Notes for Environments featuring explosions risks (Ex)
Ensure the sensor suits the classification of the area, and the characteristics of flammable substances that can be
found on the system.
Operate in such a manner as to absolutely avoid causing sparks, there where an air-gas burning mixture is found in
the environment.
Working in this area is prohibited unless the person is not qualified.
Safety measures shall be taken to avoid harming individuals and damaging the structure.
See “Additional Safety Instruction”for more information.
4.2 ELECTRICAL WIRING
The connection shall be made in accordance with the wiring diagram with at
least 3 x 0.75 mm² cables depending on the desired switching function. In
selecting the cable, take care it suits the envisaged application field (see
temperature, weather influences, aggressive atmosphere etc.).
Magnetic switches shall be connected in accordance with the laws in force in
the country of installation, and mind the power supply data.
Notes for environments featuring explosion risks (Ex)
The connections shall be made through cable entrances or tube piping in compliance with the EN 60079-14
standard.
The cable entrance shall not affect the specific properties of the protection method as indicated in the EN 60079-1.
When the cable inlet is made by using a cable gland, the latter shall be correctly chosen as a function of the system
type and of the cable type. The cable gland shall be screwed tight to allow the sealing rings to exert the required
pressure.
The ground connection must be connected to the general system ground with a conductor of suitable section
(normally the same section as the mains connection).
5. SETTING AT WORK
Make sure that the instrument is not used beyond the allowed limits (e.g. temperatures) and that the electrical
rating applied complies with the technical data.
Before operating them, locate the magnetic switches at the desired heights and make the float of the level indicator
slide slowly inside the tube bottom up. After that, make it run down slowly. If this is not possible, carry out the
operation by making them float, with the magnet on the top, beside the magnetic switch. If no float is available, you
may even use a permanent magnet with radial polarity.
Ensure the instrument correctly performs the switching by varying the level inside the indicator a few times.
6. CALIBRATION
The functional test is meant to assess correct operation of the reed type contacts.
Disconnect the power supply connection before carrying out the test. To rate the switching, use a continuity tester or
similar units.
Since magnetic switches are bistable, they demand a given initial condition before being operated, otherwise the
switching function risks to become faulty and engages a false position of the contact in the process control.
Notes for Environments featuring explosion risks (Ex)
The testing equipment for the functional test shall be appropriate or certified for use in dangerous areas. Only qualified
persons can carry out this work. The competent technical staff shall connect and disconnect the electrical lines.
Notes for Model T25 HT Sensor
During the calibration stage, it being understood that the position along the axis is at the discretion of the installer,
the radial position shall be the one opposite the rod that holds the Reeds as shown in Fig. 2.