IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018 1
InstallationInstructions-Conguring
IQ422, IQ4NC/00, IQ4NC/12
Controllers
Important: Retain these instructions
These instructions shall be used by trained service
personnel only. If the equipment is used in a manner not
speciedbytheseinstructions,theprotectionprovidedbythe
equipmentmaybeimpaired. https://partners.trendcontrols.com
1 Isolate All Power (includinganyI/Osupplies)
1 BEFORE STARTING CONFIGURATION
CONTENTS
1 BeforeStartingConguration.......................................1
2 Conguration.................................................................1
3 Connect to IQ4xx........................................................10
4 Reset to Defaults.........................................................12
2 CONFIGURATION
Read&AgreetoEndUserLicenceAgreement
Additional Documentation Required
▪SETManual(TE200147)
▪IPToolManual(TE200638)
▪IQToolMonitorAppletManual(TE201298)
▪IQToolAddresserAppletManual(TE201299)
▪IQ4CongurationManual(TE201263)
Note: PDF copies are included with SET installation in the
following folder: C:\...\Trend Control Systems\Documentation
IQ422, IQ4NC/00, IQ4NC/12 Installation
Instructions-Mounting(TG201264) SETManual(TE200147)
Prepare Ethernet Network (ifusingEthernet)
Install DHCP Server
IftheIPaddresssettings(IPaddress,subnetmask,default
router,WINSandDNSservers’addresses)aretobesupplied
by a DHCP server, ensure one is installed on the Ethernet
segment to which the IQ422, IQ4NC/00, IQ4NC/12 is
connected.
Install WINS Server
If host names are being used for IP addressing across a
router,aWINSservermustbeinstalled.
Install DNS Server
Ifemailalarmsarebeingsent,andtheemailserveraddress
isidentiedbyinternetdomainname,aDNSservermustbe
installed.
IQ422, IQ4NC/00, IQ4NC/12 Installation
Instructions-Mounting(TG201264)
PSU
PSU
O
I
O
I
O
I
Install the IQ422, IQ4NC/00, IQ4NC/12 InstallSETonPC/Laptop
WARNING Connecting leads may be connected
topowersupplies.Isolatebeforetouching.
2 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018.
IQ422, IQ4NC/00, IQ4NC/12 InstallationInstructions-Conguring
6Select Terminator Switch Position (IQ4NCusingMS/TPnetworkonly)
3 PeelOffTopSerialLabel&Retain
5 Disconnect All I/O
4OpenRotatingCovers
2Open Panel / Enclosure
2 CONFIGURATION (continued)
Serial
Number
nq4eyecp412345
Q422B_V53440388 O/S
Q422B_V53440388
nq4eyecp412345
00:10:70:0D:1E:92
MAC Addr
IQ411-1010U5000
Part No:
LAN
422
MAC
Addr
IP
Addr
LAN
Location
S/No:
MAC Addr
00.10.70.00.UD.BB
S/No:
Q3B____X73010003
IP Addr
Location
TerminatoroutofcircuitTerminatorincircuit
IQ422, IQ4NC/00, IQ4NC/12 Installation
Instructions - Mounting (TG201264) for
detailsofterminatoruse.
Leave Power, Ethernet, Current loop LAN, USB, RS232,
andMS/TPconnected(whereappropriate).
WARNING Opening the panel may expose
dangerousvoltages.
IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018 3
InstallationInstructions-Conguring IQ422, IQ4NC/00, IQ4NC/12
8 CloseRotatingCovers
10 CheckPower&WatchdogIndicators
9 Switch On Power to IQ4xx
7 ConnectPC/Laptop
11 Check Ethernet Indicators (ifEthernetisconnected)
2 CONFIGURATION (continued)
O
I
Either:viaEthernetHub/Switch Or:usingdirectconnection
Note: To connect with SET a vCNC is required (see step 14).
