OPTICLIMATE PRO3 Series User manual

OPTICLIMATE
PRO 3 Y PRO4 (INVERTER)
INSTALLATION AND USER GUIDE
EN
All manuals at:
www.theclimatefactory.com
Any other information:
info@theclimatefactory.com
OPTIMAL CLIMATE CONTROL

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
INSTALLATION
If the unit is placed in a narrow room or in the ridge of a gable roof, the fan outlet side can be installed at
the short side of the unit. This can be done simply by reversing the dark panels so that the fan panel is moved
around to the short side of the unit. Loosening the corner bracket will eliminate the need for disconnecting
cable connections.
Fan installation (front / side)
Installation
To guarantee proper air suction, leave at least 15cm of space between the wall and the backside of the unit,
where the carbon & dust filters and air inlet are located. At least 15cm of space should also be left between
the topside of the unit and the ceiling. Larger spaces are preferred. The unit must stand free from the wall to
avoid contact noises.

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
1 cm fall
The unit should be mounted in such a way that the side of the condensation drain is at least 1 cm lower than
the other side (slope) to ensure that the condensate drains properly. In practice, the 1 cm elevations at all
corners – except the corner of the condensate drains – are exactly right for a correct fall. Using a spirit level is
recommended.
To avoid contact noises, the OptiClimate comes standard with rubber shock absorbers that are suitable for
suspended installation. If the OptiClimate is going to be placed on a solid base, the rubber shock absorbers
supplied with the connection set need to be used.
Special insulating springs can also be supplied for areas that have to be extra quiet. Placing the insulating
springs on the supports will ensure that the unit has automatic fall to the condensation drain.
The rubber feet with which the OptiClimate is placed on the pallet are use to suspend the unit by means of
thread ends. A thread end, a large washer and a nut must be fitted. (not supplied)
Installation of rubbers Installation of insulating springs

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
First, the panel at the left side near the manometer should be removed to make the various electrical connec-
tions. A magnetic valve, water leakage sensor, automatic moisture meter, remote control and room
temperature sensor are supplied with the unit. Their cables can be led to the outside through the opening at
the bottom of the panel. The power cable for the power supply can be led through the black feed-through
rubber at the side of the unit.
Automatic moisture meter, Re-
mote Control, Solenoid Valve,
Temperature Safeguard, tem-
perature sensors in the area
Power cord
The plug of the solenoid valve should be connected using the black cable supplied with the unit, as shown in
the illustration below.
The other end of the cable should then be connected to the appropriate terminals - terminal N and terminal
7 - on the terminal strip (see page 6). The third connection of the solenoid valve can be used as earthing.
The connection set contains a loose, 5m long white wire: the water leakage sensor. This sensor is connected
to the eighth terminal on the printed circuit-board. The sensor cable should be led to the outside through the
opening in the panel and should be placed on the ground at the lowest point. The end of the sensor cable
can be split into several cores using a connector, so that more than one point is secured against leakage.
If the sensor has a black cap, this should be cut back and stripped 5mm and the cores should be stripped.
Connect the other side to the little white plug on the printed circuit-board as shown in the illustration. In case
of water leakage, the water supply will be stopped immediately by means of the electrical valve in the water
pipe.
ELECTRICAL CONNECTIONS
Electric solenoid valve
Water leakage sensor

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
ELECTRICAL CONNECTION
Sensor de temperatura
ambiente A101 Sensor de fuga
de agua A108
Puerto de
alarma
Alarm port
The printed circuit-board has an alarm port, which is activated (makes contact) by a malfunction (error). This
contact can be connected to a GSM detector. The contact can be set to NO (contact open) or NC (contact
closed) using the Settings menu This means that the contact will be opened or closed in case of detection.
See the manual of the GSM detector or alarm for this.
Automatic moisture meter with light cell
The automatic moisture meter with built-in light cell supplied with the unit is already connected. The cable
should be led through the opening in the panel. The automatic moisture meter should be hung in the room
and may NOT be covered. The light cell in the automatic moisture meter automatically switches the OptiCli-
mate from day to night mode.
Room temperature sensor
The compartment also has a room temperature sensor, which is already connected to the printed cir-
cuit-board. This sensor should be led to the outside through the opening in the panel and should be hung at
the level of the upper side of the vegetation. The sensor should be protected against heat radiation but may
not be put in the shade. A protective cover over the sensor is sufficient.
The remote control
The remote control contained in the compartment can be
hung in the room but can also be hung elsewhere. This
way the OptiClimate can also be controlled from outside
the room. The four-core cable is already connected and
should be led to the outside through the opening in the
panel.

