Page : 3
INSTALLATION
PRECAUTIONS.- Theinstallationandthe
future use of this unit
must be done by suit-
able qualified person-
nel.TheunithasnotAC
(mains)switch,itwillbe
inoperationassoonas
power is connected.
The installation must
incorporateanexternalmainswitch.
The unit has a protection fuse incorporated on the AC socket, if it is
necessary to change or replace, use the time-lag fuse according to
IEC127/2andthevaluesindicatedbelow.
200 mA when the unit is operating at 230 Vac
400 mA when the unit is operating at 115 Vac.
Install also the necessary devices to protect the operator and the
process when using the unit to control a machine or process where
injurytopersonnelordamagetoequipmentorprocess,mayoccuras
a result of failure of the unit.
Seeparagraph6,WIRINGandparagraph8,CONFIGURATIONand
check that all jumpers AND switches are on the correct position.
SAFETY PRESCRIPTIONS.-
TheunithasbeendesignedandtestedunderEN-61010-1rulesand
isdeliveredingoodcondition.Thisopera-
tor's manual contains useful information
for
electricalconnections.Donotmakewiring
signal changes or connections when
power is applied to the unit. Make signal
connectionsbeforepowerisappliedand,if
reconnection is required, disconnect the
AC (mains) power before such wiring is
attempted.
Installtheunitin placeswithagoodventilationtoavoidtheexcessive
heating.Andfarfromelectricalnoisesourceormagneticfieldgenera-
torssuch aspower relays,electricalmotors, speedcontrols etc...
The unit cannot be installed in open places. Do not use until the
installationisfinished.
POWERSUPPLY.-
Thepowersupplymustbeconnectedtotheadequateterminals (see
theconnectioninstructions).Thecharacteristicsofthepowersupply
areshowedonthelabelontherearpart.Pleasemakesurethattheunit
is correctly connected to a power supply of the correct voltage and
frequency.
Donotuseotherpowersupplyotherwisepermanentdamagemaybe
causedto theunit.
Donotconnecttheunittopowersourcesheavilyloadedortocircuits
which power loads in cycle ON-OFF or to circuits which power
inductiveloads.
SIGNALWIRING.-
Certainconsiderationsmustbegivenwheninstallthesignalinputand
control wires. If the wires are longs can act like an antenna and
introducethe electricalnoise totheunit, therefore:
Do not install the signal input wires in the same conduit with power
lines, heaters, solenoids, SCR controls etc....and always far from
theseelements.
When shielded wires are used, connect the shield to the common
terminalandleaveunconnectedtheotherendoftheshieldanddonot
connecttothemachineground.
1.- IMPORTANT SAFETY CONSIDERATIONS
SAFETY CONSIDERATIONS
PRESCRIPTIONS.-
Before starting any operation of adjustment, replacement,
maintenanceorrepair,theunitmustbedisconnectedfromanykind
ofpowersupply.
Keeptheunitclean, toassure goodfunctioning and performance.
Use for it a clean and humid rag. Do not use for the frontal lens
abrasiveproducts,solvents,alcohol,etc...becauseitstransparence
couldbe damagedand thismaycause difficultyfor acorrectvision
ofthereading.
To prevent electrical or
fire hazard, do not ex-
pose the unit to exces-
sivemoisture.
Do not operate the unit
inthepresenceofflam-
mable gases or fumes,
suchasenvironment
constitutes a definite
safetyhazard.Theunitis designedtobe mountedina metalpanel.
Iftheunitshowssignsofdamage,orisnotabletoshowtheexpected
measures, or has been stored in a bad conditions or a protection
failurecanoccur,thendonotattempttooperateandkeeptheunitout
ofservice.
IN CASE OF FIRE
1.- Disconnect the unit from the power supply.
2.-Give thealarm accordingto thelocal rules.
3.-Switch off allthe airconditioning devices.
4.-Attackthe firewith carbonicsnow, donot usewater inany case.
WARNING : In closed areas do not use systems with
vaporizedliquids.
CONNECTIONS
All wiring connections are made using push-in cable connectors.
There is a separate connector block for power supply and input
signals.Pleasemakesurethateachconnectorblockisconnectedon
theadequateplace.
Thewirecrosssectionrecommendedforsignalinputsis1mm2and
for power supply 2.5 mm2.
PANEL MOUNTING
Verifythatthepanelcut-outiscorrectlyaccordingtothedimensions
indicated on page 20 with a minimum depth of 150 mm. (5.9").
Install the fixation pieces in the lateral guides of the unit by its rear
partandthenturnthescrew firmlyagainstthepanel,untiltheunitis
totallyholdon.
Seeparagraph11on page20.