SETcanconnectwhenonadifferentsubnet.
Note:Othermethodsofconnectionareavailablesee‘Connect
to IQ4xx’ on page 10.
Normal operation indication
Power
Watchdog
Fault indications
Power
Checkinputpowersupply
Watchdog
Devicefault.TryresettingtheIQ4xx
todefaultsettings(seepage12).
10s
Normal operation indication
OK
RX
or
Fault indications
OK
CheckEthernet
RJ45 StandardEthernetcable
(Cat5etwistedpair)
max100m(109yds)
StandardEthernetcable
(Cat5etwistedpair)
max100m(109yds)
RJ45
Hub/Switch
Router
Note: All LEDs illuminate for several seconds after switch on.
Watchdog
(red)
Power
(green)
OK
(green)
RX
(yellow)
4 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018.
IQ422, IQ4NC/00, IQ4NC/12 InstallationInstructions-Conguring
12 Connect to the IQ4xx
13 SetupIPAddressingDetails(ifusingEthernet)
2 CONFIGURATION (continued)
nq4eyecp412345
Q422B_V53440388 O/S
00:10:70:0D:1E:92
MAC Addr
IQ422-1010U5000
Part No:
LAN
IP
Addr
422
Then nd the IQ4NC, IQ422 by its MAC
addressasshownonseriallabel
SETManual(TE200147)
IPToolManual(TE200638)
UseIPTool–seestep12–tochooseeitherstatic(xed)or
dynamic(DHCP)addressing:
Dynamic(DHCP)Addressing(default)
Parameter Value
DeviceMode
Static(Fixed)Addressing
Parameter Value
DeviceMode
IPAddress
Enterrequiredvalueinformat:
xxx.xxx.xxx.xxx
SubnetMask
Default Router
WINSServer
Whensettodynamic(DHCP)addressingtheunitautomatical
obtains its IP addressing details (IP address, subnet mask,
default router, WINS server and DNS server) from the
network’s DHCP (Dynamic Host Conguration Protocol)
server.If no DHCPserverisfound, the unitdefaults to link/
localmodewhereitautonegotiatesitsIPaddresswithother
devicesonitsEthernetsegment,
Note: It is recommended that link/local only be used on a
single segment system.
When set to static (xed) addresssing the IP addressing
detailsmustbeconguredmanually.
Note: If email alarms are being sent, and the email server
address is identied by internet domain name, then a DNS
servermustalsobespeciedusingTextComms.
IPToolManual(TE200638)
UsingthePC/laptop(seestep7)runSET/IPTool
14 Set up Virtual CNCs (ifrequired)
Bydefault,IQ4NCshave4enabledvCNCs(4,5,6,and7)and
IQ422s have 3 disabled vCNCs. A vCNC must be enabled
if connection to a supervisor, tool or display is required. If
necessarydisable/congurethemtoavoidaddressconicts.
Use IP Tool– see step12– to set up theaddress and port
numberofeachvCNC.
Parameter Range
Address
0(disabled),1,4to9,11to119
PortNumber
1to32767
Default = 10000 plus the address
(e.g.address23setsportto10023)
OncethevCNCsetupinIPTooliscomplete,useIQSETto
congurethevCNCs.
▪UsingIQSETconnecttooneofthecontroller’svCNCs.
▪Youwillbeprompted to press the servicebutton on the
controller.OncepressedtheSecureSiteConguration
dialogueboxisdisplayed.
▪Congure the vCNCs as required, and enter the
credentialsfortheCNCUsermodule.
Note: conguring the vCNCs require physical access to
the controller ensure this is done before leaving site.
SETManual(TE200147)
IPToolManual(TE200638)
IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-20185
InstallationInstructions-Conguring IQ422, IQ4NC/00, IQ4NC/12
15 Set up IQ4NC Communication Mode (ifusingIQ4NC)
16 CheckTrendCurrentLoopNetworkIndicators(ifcurrentloopnetworkbeingused)
17 Check MS/TP Network Indicators (IfIQ4NCusingMS/TPnetwork)
