RMI-JB3
Triple Hub Connection Kit Installation Instructions
(Killark HKB box shown)
DESCRIPTION
The nVent RAYCHEM RMI-JB3 Connection Kit is designed for
use with RAYCHEM RMI heating cables.
Materials to connect one or two heating cables to power are
included in this kit.
Refer to the RMI Installation and Maintenance Guide (H55047)
for additional information. For technical support call nVent at
(800) 545-6258.
TOOLS REQUIRED
• Wire cutters • Needle nose pliers
• Adjustable wrench • 3/16 in. slotted screwdriver
• 5/16 in. Allen wrench (for Killark HKB enclosure plugs)
• 1/2 in. drive ratchet (for Adalet XIHL enclosure plugs)
GENERAL INSTALLATION GUIDELINES
All junction boxes and thermostats must be mounted off the
pipe, typically on a beam or a stanchion, to prevent overheating.
All junction boxes, thermostats and transformers must be
located above grade level.
Conduit leading to junction boxes, thermostats and transformers
must be installed so that water does not enter the enclosure.
To prevent water ingress, use an agency approved Class I, Div.
1 sealing fitting with a drain valve. Angle the heating cable cold
lead downward where it exits the insulation.
This component is an electrical device that must be
installed correctly to ensure proper operation and to
prevent shock or fire. Read these important warnings and
carefully follow all of the installation instructions.
• To minimize the danger of fire from sustained
electrical arcing if the heating cable is damaged
or improperly installed, and to comply with the
requirements of nVent, agency certifications,
and national electrical codes, ground-fault
equipment protection must be used. Arcing may
not be stopped by conventional circuit breakers.
• Component approvals and performance are
based on the use of nVent-specified parts
only. Do not use substitute parts or vinyl
electricaltape.
KIT CONTENTS
Item Qty Description
A 1 Junction Box with Lid (Killark HKB or Adalet XIHL)
B 3 3/4 x 1/2 in. NPT reducers
C 1 Terminal Block (max: one 6 AWG wire or two 12
AWG wires)
A
B
(Killark HKB box shown)
C
APPROVALS
Class I, Div. 1 & 2, Groups B, C, D
Class II, Div. 1 & 2, Groups E, F, G
Class III
APPROVED
Hazardous Locations