OBO Bettermann isCon Series User guide

01/2018 EN
isCon®
System instructions
Building Connections

© 2018 OBO Bettermann GmbH & Co. KG
Reprinting, even of extracts, as well as photographic or electronic reproduction are prohibited!
isCon® is a registered brand of OBO Bettermann GmbH & Co. KG
OBO isCon
®
System instructions

System instructions OBO isCon®EN | 3
Table of contents
Table of contents
1 About these instructions . . . . . . . . . . . . . . . . . . . . .5
1.1 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Using these instructions . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Types of safety information . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 Correct use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.5 Declaration of conformity . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.6 Basic standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 General safety information . . . . . . . . . . . . . . . . . . . .7
3 Product description . . . . . . . . . . . . . . . . . . . . . . . .8
3.1 Basic principles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2 isCon® conductor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.3 Insulated air-termination rods . . . . . . . . . . . . . . . . . . . . . . 12
3.4 System accessories for fastening . . . . . . . . . . . . . . . . . . . . 14
3.4.1 Air-termination rod stand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.4.2 Air-termination rod support for isFang mounting . . . . . . . . . . . . . . . . . 17
3.4.3 Holder for the isCon® conductor . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.5 System accessories for connection . . . . . . . . . . . . . . . . . . . 19
4 Planning an installation. . . . . . . . . . . . . . . . . . . . . 20
4.1 Schematic diagram of the isCon® system using the example of the
isCon® ProPl 75 SW . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.2 Calculating, checking and maintaining the separation distance . . . . 23
4.3 Cable lengths and lightning protection classes . . . . . . . . . . . . . 23
4.4 Installation in potentially explosive areas . . . . . . . . . . . . . . . . 25
4.5 Soft-covered roofs . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5 Installing the isCon® system . . . . . . . . . . . . . . . . . . 28
5.1 Cutting and removing the insulation of the isCon® conductor . . . . . . 28
5.1.1 Removing the light grey protective jacket (isCon® ProPI 75 LGR) . . . . . . . . 28
5.1.2 Revealing the copper core for connection . . . . . . . . . . . . . . . . . . . . 29
5.2 Mounting the isCon® connect connection elements . . . . . . . . . . 30
5.2.1 Air-termination rod with internal isCon® conductor . . . . . . . . . . . . . . . . 32
5.2.2 Air-termination rod with external isCon® conductor . . . . . . . . . . . . . . . . 38
5.3 Fastening the air-termination rod in the air-termination rod stand . . . 42
5.3.1 Mounting the concrete plinth . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.3.2 Erecting the air-termination rod stand . . . . . . . . . . . . . . . . . . . . . . 42
5.3.3 Fastening the air-termination rod in the air-termination rod stand . . . . . . . . 45
5.4 Fastening the air-termination rod to pipes, a wall or T support . . . . . 47
5.5 Routing the isCon® conductor. . . . . . . . . . . . . . . . . . . . . . 48
5.6 Attaching the potential connection . . . . . . . . . . . . . . . . . . . 49
5.6.1 Installing the potential connection on an insulated air-termination rod . . . . . . 49
5.6.2 Installing the potential connection on the end of the isCon® conductor . . . . . 52
5.6.3 Including the air-termination rod stand in the functional equipotential bonding . 54
5.6.4 Installing additional potential connections . . . . . . . . . . . . . . . . . . . . 55
5.6.5 Creating additional equipotential bonding for isCon® ProPlus in potentially
explosive areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

OBO Bettermann
4 | EN
Table of contents
6 Mounting variants . . . . . . . . . . . . . . . . . . . . . . . . 58
6.1 Separate lightning protection ring conductor . . . . . . . . . . . . . . 58
6.2 Metallic roof parapet . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.3 Internal and external isCon® conductor . . . . . . . . . . . . . . . . . 61
6.4 Lightning protection class I . . . . . . . . . . . . . . . . . . . . . . . 62
6.5 isCon® conductor included in the ring conductor . . . . . . . . . . . . 63
7 Checking the lightning protection system . . . . . . . . . . 64
8 Testing report for the OBO isCon® system . . . . . . . . . . 65