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
ELECTRICAL CONNECTION
Power cables and circuit breakers
Six different OptiClimate models are available. For your safety and the safety of the OptiClimate, the fo-
llowing specifications should be observed when connecting the power supply: use the circuit breakers (MCB)
and cable thickness specified.
Models
2000 PRO3 & PRO4 1 phase D16 2,5mm2 de cable
2000 PRO3 & PRO4 3 phase D16 2,5mm2 de cable
3500 PRO3 & PRO4 1 phase D16 2,5mm2 de cable
3500 PRO3 & PRO4 3 phase D10 2,5mm2 de cable
6000 PRO3 & PRO4 1 phase D25 4,0mm2 de cable
6000 PRO3 & PRO4 3 phase D16 2,5mm2 de cable
10000 PRO3 & PRO4 1 phase D35 4,0mm2 de cable
10000 PRO3 & PRO4 3 phase D20 2,5mm2 de cable
15000 PRO3 & PRO4 1 phase D50 6,0mm2 de cable
15000 PRO3 & PRO4 3 phase D35 4,0mm2 de cable
15000 PRO3 & PRO4 3 phase D25 4,0mm2 de cable *
*The compressor of this unit is divided over 3 phases
The cables for the supply voltage should be led through the feed-through rubber at the side and connected to
the left-hand side of the terminal strip as described in the illustration. The earthing can be connected to the PE
terminal or to the screw on the metal housing at the bottom right of the terminal strip.
N 7 15L1 16L2 12L3 14
(COM) 18
P
EN
N 7 15L1 16L2 12L3 14
(COM)
18
P
EN
Connec-
ting to the
terminal
strips left
corner
Connecting to the terminal strips right corner
Connecting to the terminal strips left
corner Connecting to the terminal strips right corner
230V 3 Phase
blue yellow green red
2 loops with 230V 1 phase Solenoid valve
The automatic
moisture meter
Temperature safeguard
400V 3 Phase
blue yellow green red
No loops with 400V 3 phase Solenoid valve The automatic
moisture meter
Temperature safeguard
Earthing
Earthing

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
DN 7 15L1 16L2 12L3 14
(COM)
18
P
EN
r
Inverter models
Connecting to the terminal strips left
corner
INVERTER 1 PHASE 230VOLT
Connecting to the terminal strips right corner
When connecting the inverter models to 1 phase 230volt, there need to be bridges between L1, L2 and L3.
There should also be a bridge between N and D. With a new unit, the bridges are connected.
DN 7
15
L1
16
L2
12
L3
14
(COM)
18
P
EN
a
Connecting to the terminal strips left
corner Connecting to the terminal strips right corner
When connecting the inverter models to 3 phase 400volt, there may not be any bridges between L1, L2
and L3. There may also not be a bridge between N and D. With a new unit, the bridges are always con-
nected.
Note: Failure to observe the above description can cause irreparable damage to compressor/ inverter.
ELECTRICAL CONNECTION
Earthing
Earthing
blue
yellow green red blue
2 loops with 230V 1 phase Solenoid valve The automatic
moisture meter
Temperature safeguard
INVERTER 3 PHASE 400VOLT
No loops with 400V 3 phase
blue
yellow green red blue
Solenoid valve
The automatic
moisture meter
Temperature safeguard

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
WATER-SIDED CONNECTIONS
High temperature safeguard
Using this safeguard, the OptiClimate can switch off the heat sources (e.g. lamps) when the temperature in
a room becomes too high. The unit has a terminal that can be connected to the timer of a control panel, for
example.
The feed wire running to the switch in the timer should be interrupted for this purpose. Terminal 1, for exam-
ple, is for a Grasslin clock and terminal 4 for a LeGrand timer.
16
15
LeGrand nilssarG
16
15
16
15
The two ends should be connected to terminals 15 & 16 on the terminal strip in the electrical compartment of
the OptiClimate. The OptiClimate supplies the power for the timer.
The OptiClimate supplies the power for the timer. If the room temperature exceeds 35°C, the OptiClimate
will interrupt the circuit, switching off the heat sources ERROR15 is then displayed on the remote control.
Always refer to the timer manufacturer’s manual if a model other than the one
shown is used.
M
L N

