FUEL TRANSFER CONTROLLER
Part Number: 3350-FTC Fuel Transfer Controller
INSTALLATION AND OPERATING INSTRUCTIONS
The 3350-FTC Fuel Transfer Controller is designed to display the contents of the “Day” or “Consumption” Fuel
Tank and control the pumping of fuel from the storage or “Bunker” tanks into that tank.
The 3350-FTC is housed in a standard 2” / 52mm diameter panel gauge instrument that contains a blue LED digital
display, front panel “START” and “STOP” buttons and a 10 Amp changeover relay to control the Fuel Transfer
Pump.
It has a standard NMEA2000® micro sized male plug to link to the NMEA2000® network and 3 x ¼” male spade
terminals to link to the transfer pump wiring.
SAFETY WARNING
This instrument should only be installed by a person competent and experienced in working on electrical systems
on boats.
BEFORE BEGINNING WORK THE BATTERY SHOULD BE DISCONNECTED TO AVOID THE RISK OF A SHORT CIRCUIT,
A FIRE OR AN EXPLOSION.
Before drilling any holes to mount the unit or to run the cabling always make sure it is safe to do so.
The 3350-FTC Fuel Transfer Controller displays the “Day” or “Consumption” tank level as a % level and so it should
be situated within sight of the helm position.
If there are multiple helm positions then multiple instruments can be installed. In this event the pump control
wiring can be connected in parallel so that either instrument can control the filling of the Day tank.
The instrument is designed to be panel mounted in a 2” or 52mm clearance hole and requires clearance of at
least 100mm behind the hole to allow for cable connections to be run without undue stress.
It is fixed to the panel by using a reversible rear mounting ring nut which can accommodate panels of up to 25mm
thick. The front of the instrument is sealed to IP67 and when correctly mounted in a panel using the supplied
gasket will provide an IP67 seal to the panel.
A mounting hole providing clearance for a 2” / 52mm diameter should be cut at the desired location. The
instrument should be inserted from the front with it’s gasket. The mounting ring nut is attached at the rear and
tightened sufficiently to hold the instrument securely.
THE UNIT ADDRESS SWITCH ON THE BACK OF THE INSTRUMENT MUST BE SET TO EXACTLY MATCH THE UNIT
ADDRESS SWITCH ON THE “DAY” OR “CONSUMPTION” TANK LEVEL SENDER. IF THIS IS NOT DONE THEN THE UNIT
CANNOT STOP A TRANSFER AND A FUEL SPILL COULD HAPPEN.
WIRING AND NETWORK
The male NMEA2000® micro plug should be attached to a Tee connector on the NMEA2000® network either
directly or by using a NMEA2000® micro drop cable.
The wiring to the transfer pump should be as follows:
The power control cables on the back of the 3350-FTC should be connected to the “C” and “NO” terminals.
INSTALLATION AND LOCATION
1
LED Indicator
Fuel Transferring
LED Indicator
Display
STARTSTOP
0
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
NC
C
NO
Unit Address Switch
3802 T - Adaptor
Fuel Transfer Controller
NMEA2000® Network Backbone
0
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
NC
C
NO
Bunker Tank Day or
Consumption Tank
Fuel Transfer
Pump
NC-Terminal
C-Terminal
NO-Terminal
The 3350-FTC Fuel Transfer Controller can be operated in either Manula or Automatic modes.
MANUAL OPERATION
When the user wants to refill the “Day” or “Consumption” tank he simply presses the green START button which
will cause the relay to start the fuel transfer pump if the level in the Day Tank is less than 95%.
The user can stop the transfer at any time by pressing the red STOP button.
AUTOMATIC OPERATION
The unit can be set to automatically start the Fuel transfer if the level in the Day tank falls below a user settable
value. This feature can be enabled by the user setting the automatic start level to 0% through to 70% at 10%
intervals.
This is done by pressing and holding the STOP button and pressing the START button until the display shows the
required start level percentage. If the value is set to 0% then the automatic start feature will remain disabled and
not be functional.
DURING FUEL TRANSFER
Whilst the fuel is transferring the red LED will flash to indicate that a Fuel transfer is in progress.
As soon as the tank level has reached 95% then the relay will stop the transfer automatically.
Please note that the user can stop the transfer at any time by pressing the red STOP button.
If the ship’s power is removed during fuel transfer the transfer will stop. For safety reasons when the power is
restored the unit will NOT restart the transfer unless the START button is depressed again or the automatic start
feature is enabled and the tank level is below the user settable threshold.
CLEANING
The 3350-FTC instrument can be cleaned with mild soap and water. Do NOT use solvents or abrasive or pressure
washers as these could damage the front of the instrument.
OPERATION
2
Copyright © 2016 Offshore Dynamics Ltd. All rights reserved.Our policy is one of continuous product improvement so product
specifications are subject to change without notice. Offshore Dynamics products are designed to be accurate and reliable. However,
they should be used only as aids to vessel monitoring, and not as a replacement for traditional navigation and vessel monitoring
techniques. NMEA2000® is a registered trademark of the National Marine Electronics Association.
Offshore Dynamics Ltd
Unit 10 -11 Milton Business Centre, Wick Drive,
New Milton, Hampshire, BH25 6RH, United Kingdom
Tel: +44(0)1425 610022 Fax: +44(0)1425 614794
Email: [email protected] Web: www.osukl.com
DOC NO. 00112 Rev. 1.0
STARTSTOP
Fuel Transferring
Transferring can
be manually stopped
any time