System instructions OBO isCon®EN | 5
About these instructions
1 About these instructions
1.1 Target group
These mounting instructions are intended for specialists, who are quali-
fied to erect lightning protection systems, e.g. lightning protection spe-
cialists. These specialists must know the lightning protection standards
applicable at the mounting location, as well as the generally recognised
rules of technology.
1.2 Using these instructions
• These instructions are based on the standards valid at the time of
compilation (January 2018).
• Before commencing work, read these instructions through once com-
pletely. In particular, please observe the safety instructions.
• Keep all the documents supplied with the isCon® system safe, so that
the information is available should you need it.
• We will not accept any warranty claims for damage caused through
non-observance of these instructions.
• Regional and seasonal factors were not taken into account.
• To find out more about planning and installation using the OBO isCon®
system, we recommend a comprehensive training course.
1.3 Types of safety information
WARNING
Type of risk!
Shows a possibly risky situation. If the situation is not avoided, then death
or serious injury may result.
CAUTION
Type of risk!
Shows a possibly risky situation. If the situation is not avoided, then light
or minor injury or damage to property may result.
ATTENTION
Type of risk!
Shows a possibly hazardous situation. If the situation is not avoided, then
damage to the product or the surroundings may occur.
Note! Indicates important information or assistance!

OBO Bettermann
6 | EN
About these instructions
1.4 Correct use
The OBO isCon® system is a lightning protection system for the external
lightning protection of buildings and systems, which, in the case of direct
lightning strikes, can arrest the lightning surge currents into the earth,
thus protecting the building, the system and people against the impacts of
the lightning strike, e.g. fires, mechanical building damage and possibly
lethal voltages and current pulses.
The system is not designed for any other purpose than the one described
here. If the system is installed and used for another purpose, any liability,
warranty or damage claims shall be rendered null and void.
If you require information on the use of the OBO isCon® system for some-
thing other than under the conditions of use described here, please speak
to your OBO contact.
1.5 Declaration of conformity
Lightning protection components are not subject to an EU directive.
Instead, OBO makes the manufacturer's declarations of conformity avail-
able for the appropriate components of the lightning protection systems.
These declarations of conformity certify the agreement with the named
standards and stored documents, but do not, however, contain any guar-
antee of properties.
You can find individual proofs for lightning protection components on the
OBO web pages (www.obo-bettermann.com).
1.6 Basic standards
Comply with the following standards*, amongst others, during the plan-
ning, mounting, maintenance and repair of lightning protection systems:
• DIN EN 62305-1 (IEC 62305-1, VDE 0185-305-1), Protection against
lightning Part 1: General principles
• DIN EN 62305-2 (IEC 62305-2, VDE 0185-305-2), Protection against
lightning Part 2: Risk management
• DIN EN 62305-3 (IEC 62305-3, VDE 0185-305-3), Protection against
lightning ‒ Part 3: Protection of structural facilities and persons
• DIN EN 62305-4 (IEC 62305-4, VDE 0185-305-4), Protection against
lightning ‒ Part 4: Electrical and electronic systems within structures
• DIN EN 62561-1 (IEC 62561-1, VDE 0185-561-1), Lightning protection
system components – Part 1: Requirements for connection compo-
nents
• DIN EN 62561-2 (IEC 62561-2, VDE 0185-561-2), Lightning protection
system components – Part 2: Requirements for conductors and earth
electrodes
• DIN EN 62561-4 (IEC 62561-4, VDE 0185-561-4), Lightning protection
system components – Part 4: Requirements for conductor fasteners
• DIN 18014, Foundation earthers
• IEC TS 62561-8 (draft)
* Date of standards: January 2018

System instructions OBO isCon®EN | 7
General safety information
2 General safety information
Observe the following general safety information on handling the OBO
isCon® system:
• The work may only be carried out by lightning protection specialists,
who have been trained for the installation of standard-conformant
lightning protection systems.
• If there is a lightning strike, lethal currents can flow through the light-
ning protection system. Never work on the elements of the lightning
protection system during a thunderstorm or if there is a risk of one.
• Lethal voltages can occur during the handling of electrical resources.
Therefore, never work on parts through which power is flowing. Wear
suitable protective clothing and comply with all the required safety
guidelines!
• To install the OBO isCon® system, use only components of the OBO
product range, as otherwise there is no guarantee that safe installation
is possible.
• Only the jacketing of the grey OBO isCon® conductor may be painted a
different colour, as it does not possess any electrical properties which
could be at risk from paint.
• The production method means that metallic objects may have areas
with sharp edges. Wear suitable protective gloves to avoid cutting
injuries.
• When erecting function maintenance systems, take the necessary fire
protection regulations into account. These instructions do not mention
any fire protection standards which are to be complied with. Read the
OBO fire protection guide (article number: 9134859) for more informa-
tion.