▪ConnectaPCdirectlytotheIQ4usinganEthernetcable,
see‘ConnecttoIQ4’onpage10.
▪Usinga web browser,e.g. Internet Explorer,accessthe
controller’swebpagesandselectModules>Networks to
displaytheNCCongurationWizard.
▪Click required mode, and if necessary specify any
parameterse.g.LANnumber.
▪Click ;thecontrollerwillrestart.
EthernetInternetworktotoMS/TPLAN(default)
Parameter Notes
LANnumber
1,4to9,11to119
BACnetIP
Canbedisabled
CurrentLoopInternetworktoMS/TPLAN
Parameter Notes
LANnumber
1,4to9,11to119
BACnetIP
Canbedisabled
EthernetInternetworktoCurrentLoopLAN
Parameter Notes
LANnumber
1,4to9,11to119
BACnetIP
Canbedisabled
BACnet
MSTP
Can be enabled e.g. for
connectionofPEHAdevices
Ethernet Internetwork to Current loop
Internetwork
Note:Addressnolongerneedstobe>100.
Parameter Notes
LANnumber
1,4to9,11to119
BACnetIP
Canbedisabled
BACnet
MSTP
Can be enabled e.g. for
connectionofPEHAdevices.
Manualconguration
E.g. Ethernet Internetwork to Current loop
InternetworkplusMS/TPLan
2 CONFIGURATION (continued)
IQ4WebUserGuide(TC201256).
Note: The IQ4NC always has a LAN to connect to the
internetwork so cannot join another LAN on the internetwork.
Normal operation indication
TX
RX
Fault indications
TX
Checkconnectiontodownstreamdevice
RX
Checkconnectiontoupstreamdevice
Normal operation indication
RX
TX
Fault indications
RX
Signal not reaching RX on downstream
deviceonnetwork–checkdevice/wiring
TX
No TX signal from upstream device on
network–checkdevice/wiring
TX
(yellow)
RX
(yellow)
TX
(yellow)
RX
(yellow)
6 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018.
IQ422, IQ4NC/00, IQ4NC/12 InstallationInstructions-Conguring
19 SetupTrendAddressing
18 Set up Ethernet Access Across Routers (ifrequired)
20 WriteAddressDetailsonLabel
2 CONFIGURATION (continued)
IftheLANistobebuiltacrossarouter(s)detailsofdevices
(on each subnet) must be specied to enable cross-router
communications.
UseIPTool–seestep12–tospecifyIPsettingsforupto20
devicesintheRemoteTrendDeviceslist:
Parameter
Value
IPAddress
If using dynamic (DHCP) addressing:
Enterthehostnameoftheremotedevice.
Ifusingstatic(xed)addressing:
EntertheIPAddressoftheremotedevice,
intheformat:xxx.xxx.xxx.xxx
SubnetMask
Thesubnetmaskfortheremotedevice,in
theformat:xxx.xxx.xxx.xxx
IPToolManual(TE200638)
It is recommended that atleasttwodevicesfromeachsubnet
are specied. For increased reliability details of additional
devicesshouldbespecied.
IfstaticIPaddressingisbeingusedthelistshouldcontainthe
deviceswiththelowestIPaddresses.
ThesamelistmustbecopiedtootherEINCtypedeviceson
thenetwork.
Hint:TickingthecheckboxnexttotheRemoteTrendDevices
listretainsthelistinIPTool,allowingittobeeasilycopiedto
other devices:
nq4eyecp412345
Q422B_V53440388
O/S
00:10:70:0D:1E:92
MAC Addr
IQ422-1010U5000
Part No:
LAN
IP
Addr
422
IPToolManual(TE200638)
IQTool Addresser Applet Manual
(TE201299)
IfconnectingtoaLANonEthernet(orstandalonemode):
▪UseIPTool–seestep12–tosetthedeviceaddressand
LANnumber.
IQ4xx controllers are given a default device address and
LANnumberinthefactory.Thedeviceaddressissetinthe
range11to119onarollingbasiswiththeLANnumbersetto
20. Therefore it may be necessary to set the address/LAN
numberasrequired.
Parameter Value
LocalAddress
1,4to9,11to119
(mustbeuniqueonLAN)
LocalLAN
1,4to9,11to119