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
WATER-SIDED CONNECTIONS
Supply and drain connections of the cooling water
The unit has a water inlet and outlet. The inlet should be installed at a draw-off point with a solenoid valve
installed between the draw-off point and the inlet (always check the flow direction arrow on the valve!). The
solenoid valve should be installed as close as possible to the draw-off point, as this is the water seal. When
a leak occurs, the solenoid valve closes automatically.
Make sure that the black magnetic coil of the solenoid valve is directed upwards (preferred) or to the side. If
it is directed downwards, condensate from the valve might enter the coil. Make sure that the solenoid valve
is installed at a fixed point that is always easily accessible to the user.
A filter should be placed in the water inlet. This filter prevents blockage in the unit. Disassembly of the filter
often releases dirt into the unit. As such, it may only be removed after contacting the Technical Service de-
partment.
It is recommended to insulate the water supply line in order to prevent condensation build-up. The upper
water connection is the water outlet. The water outlet can be connected directly to the drain (sewer). Alterna-
tively, the warm water can be used for heating purposes.
Note: Only use solid copper or LDPE pipes and affix these properly to the wall using clamps. Always avoid
putting the LDPE under tension. Make sure that the solenoid valve is affixed properly to the wall or another fixed
point. Never use a garden hose!
When all the LDPE connections are checked for leaks and the unit operates properly, all flare fittings should be
glued. You do this by unscrewing the coupling, applying some glue to the thread and re-tightening the blue flare
nut. If done properly, the flare fittings will never come loose as a result of vibration. If it is necessary to loosen the
flare fittings, then two water pump pliers will do the trick.
Copper pipes of 15 mm or LDPE pipes of 16 mm are sufficient for all units. If several units have to cool at
more than 15 kW, the main pipe should be 20 mm copper or 20 or 25 mm LDPE. If the supply pipe has
high pressure, a copper pipe of 15 mm will cool up to 30 kW.
Water drainage
Condensate drainage
Solenoid valve
16mm PE pipe
Pipe insulation
Solenoid valve in the supply pipe of the water

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
WATER-SIDED CONNECTIONS
All types of cooling water (tap, well, pond or swimming pool water) can be used for cooling. However,
tap water is preferred because you won’t need to rely on additional electric pumps. Well water contains
clay and iron particles that accumulate on the inner wall of the heat exchanger. The result is that sooner or
later the unit will cool less effectively or not at all. If you use well water, you can install a filter, but such a
solution requires maintenance. A normal 22mm tap water connection has sufficient capacity to continuously
cool three or four These are 3 or 4 OptiClimate 15000 units. We also have suitable solutions for larger
installations when there are problems with the water supply and discharge. In such cases, please contact the
Technical Service department.
Discharge of the condensation water
The unit will also dehumidify the air during cooling. The moisture extracted from the air comes into the condensation
drain. The condensation drain is connected to a sturdy garden hose or a pipeline that does not bend easily. The con-
densation water drips from the hose, which can be connected to the drain pipe. The condensate can also be used
as feed water. The cooling block has been adjusted to prevent metals or oxides from entering the condensate. This is
ideal when the only feed water available is hard water.
The drain pipe of the condensation water may not have loops and may not be put under the water level in a
drum. If the unit is installed at the same level or lower than the drain or sewer, a condensation lift pump can
collect the water. This small lift pump pumps the water through a hose of 9mm to a height of 4 metres into the
drain. Stronger pumps are also available.
The drain to the pump must not be under the water level and the pipe may not have loops as shown abo-
ve. It’s possible that too much air is sucked in through the condensation water pipe causing the condensate
water not to drain properly. Then there is too much resistance in the intake system. Dimension hoses of e.g.
a plenum box as large as possible and ensure that during operation all panels are mounted on the unit. A
special syphon can also be mounted. Ask your dealer.
Drain pump of the condensation water incorrect drain installation

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
PUTTING INTO OPERATION
=
=
T=
FN =
S=
R=
M=
On/Off =
Temp up / scroll
Temp down / scroll
Press and release to set the time / press and hold to set the timer
FN = Fan speed
Press and release to read Sensors / press and hold to bring up the Menu
Press and release to confirm / press and hold to delete error codes
Press and release to switch between day and night mode.
Press and hold to turn automatic light cell mode on/off.
Turn unit on/off or confirm menu option.
1) On/Off key
The unit is switched On or Off using the On/Off key. The LED will be green when the unit is On. The LED
will be red when the unit is Off. In case of malfunctioning, the LED will flash red and green. The On/Off key
is also used to confirm a menu selection.
2) Mode key M
Pressing the mode key will switch the mode from day mode (cooling) to night mode (heating/dehumidifying).
The display will show a lit snowflake in day mode and a sun with drops of water in night mode.
3) Fan speed key
This key is used for selecting the air speed of the fan. The sequence is as follows:
The speed changes whenever the Fn key is pressed. If you select the automatic fan mode in the Cool mode,
the unit will ventilate more or less depending on the need for cooling.
By selecting day or night with the mode key a different fan speed can be chosen for both day and night.
For the night we recommend the lowest fan speed for heating and dehumidifying. If a great deal must be
dehumidified during the night, the fan speed can be set to position 2 or 3.
Temperatures for the day and night can be set using the mode function. These can be changed
later, if required.
Fn
A
Remote Control
automatic low medium high