OBO Bettermann
8 | EN
Product description
3 Product description
3.1 Basic principles
Without any additional countermeasures, the high-voltage pulses which
occur when there is a direct lightning strike will cause arcing to insula-
tion surfaces. This effect is termed a creep flashover. When the so-called
creep discharge inception voltage has been exceeded, surface discharge
is initiated, which can bridge a gap of several metres. To avoid dangerous
arcing between conductive parts (electrical systems, pipelines, etc.), the
maintenance of the separation distance is a key requirement when plan-
ning and implementing a lightning protection system.
These days, the roof level of building complexes is used as an installation
area for air-conditioning, ventilation, transmission and energy collection
systems, meaning that the structural features may be in the way of the
required spacing between the air-termination systems and the electrical
installations.
The isCon® insulated lightning protection system is used to maintain the
required separation distance. Depending on the design, after the first
potential connection behind the connection element on the air-termination
rod, the isCon® conductor reflects an equivalent separation distance of
up to 0.45‒0.9 metres in the air or double that in solid matter. This means
that installation is possible directly on metallic and electrical structures. If
there is a direct lightning strike, the incoming energy is arrested through
the isCon® conductor to the building's earthing system. There is no direct
arcing between the down-conductor and the building to be protected.
The isCon® system has a tested arresting capacity of 150‒200 kA light-
ning surge current (10/350 μs). It primarily consists of the following com-
ponents:
– isCon® conductor
– Insulated air-termination rods
– System accessories for fastening (air-termination rod stand, support
and holder)
– System accessories for connection
3.2 isCon® conductor
According to DIN EN 62305-3/VDE 0185-305-3/IEC 62305-3, the insu-
lated isCon® conductor implements a separation distance of 0.45‒0.9
metres in the air and 0.9‒1.8 metres in the case of solid mater-
ials, depending on the product design. The isCon® conductor is equipped
with an external semi-conductive jacket, allowing it to limit high lightning
voltage pulses against a reference potential, by creating a connection be-
tween the external semi-conductive jacket and the building's equipotential
bonding, which is not energised with lightning current, in the area of the
connection element.
The isCon® conductor is flame-resistant according to DIN EN 60332-1-2,
weather-resistant and halogen-free. It is suitable for routing in external
areas and can be routed on roofs, in walls, in concrete, in facade installa-
tions or in buildings.

System instructions OBO isCon®EN | 9
Product description
The isCon® conductor is sold by the metre and in five variants:
Conductor type Characteristic Item number
isCon® PR 90 SW (Premium) Black 5408 018
isCon® Pro 75 SW Black 5408 008
isCon® ProPl 75 SW Black 5408 002, 5408 004,
5408 006
isCon® ProPl 75 LGR Light grey 5407 995, 5407 997
isCon® BA 45 SW (Basic) Black 5408 014
Table 1: Product variants, isCon® conductor
The light grey isCon® conductor is also suitable for routing in the earth. It
can also be painted, e.g. with the paint of the facade. As the external light
grey protective jacket is non-conductive, it must be removed in the contact
areas.
35 mm²
Ø 23 mm
Ø 26 mm
1
2
3
6
5
4
Figure 1: Schematic diagram of the isCon® conductors ProPl 75 SW and
ProPl 75 LGR
35 mm²
x
x = Ø 20 mm
(Pro 75 SW/BA 45 SW)
x = Ø 23 mm
(PR 90 SW)
1
2
3
4
Figure 2: Schematic diagram of the isCon® conductors Pro 75 SW, BA 45 SW
and PR 90 SW
Legend:
1
Round conductor, multi-wire, 35 mm2, Cu
2 Inner conductive layer
3
Insulation
4 Outer conductive layer
5
External jacket
6
External jacket, light grey