(must be the same for all devices
requiredtoformaLAN).
Note:ChangingtheLAN numberand/ordeviceaddress will
causethecontrollertoreboot.
IfconnectingtoaLANoncurrentloop(withonlyIQ4type
controllers):
▪Use SET’s IQTool Addresser Applet, and run the
DiscoveryWizard.
▪Select either ‘Automatic Discovery’ (recommended) or
‘Manual Discovery’. If ‘Automatic Discovery’ is chosen
youshouldthenselect‘DuplicateAddressResolution’.
Automatic Discovery: Thetoolwilldiscoverthedevices,
andattempttoresolveanyduplicateaddresses.
Manual Discovery: Either scan the bar code, or press
theServiceButtonforeachcontroller.
WARNING For /230 variants hazardous
voltagesexistwhentheunitispowered.Take
suitableprecautionsifpressingservicebutton.
Note: If the LAN is not as expected after discovery it could
bebecauseofinstallationrelatedreasons,e.g.wiringfaults,
powerfailure,etc.Checkthedevicesareoperatingcorrectly
and repeat discovery. If there are duplicate addresses add the
devicestothegridmanually,usingnetworkaddressandserial
number.IfnecessaryuseSET’sSystemViewtosettheLAN
number,andIQTooltosettheaddress.
If connecting to a LAN on current loop (with pre IQ4
controllers):
▪UseSET’sIQToolAddresserApplettomanuallyaddthe
IQ4tothegridusingtheserialnumberandaddress.
▪UseSET’sSystemViewtosettheLANnumber.
Deviceaddress(O/S)
LANnumber
FixedIPAddress
orHostname(ifDCHP)
IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-20187
InstallationInstructions-Conguring IQ422, IQ4NC/00, IQ4NC/12
21 SetCurrentLoopBaudRate(IQ4NCor../LANvariantsonly,ifcurrentloopnetworkbeingused)
22 SetupRS232/USBPortAddressing(ifrequired)
23 CheckLANOKIndicator(notIQ4NC)
2 CONFIGURATION (continued)
I QTo ol M on it o rA p p letM an ua l ( TE 2 012 9 8)
SETManual(TE200147)
IQ4CongurationManual(TE201263)
Parameter Range
Supervisorport
0,4to9,11to119
Default=0localaccessonly
USB
Engineeringport
0,4to9,11to119
Default=0temporarilytakesaddress125
UseSET’sIQToolMonitorApplettosettheSupervisorPortor
USBEngineeringPortasrequired.
I QTo ol M on it o rA p p letM an ua l ( TE 2 012 9 8)
SETManual(TE200147)
IQ4CongurationManual(TE201263)
If the IQ4xx is to provide connection to the network for
supervisors and tools it is necessary to setup the RS232
SupervisorPortorUSBEngineeringPortasrequired.
Normal operation indication
LANbuiltOK
AttemptingtobuildLAN
Note:ItisnormalbehaviourforLANOKindicatortoextinguish
forupto1minafterdetectingbaudrate,thenilluminate.
Fault indication (EthernetLAN)
UnabletocommunicateonLAN.
Note: Only applies if current loop is
disabledorisnottted.
Fault indication (CurrentLoopLAN)
every15s
Longerthan2minutesindicates
LAN/internetworkcannotbebuilt.
▪
Checkbaudsettingsofalldevicesoncurrentloop–see
step21,andcheckalldeviceconnections.
▪Ifstillashing,tloopback:
85
84 86 87
RX- RX+
TX- TX+
IfindicatorturnsOFF,deviceisfaulty.IfON,reconnect
networkandswitcho󰀨allotherdevicesonthenetwork.
▪
IfstillOFF,checknetworkcablingforshortcircuitswith
amultimeter(NOTMegger).
▪
IfONswitchonotherdevicesinturnuntilfaultydevice
found (i.e. LAN OK goes OFF), inspect that device to
determineandandcorrectthefault.
BydefaulttheIQ4xxwillautodetectthebaudrateinuseon
thecurrentloop.Ifalldevicesaresettoautodetectthebaud
rate chosen cannot be guaranteed,in which caseit may be
necessarytomanuallysetonedevicetoaknownrate.