Other Offshore Controllers manuals

Offshore 3350-GTPO User manual

Offshore

Offshore 3350-GTPO User manual

Offshore 3350-HTPO User manual

Offshore

Offshore 3350-HTPO User manual

Popular Controllers manuals by other brands

White Knight CPC-1 manual

White Knight

White Knight CPC-1 manual

SONBEST SM3260S user manual

SONBEST

SONBEST SM3260S user manual

Datakom DKG-325 user manual

Datakom

Datakom DKG-325 user manual

Omron SYSMAC PLC Basic Technical guide

Omron

Omron SYSMAC PLC Basic Technical guide

Vimar Eikon Evo Well-contact Plus 21849 instructions

Vimar

Vimar Eikon Evo Well-contact Plus 21849 instructions

midique KNTRL9 user manual

midique

midique KNTRL9 user manual

Belimo LF24-SR US quick start guide

Belimo

Belimo LF24-SR US quick start guide

Kantech Door Controller Innovative and Powerful... installation manual

Kantech

Kantech Door Controller Innovative and Powerful... installation manual

FW Murphy Centurion C5 M-VIEW Touch Series Operation manual

FW Murphy

FW Murphy Centurion C5 M-VIEW Touch Series Operation manual

Siemens TIM 1531 IRC operating instructions

Siemens

Siemens TIM 1531 IRC operating instructions

Linak TECHLINE LA33 user manual

Linak

Linak TECHLINE LA33 user manual

Generac Power Systems PWRmanager owner's manual

Generac Power Systems

Generac Power Systems PWRmanager owner's manual

Leviosa Zone user manual

Leviosa

Leviosa Zone user manual

Carel SmartCella 3PH quick guide

Carel

Carel SmartCella 3PH quick guide

CLA-VAL CRL-60 Installation, operation & maintenance manual

CLA-VAL

CLA-VAL CRL-60 Installation, operation & maintenance manual

Hayward Aqua Plus® installation manual

Hayward

Hayward Aqua Plus® installation manual

DURAVIT DuraSystem WD5001 Series Mounting instructions

DURAVIT

DURAVIT DuraSystem WD5001 Series Mounting instructions

TREND IQ422 installation instructions

TREND

TREND IQ422 installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.