OBO Bettermann
10 | EN
Product description
The isCon® conductor may only be connected to air-termination rods or
forwarding systems using system-tested connection elements (see also
“„5.2 Mounting the isCon® connect connection elements“ on page 30).
Type isCon® BA 45
SW
isCon® Pro 75
SW
isCon® ProPl 75
SW
isCon® ProPl 75
LGR
isCon® PR 90
SW
Colour Black Black Black Light grey Black
Equivalent separation distance,
air (cm)
≤ 45 ≤ 75 ≤ 75 ≤ 75 ≤ 90
Equivalent separation distance,
solid materials (cm)
≤ 90 ≤ 150 ≤ 150 ≤ 150 ≤ 180
Equivalent separation distance,
mixed materials See EN 62305-3
External diameter ~ 20 mm ~ 20 mm ~ 23 mm ~ 26 mm ~ 23 mm
Round conductor, multi-wire, Cu 35 mm2
Conductor weight ~ 0.570 kg/m ~ 0.570 kg/m ~ 0.694 kg/m ~ 0.868 kg/m ~ 0.666 kg/m
Temperature range for routing min. -5 °C, max. 40 °C
Operating temperature min. -30 °C, max. 70 °C
Bend radius min. 200 mm min. 200 mm min. 230 mm min. 260 mm min. 230 mm
Maximum tensile load 1 750 N
Routing in the earth No No No Yes No
Can be painted No No No Yes No
Weathering resistance (UV-
stabilised)
Ozone resistant according to DIN EN 60811-2-1 Section 8
Sunlight resistance test according to UL 1581 Section 1200
Coldness impact resistance according to DIN EN 60811-1-4 Section 8.5
Fire load (kWh/m) 3.3 4.3 5.1 4.2
Lightning current carrying
capacity (class/Iimp (kA)
H1/150 H1/150 H1/150 H2/200
Testing certificate according to
IEC TS 62561-8 Yes
Halogen-free Yes
Softener None
Table 2: Technical data of the isCon® conductors

System instructions OBO isCon®EN | 11
Product description
isCon
1
2
Figure 3: isCon
®
conductor in the air-termination rod with internal connection ele-
ment
1
(type isCon® IN connect, isCon® IN con PRE, isCon® IN con 2)
and isCon® connection element
2
(type isCon® connect)

OBO Bettermann
12 | EN
Product description
3.3 Insulated air-termination rods
The insulated air-termination rods of the isCon® system come in three
parts and consist of the air-termination rod (length 1,000 mm), the insulat-
ed central rod (length 1,500 mm) and the retaining rod (length 1,325 mm
or 3,325 mm).
1
2
3
Figure 4: Air-termination rod components
Legend:
1 Air-termination rod
2
Insulated central rod
3
Retaining rod
The metallic components of the rods are made of aluminium and stainless
steel (V2A). The insulated central rod is made of glass-fibre-reinforced
plastic (GRP) and allows sufficient spacing of the arresting components
(connection element at the bottom end of the air-termination rod) to all
roof structures. In addition, it guarantees a sufficient distance of 1,500 mm
to the equipotential bonding, which is connected at the bottom end of the
insulated rod (see also Figure 13 No.
5
).

System instructions OBO isCon®EN | 13
Product description
The system comprises three types of air-termination rods (see Figure 5).
This means it can be used in different mounting situations.
1 2 3
Figure 5: Three air-termination rod types (without potential connection)
Legend:
1 Air-termination rod with internal isCon® conductor and side exit
2
Air-termination rod with external isCon® conductor
3 Air-termination rod with internal isCon® conductor and bottom exit
Type Item number
Overall
length
m
Diameter
mm Material Type (Fig. 4)
Corresponding
air-termination rod
stand
isFang IN-A 4000 5408 938 4,000 50 Alu/GRP
1
isFang 3B-100-A
isFang IN-A 6000 5408 940 6,000 50 Alu/GRP isFang 3B-150-A
isFang IN-A 8000 5408 888 8,000 50 Alu/GRP isFang 3B-250-A
isFang IN-A 10000 5408 890 10,000 50 Alu/GRP isFang 3B-250-A
isFang 4000 AL 5408 943 4,000 40 Alu/GRP
2
isFang 3B-100 AL
isFang 6000 AL 5408 947 6,000 40 Alu/GRP isFang 3B-150 AL
isFang 4000 5408 942 4,000 40 V2A/GRP isFang 3B-100
isFang 6000 5408 946 6,000 40 V2A/GRP isFang 3B-150
isFang IN 4000 5408 934 4,000 50 Alu/GRP
3
To be fastened with
support system
isFang IN 6000 5408 936 6,000 50 Alu/GRP
isFang IN 8000 5408 868 8,000 50 Alu/GRP
isFang IN 10000 5408 870 10,000 50 Alu/GRP
Table 3: Technical data of the isCon® air-termination rods
Contact OBO Customer Service about other air-termination rod variants.