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
PUTTING INTO OPERATION
Inverter
The OptiClimate inverter models adjust the cooling capacity to the need. Non-Inverter models operate on
an on / off basis, while the inverter models run the compressor harder/ softer when more or respectively
less cooling capacity is required. This provides an even more stable climate and prevents the frequent trip-
ping of the unit in case of over capacity.
The inverter function operates on the basis of the fan speed. This means that the fan can be set to automatic
in the day position, using the remote control (FN). If the fans are set at a fixed rate, the inverter
function is switched off and the compressor also runs at a fixed rate. (resp. low / middle / high). For the
night position, we recommend that you always use the low setting.
4) Temperature setting
Users can set the temperature from 16°C to 34°C.Pressing the or key will show the set temperature SET
TEMP on the display. By pressing it once more, you can set the required temperature. The set temperature
will be saved and stored after 3 seconds. Switching between day and night temperatures is done using the
[M] mode key.
5) Time setting [T] key
Press the [T] key once to select the hours and then press the or key to change the hours. Press the [T] key
again, and the minutes will flash and then press the or key to change the minutes. Now press the [R] key
to confirm the hours and minutes that you entered.
Automatic Light Cell setting (Day /Night programme)
The automatic moisture meter in the pro3 series has a light cell, which switches to the day mode when it sees
the light is on and to the night mode when the light is off. Only the Day/Night temperatures have to be set,
the rest is done automatically.
If you want to set the unit manually, the automatic light cell can be switched off and the unit will operate ma-
nually. By pressing the [M] key for 3 seconds, the mode switches from light cell to manual. By pressing the
[M] key again for 3 seconds, the mode switches from manual to light cell. If the automatic light cell
is activated, the display shows an A.
7) Timer Setting (DAY/NIGHT programme)
As a general rule, we recommend using the automatic light cell mode. Only set the timer if you do not want
to work with the light cell!
This function can be used to set the DAY/NIGHT programme. The programme restarts every day regardless
of which day it is. If the timer is set, the display will show the clock icon next to the time:
Press the [T] key for 2 seconds. When “---”, ON becomes visible, you can change the timer setting. Pressing
the or key will allow you to set the hours of the ON time. Pressing the [T] key again will allow you to set
the minutes of the ON time. The ON time is the time that the unit will start to cool.
Pressing the [T] key again will allow you to set the OFF time. The OFF time is the time that the unit will start
to heat/ dehumidify. If the timer is not set yet, the display will show “--:--” or the time that was already set.
Note: It is important to note that when the Timer setting is programmed the automatic light cell mode is
deactivated. Therefore, program a Timer only if you want to use advanced options. The Timer mode is
active when a clock icon appears in the display.

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
PUTTING INTO OPERATION
Example:
The unit must cool between 8:00 AM and 8:00 PM.
The ON time should then be set to 8:00 AM
and the OFF time to 8:00 PM
AM = after midnight (from 0:00 to 12:00 hours)
PM = after noon (from 12:00 to 24:00 hours)
1:00 AM equals 01:00
2:00 AM equals 02:00
3:00 AM equals 03:00
4:00 AM equals 04:00
5:00 AM equals 05:00
6:00 AM equals 06:00
7:00 AM equals 07:00
8:00 AM equals 08:00
9:00 AM equals 09:00
10:00 AM equals 10:00
11:00 AM equals 11:00
12:00 PM equals 12:00
1:00 PM equals 13:00
2:00 PM equals 14:00
3:00 PM equals 15:00
4:00 PM equals 16:00
5:00 PM equals 17:00
6:00 PM equals 18:00
7:00 PM equals 19:00
8:00 PM equals 20:00
9:00 PM equals 21:00
10:00 PM equals 22:00
11:00 PM equals 23:00
12:00 AM equals 00:00

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
PUTTING INTO OPERATION

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
SETTINGS (SETUP)

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
SETTINGS (SETUP)

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
SETTINGS (SETUP)

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
SETTINGS (SETUP)

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
FAULT ANALYSIS AND ERROR MESSAGES

THE CLIMATE FACTORY/MANUALS/OPTICLIMATE (INVERTER)
www.theclimatefactory.com info@theclimatefactory.com
© The Climate Factory
FAULT ANALYSIS AND ERROR MESSAGES
Other manuals for PRO3 Series
4
This manual suits for next models
11
Table of contents
Other OPTICLIMATE Inverter manuals
Popular Inverter manuals by other brands

Mastervolt
Mastervolt WHISPER 25 ULTRA installation guide

Hoymiles
Hoymiles HM-800 user manual

Honeywell
Honeywell HW100SPI owner's manual

Perfect power systems
Perfect power systems EXT Series Installation and operation manual

SMA
SMA SUNNY TRIPOWER 60 installation guide

Invest Solar
Invest Solar SICM8H12 instruction manual