructions

Murata
Murata GJM0335C1E1R6CB01 Series Reference sheet

ITRON
ITRON EquaScan FNet installation manual

ZWAE
ZWAE ONIII Installation and service manual

OmniOn Power
OmniOn Power 150049763 quick start guide

Siemens
Siemens 3VA921-0JC22 Series operating instructions