OBO Bettermann
14 | EN
Product description
Scope of delivery of the air-termination rods with internal conductor:
– Insulated air-termination rod with side exit
– Internal connection element (type isCon® IN connect)
– Potential connection element (type isCon® IN PAE)
– Brief instructions
Scope of delivery of the air-termination rods with external conductor:
– Insulated air-termination rod with bottom exit
– Brief instructions
3.4 System accessories for fastening
Air-termination rod stands (see section 3.4.1) or supports for wall or pipe
mounting (see section 3.4.2) can be used to fasten the isCon® air-temin-
ation rods. In addition, the system offers special holders for the isCon®
conductor (see section 3.4.3).
3.4.1 Air-termination rod stand
Figure 6: Air-termination rod stand with concrete blocks
The isCon® system contains folding air-termination rod stands of different
sizes, to allow the isFang air-termination rods to be mounted on flat roofs,
for example. The tripod air-termination rod stands allow the erection of the
air-termination rods without penetrating the building structure with bolts/
anchors.
Instead, the air-termination rod stands are weighed down with FangFix
concrete blocks. The number of blocks required is dependent on the
height of the air-termination rod and the wind speed zone.
Note: You can find further information on wind speed zones in the OBO TBS
lightning protection guide (order no.: 9131970) and national directives.
The air-termination rod stand can compensate for a slope in the roof
surface of up to 5° (see also Figure 48 on page 44). To protect the
roof surface, it may be wise to place a protective film under the concrete
blocks of the air-termination rod stand. We recommend contacting the
roofer about this.
Scope of delivery of the air-termination rod stand:
– Tripod air-termination rod stand
– Crossbar for potential connection with bolt, nut and lock washer
– Brief instructions

System instructions OBO isCon®EN | 15
Product description
D
B
L
H
Figure 7: For the dimensions of the air-termination rod stand, see Table 4
Type Item number Dimension B
mm
Dimension D
mm
Dimension L
mm
Dimension H
mm Material
with side exit for internal isCon® conductor
isFang 3B-100-A 5408 930 1,026 50 600 885 V2A
isFang 3B-150-A 5408 932 1,500 50 900 1,275 V2A
isFang 3B-250-A 5408 902 2,900 50 1,450 2,055 V2A
with bottom exit or for external isCon® conductor
isFang 3B-100 AL 5408 966 1,000 40 600 885 Al
isFang 3B-150 AL 5408 967 1,500 40 900 1,275 Al
isFang 3B-100 5408 968 1,000 40 600 885 V2A
isFang 3B-150 5408 969 1,500 40 900 1,275 V2A
Table 4: Technical data of the air-termination rod stand
The isCon® concrete blocks weigh approx. 16 kg and are screwed to
the bottom of the unfolded air-termination rod stand. The blocks can be
stacked to increase the stand weight (e.g. for increased wind speeds)
(see Figure 8). Additional blocks can mounted internally in the air-termin-
ation rod stands of diameter 1,500 mm (unfolded).
Figure 8: Increasing the stand weight by stacking the concrete blocks

OBO Bettermann
16 | EN
Product description
1
2
3
4
5
Figure 9: Concrete block with fastenings
Legend:
1
Hexagonal nuts (with washers) for height compensation
2 Lock nut (with washer and plate)
3
Concrete block
4
Edge protection
5 Threaded rod
Product Type Item number Features Material
FangFix concrete
block
F-FIX-S16 5403 227 Weight: 16 kg; Ø 365 mm;
stackable
Concrete, frost-resistant
Edge protection for
concrete block 16 kg
F-FIX-B16 3B 5403 238 Edge protection with gland hole Polyamide
Threaded rod isFang 3B-G1 5408 971 270 mm, for 1 concrete block1) V2A
Threaded rod isFang 3B-G2 5408 972 340 mm, for 2 concrete blocks1) V2A
Threaded rod isFang 3B-G3 5408 973 430 mm, for 3 concrete blocks1) V2A
Threaded rod isFang 3B-G4 5408 905 500 mm, for 4 concrete blocks1) V2A
Table 5: Technical data of the concrete blocks with accessories
1) Number of concrete blocks for mounting on flat surface. For height com-
pensation in an inclined position, select a longer threaded rod if neces-
sary (see Figure 48 on page 44).
Nuts and washers are included in the scope of delivery of the threaded
rods.