Use SET’s IQTool Monitor Applet to disable autobaud and
specifythebaudrate.
Module Parameter Range
IQ Lan
network
Autobaud
0(disabled)or1(enabled)
Baud Rate
1k2,4k8,9k6,19k2,38k4
LANOK
(green)
8 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018.
IQ422, IQ4NC/00, IQ4NC/12 InstallationInstructions-Conguring
24 DownloadStrategy
25 Check IQ422 or IQ4NC on BACnet (If/BACorIQ4NCandBACnetprotocolcommunicationsrequired)
26 Test Inputs (NotIQ4NC/.../00)
2 CONFIGURATION (continued)
SETManual(TE200147)
IQ4CongurationManual(TE201263)
SETManual(TE200147)
O
I
Switcho󰀨 Re-connect inputsOpencovers Closecovers
O
I
Switchon
Note: An Ethernet connection is required to download both
strategyandbackdroples.Otherconnectiontypesonlyallow
downloadofstrategyles.
Note: strategy download is not recommended over current
loopwithbaudrate<9k6.
Note: SET will set up the controller’s date and time to that of
thePCduringdownload.However,theymaybesetupfroma
controllerconguredastimemaster.
ConguretheIQ4xxstrategyusingSET,andtestusingSET’s
simulationmode.
Use SET to download the strategy and backdrop le (if
required).
Use SET to check that the IQ4 BACnet functionality is
operatingbycheckingitappearscorrectlyintheSystemView
onitsBACnetnetwork.
S
Checkdigitalinputs Checkanalogueinputs
LED(yellow)
IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018
9
InstallationInstructions-Conguring IQ422, IQ4NC/00, IQ4NC/12
28 Test Outputs (NotIQ4NC/.../00)
29 Connect Supervisors/Tools/Display
Panels (ifrequired)
31 BackupStrategy
33 Close Panel / Enclosure
32 CloseRotatingCovers
30 CongureWebServer
2 CONFIGURATION (continued)
Connect PCs (e.g. for supervisors/tools) and displays as
describedin‘ConnecttoIQ4xx’onpage10.
Connectionofsupervisors,tools,displaypanelsetccanbe
madedirectlytocontrollerviatheRS232Localsupervisor
Port,USBLocalEngineeringPort,WallbusPort,orEthernet
port.ConnectioncanalsobemadeovertheTrendnetwork
overEthernetorthecurrentloop.
Use SET to upload the strategy and compare it with the
strategyheldbySET.
Note: An Ethernet connection is required to upload strategy
andbackdroples.Otherconnectiontypesonlyallowupload
ofstrategyles.
SETManual(TE200147)
O
I
Switcho󰀨 Re-connect outputsOpencovers Closecovers
O
I
Switchon Checkdigitaloutputs Checkanalogueoutputs
LED(yellow)
LOAD
LED(yellow)
LOAD
ConnectiontotheIQ4webservercanbemadeviaHTTP
and/or HTTPS protocol. Where HTTPS is used it will be
necessarytocongureSSLcerticates.
Ifwebaccessisnotrequireditisrecommendedthattheweb
serverisdisabledforsecurity.
IQ4CongurationManual(TE201263)
SETManual(TE200147)
10 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018.
IQ422, IQ4NC/00, IQ4NC/12 InstallationInstructions-Conguring
1 SwitchOffPowertoIQ4xx 2Open Top Cover (ifrequired)
3 Make Connection
O
I
PCviaLocalEngineeringPort(USB)
Connect Directly to Controller
PCviaEthernetPort
RJ45 StandardEthernetcable
(Cat5etwistedpair)
max100m(109yds)
Connection use
Notes
IPTool
ü
SET
ü
RequiresvCNC
WebBrowser
ü
Supervisor
ü
RequiresvCNC
PCviaLocalSupervisorPort(RS232)
CABLE/EJ101442
9wayfemale
Dtype
RJ11
PC
ConnectiontotheIQ4xxcanbemadedirectlyviatheRS232LocalSupervisorPort,USBLocalEngineeringPort,orEthernet
Port.Connectioncanalsobemadeoveranetwork(Ethernet).
Connection use
Notes
IPTool