System instructions OBO isCon®EN | 17
Product description
3.4.2 Air-termination rod support for isFang mounting
160 mm
200-300 mm
∅ 50-300 mm
∅ 50-300 mm
100/200/300 mm
∅ 40-50 mm max. 50 x 70 mm
∅ 50-60 mm
≤ 160 mm
200 mm
200 mm
1
2
4
3
6
5
78
9
10
Figure 10: Support for wall or pipe mounting of the isFang air-termination rods
Fig no. Type Item number
Ø isCon
air-termination
rod mm
Features Material
1
isFang TW30 5408 952 40/50 Surface mounting, distance from wall 30 mm V2A
2
isFang TW80 5408 950 40/50 Surface mounting, distance from wall 80 mm V2A
3
isFang TW200 12 5408 910 40/50 Surface mounting, distance from wall 200 mm V2A
4
isFang TW200 5408 954 40/50 Surface mounting, variable distance from wall
200-300 mm
V2A
5
isFang TW200 Set 5408 914 40/80 Mounting set for T support, in conjunction with
isFang TW200
4
V2A
6
isFang TR100 5408 956 40/50 Tightening strap clip for round construction
pipes of Ø 50-300 mm; distance to pipe 40 mm
V2A
6
isFang TR100 100 5408 955 40/50 Tightening strap clip for round construction
pipes of Ø 50-300 mm; distance to pipe
100 mm
V2A
6
isFang TR100 200 5408 957 40/50 Tightening strap clip for round construction
pipes of Ø 50-300 mm; distance to pipe
200 mm
V2A
7
isFang TR100 300 5408 959 40/50 Tightening strap clip for round construction
pipes of Ø 50-300 mm; distance to pipe
300 mm
V2A
8
isFang TS40-50 5408 958 40/50 Pipe ribbon clip for round construction pipes of
Ø 40-50 mm; distance to pipe 40 mm
V2A
9isFang TS50-60 5408 960 40/50 Pipe ribbon clip for round construction pipes of
Ø 50-60 mm; distance to pipe 30 mm
V2A
10
isFang TS50x50 5408 964 40/50 Pipe ribbon clip for round construction pipes of
max 50 x 70 mm; distance to pipe 30 mm
V2A
Table 6: Technical data of the isCon® supports

OBO Bettermann
18 | EN
Product description
3.4.3 Holder for the isCon® conductor
5403 117
10 kg
1
23
6
5
4
7
8
Figure 11: Holder for the isCon® conductor
Fig no. Product Type Item number Features
1
Cable bracket for isCon
conductor
isCon® H VA
isCon® H 26 VA
5408 056
5408 064
Ø 23 mm; V2A
Ø 26 mm; V2A
2
VA cable bracket with
tightening strap
isCon® HS VA
isCon® HS 26 VA
5408 052
5408 068
Ø 23 mm; V2A; 2 m tightening strap
Ø 26 mm; V2A; 2 m tightening strap
3
PA cable bracket with
tightening strap
isCon® HS PA
isCon® HS 26 PA
5408 054
5408 066
Ø 23 mm; PA black; 2 m tightening strap
Ø 26 mm; PA light grey; 2 m tightening strap
4
Terminal for steel support
with 1, bolt M16x6 and
washer
TKI 13-6 1483587 Galvanised terminal with M6 internal thread to
fasten an isCon H VA cable bracket with
M16x6 bolt
5
Roof cable bracket with
adapter and M-Quick
cable bracket
165 MBG-8
165 MBG UH
M-Quick M25 SW
M-Quick M25 LGR
5218 691
5218 882
2153 787
2153 734
PA/PE roof cable bracket, filled with frost-
resistant concrete. Clamping range of M-Quick
cable bracket ..SW: 20-25 mm, for ...LGR:
25-32 mm
6
VA roof cable holder for
sloping roof
isCon® H280 VA
isCon® H280 26 VA
5408 047
5408 074
Ø 23 mm; V2A
Ø 26 mm; V2A
7
PA roof cable holder for
sloping roof
isCon® H280 PA
isCon® H280 26 PA
5408 049
5408 072
Ø 23 mm; PA black
Ø 26 mm; PA light grey
8
Spacer for stand-off
routing of the isCon
conductor
isCon® DH 5408 043 Material: GRP; clamping range Ø 23-26 mm;
height 1,000 mm, can be shortened; for
mounting on FangFix concrete block, 10 kg,
with edge protection
Table 7: Technical data of the holder for the isCon® conductor

System instructions OBO isCon®EN | 19
Product description
3.5 System accessories for connection
123 4
5
6 7
8
9
Figure 12: Accessories for connecting the isCon® conductor
Fig no. Product Type Item number Features
1Connection element isCon® connect
isCon® con 2
isCon® con PRE
5408 022 See “„5.2 Mounting the isCon® connect
connection elements“ on page 30
2
Stripping tool isCon® stripper 2 5408 013 To remove the insulation of the isCon®
conductor (see section 5.1.2 on page 29)
3
Cleaning cloth isCon® EPPA 004 5408 060 Cellulose polypropylene paper with abrasive
sections, doused with impregnation solution,
for cleaning the external jacket of the OBO
isCon® conductor (see Figure 22 on page
30)
4
Potential connection
terminal
isCon® PAE 5408 036 Potential connection of the isCon® conductor;
seat Ø 17-25 mm, V2A
5Potential connection clip 927 2 6-K 5057 599 Potential connection on the air-termination
rod for external isCon® conductor; seat
3/8-4", V2A
6Connection plate for one
isCon® conductor
isCon® AP1-16 VA 5408 026 16 x 8-10 mm, V2A
7
Connection plate for two
isCon® conductors
isCon® AP2-16 VA 5408 028 16 x 8-10 mm, V2A
8
Strip clip 555 7.6x380 SWUV 2332 784 Black; weatherproof, length approx. 380 mm
9
Information sign for
labelling of the lightning
protection system
isCon® HWS 5408 059 Self-adhesive, with 4 fastening holes Ø 6.5
mm
10
Information sign for
labelling of the lightning
protection system
isCon® HWS EN 5408 059 Self-adhesive, with 4 fastening holes Ø 6.5
mm
Table 8: System accessories for connection

OBO Bettermann
20 | EN
Planning an installation
4 Planning an installation
When planning the lightning protection of buildings, we recommend tak-
ing the following aspects and possible activities into account:
– Determine the protection area, the required height and the arrange-
ment of the air-termination rods, according to DIN EN 62305-3 (IEC
62305-3, VDE 0185-305-3).
– Calculate the necessary separation distance (see “„4.2 Calculating,
checking and maintaining the separation distance“ on page 23).
– Calculate the number of isCon® conductors and air-termination sys-
tems according to the lightning protection class and required cable
length (see “„4.3 Cable lengths and lightning protection classes“ on
page 23).
– Additional measures are required for installations in potentially ex-
plosive areas (see “„4.4 Installation in potentially explosive areas“ on
page 25) and on soft-covered roofs (see “„4.5 Soft-covered roofs“
on page 27).
– When erecting air-termination rods, take the appropriate wind speed
zones into account. You can find further information in the OBO TBS
lightning protection guide and national directives.
– Ensure that there is equipotential bonding (see “„5.6 Attaching the
potential connection“ on page 49).
Note: You can find additional detailed planning aids on lightning and surge pro-
tection systems in the OBO TBS lightning protection guides (order no.:
9131970).
Note: To guarantee the functionality of the isCon® lightning protection system,
tested components of the OBO delivery range must be used.
Other manuals for isCon Series
1
This manual suits for next models
7
Table of contents
Other OBO Bettermann Industrial Electrical manuals
Popular Industrial Electrical manuals by other brands

DX Engineering
DX Engineering Maxi-Core DXE-FCC050-H05-A manual

Siemens
Siemens SITRANS TCSC operating instructions

Murata
Murata GRM216R71C473KA01 Series Reference sheet

Lika
Lika SFP user manual

Murata
Murata GRM0335C1H3R2CA01 Series Reference sheet

Eaton
Eaton Crouse-Hinds FSQ Series Installation & maintenance information