SET
ü
WebBrowser

Supervisor

Connection use
Notes
IPTool

SET
ü
WebBrowser

Supervisor
ü
IQView8viaLocalSupervisorPort(RS232)
IQView8requiresitsownpowersupply.
Note: If local supervisor port address is ‘0’ (default)
communication is limited to the IQ4xx. If non-zero,
communicationispossibleovertheentirenetwork.
RJ11 RJ11
RD/SDU-IQ2COMMSCABLE3M
USBcable
MicroBUSBconnector
3 CONNECT TO IQ4XX
IQView8
IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018 11
InstallationInstructions-Conguring IQ422, IQ4NC/00, IQ4NC/12
3Make Connection (continued)
3 CONNECT TO IQ4XX (continued)
RJ11
RJ11
24Vdc
Supply
XW/R/IQ
Mustuseexternal24Vsupply
Connect Directly to Controller
RD-IQ, SDU-xcite, IQView4 via Local Supervisor Port
(RS232)
Connect via Ethernet Network
▪EnsuretheIQ4xxisconnectedtotheEthernetnetwork.
▪Connecttheotherdevice(e.g.networkdisplayorPC)to
same Ethernet network and ensure an IP connection is
availablebetweenitandtheIQ4xx.
▪TomakeaconnectionwithSET,asupervisorordisplay
ensureavCNCisavailableinaTrenddeviceonthesame
Ethernet Trend network and connect to the vCNC as
describedinthesupplieddocumentation.
Note:IfconnectingwithIPTool,thePCshouldbeonthe
same Ethernet segment as the IQ4xx.
▪To make a connection with a web browser run a web
browseronthePCandaccesstheIQ4xxIPaddressor
hostname.
XW/R/IQwirelesssensorreceiver via LocalSupervisorPort
(RS232)
PC Connection use
Notes
IPTool
ü
SET
ü
RequiresvCNC
WebBrowser
ü
Supervisor
ü
RequiresvCNC
Note: Set local supervisor port address to ‘0’ (default) as
communicationislimitedtotheIQ422,IQ4NC/00,IQ4NC/12.
IQView4 requires its own power
supply.
RJ11
RJ11
RD/SDU-
IQ2COMMSCABLE3M
RJ11
RJ11
IQView4
RD-IQ
SDU-xcite
StandardEthernetcable
(Cat5etwistedpair)
max100m(109yds)
Hub/Switch
Router
RJ45
RD-WMBviaWallbusPort
RD-WMB
TwistedPairCable
maximumlength60m(200ft)
IQView8
PC
12 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018.
IQ422, IQ4NC/00, IQ4NC/12 InstallationInstructions-Conguring
Please send any comments about this or any other Trend technical
publicationto[email protected]
© 2018 HoneywellProductsandSolutionsSARL,ConnectedBuildingDivision.Allrightsreserved.ManufacturedforandonbehalfoftheConnected
BuildingDivisionofHoneywellProductsandSolutionsSARL,Z.A.LaPièce,16,1180Rolle,SwitzerlandbyitsAuthorizedRepresentative,TrendControl
SystemsLimited.
TrendControlSystemsLimitedreservestherighttorevisethispublicationfromtimetotimeandmakechangestothecontenthereofwithoutobligation
tonotifyanypersonofsuchrevisionsorchanges.
TrendControlSystemsLimited
St.Mark’sCourt,NorthStreet,Horsham,WestSussex,RH121BW,UK.Tel:+44(0)1403211888,www.trendcontrols.com
2Reset Controller
1Isolate Power and Disconnect All I/O
3Re-congureController
The factory reset will erase the strategy and reboot the
controller into its original conguration. While the controller
iserasingthestrategy,theWatchdogandLANOKindicators
will ash alternately. During the reboot all indicators will be
ON. Once this process has completed the Watchdog and
LAN OKindicatorswill go OFF, leaving the Powerindicator
ON.This processmaytakeup to 10minutes depending on
controllertype.
Do not switch off the controller until the process has
completed.
4 RESETTODEFAULTS
Gotostep1onpage1.
Unplug the Ethernet cable and press and hold down the
service button. While continuing to hold down the button,
switchonthecontroller.Ensure the buttonremainspressed
for2to5safterpowerisswitchedon.
WARNING FOR /230 versions: Hazardous
voltages exist in this area when the unit is
powered.Thisoperationshouldonlybeperformed
aftertakingsuitableprecautions
Thestrategy,usermodules(passwords,PINsetc),alarmlogs,
andplotsarecleareddownandthefollowingparametersset
todefaults:
LANnumber
outstation address
IPaddressingmode
IP address
subnetmask
UDPport
identier
Router 1
remoteTrenddevices
VirtualvCNCs.
Timeanddateareleftattheircurrentsettings.
O
I
2to5s
22 23 24 25
RX+
28 29
WMB
RX- TX+ TX-
RX OK
45678910111213 14 15 16 17 18 123
230V
19
4 5 10
24V
0V 0V 0V 0V 0V 0V
986 7
123
Press
22 23 24 25
RX+
28 29
WMB
RX- TX+ TX-
RX OK
45678910111213 14 15 16 17 18 123
230V
19
4 5 10
24V
0V 0V 0V 0V 0V 0V
986 7
1 2 3
Release
Followsteps1,2,4,5and8(onpages1to3)to:
▪IsolatePower,
▪OpenPanel,
▪OpenRotatingCovers,
▪DisconnectAllI/O,
▪CloseRotatingCovers.

Other manuals for IQ422

1

This manual suits for next models

2

Other TREND Controllers manuals

TREND IQ422 User manual

TREND

TREND IQ422 User manual

TREND IQ41 Series User manual

TREND

TREND IQ41 Series User manual

TREND INC2 User manual

TREND

TREND INC2 User manual

TREND CNC2 User manual

TREND

TREND CNC2 User manual

TREND IQX12 User manual

TREND

TREND IQX12 User manual

TREND NBOX(B)/CNC2 User manual

TREND

TREND NBOX(B)/CNC2 User manual

TREND AD05-24 Operation manual

TREND

TREND AD05-24 Operation manual

TREND IQ23 Series User manual

TREND

TREND IQ23 Series User manual

TREND ADS10 Series User manual

TREND

TREND ADS10 Series User manual

TREND CNC2 User manual

TREND

TREND CNC2 User manual

TREND AL0620-24-K User manual

TREND

TREND AL0620-24-K User manual

TREND IQ3xcite User manual

TREND

TREND IQ3xcite User manual

TREND LonMark IQL13+ Series User manual

TREND

TREND LonMark IQL13+ Series User manual

TREND IQ3 series User manual

TREND

TREND IQ3 series User manual

TREND IQ251 User manual

TREND

TREND IQ251 User manual

TREND IQECO31/230 User manual

TREND

TREND IQECO31/230 User manual

TREND IQ4E User manual

TREND

TREND IQ4E User manual

TREND IQ41 Series User manual

TREND

TREND IQ41 Series User manual

Popular Controllers manuals by other brands

Omron G9SP Series manual

Omron

Omron G9SP Series manual

Lucent Technologies LINEAGE 2000 ECS-6 product manual

Lucent Technologies

Lucent Technologies LINEAGE 2000 ECS-6 product manual

imec PRO D579 instruction manual

imec

imec PRO D579 instruction manual

Zonet ZFN2601 Quick installation guide

Zonet

Zonet ZFN2601 Quick installation guide

Allen-Bradley Compact GuardLogix 5370 user manual

Allen-Bradley

Allen-Bradley Compact GuardLogix 5370 user manual

Emerson Copeland EV2 Series Application Engineering Bulletin

Emerson

Emerson Copeland EV2 Series Application Engineering Bulletin

Brooks SLA7950S Installation and operation manual

Brooks

Brooks SLA7950S Installation and operation manual

Panasonic MINAS A6 Series quick start guide

Panasonic

Panasonic MINAS A6 Series quick start guide

Honeywell VC6613AJ1000 Mounting instructions

Honeywell

Honeywell VC6613AJ1000 Mounting instructions

Victron energy MultiPlus-II 48/3000/35-32 230V GX manual

Victron energy

Victron energy MultiPlus-II 48/3000/35-32 230V GX manual

Hewalex G-422-P09 user manual

Hewalex

Hewalex G-422-P09 user manual

LOVATO ELECTRIC ATL10 manual

LOVATO ELECTRIC

LOVATO ELECTRIC ATL10 manual

GRAUPNER Compact Control 45 instruction manual

GRAUPNER

GRAUPNER Compact Control 45 instruction manual

Tornatech VP series Installation and maintenance manual

Tornatech

Tornatech VP series Installation and maintenance manual

Mitsubishi Electric MELSEC iQ-F FX5U user manual

Mitsubishi Electric

Mitsubishi Electric MELSEC iQ-F FX5U user manual

V2 TORQ-A manual

V2

V2 TORQ-A manual

Penn TC3X21 installation guide

Penn

Penn TC3X21 installation guide

Eaton DS7 Series manual

Eaton

Eaton DS7 Series manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.