Orcon HRC-EcoMax Series User manual

Installation manual
HRC-EcoMax / HRC-MaxComfort
Balanced ventilation system with heat recovery
This manual is intended for installers of the HRC-EcoMax and HRC-MaxComfort
balanced ventilation system. The manual contains important information
about the installation and configuration of the ventilation unit with heat
recovery. The user manual can be found on the right side of the unit.
This manual concerns the following models:
HRC-300 EcoMax
HRC-300-MaxComfort
HRC-300 EcoMax
HRC-400-MaxComfort
HRC-500-EcoMax
HRC-500-MaxComfort

2

3
Index
1. Precautions and safety instructions 3
2. Product information 4
3. Product overview 6
4. Installation 10
5. Installation components 19
6. Adjustment 25
7. Maintenance and Service 28
8. Technical specifications 39
9. Installation report 47
10. Product card 48
11. Warranty 50
12. EC declaration 50
1. Precautions and safety instructions
• Only a professional installer may install, connect, commission and carry out
maintenance to the device unless otherwise specified in this document;
• The installation of the unit must be carried out in accordance with the general
and locally applicable construction, safety and installation regulations of the
municipality and electricity company;
• Make sure that the voltage is removed during work on the unit and cannot be
switched on accidentally. Bear in mind that the motor will continue to run for
approx. 20 seconds after switching off;
• The unit is only suitable for a 230V/50 Hz. connection;
• Modification of the unit or specifications stated in this document is not permitted;
• Touching the fans by hand must not be possible, therefore ventilation tubes of at
least 900 mm length must be connected.

4
2. Product information
2.1 General product description
The HRC is a balanced ventilation system with heat recovery. This means that an equal
amount of fresh filtered outside air is supplied to the living room and bedrooms while
polluted air is extracted from the kitchen, bathroom and toilet. The heat of the extract
air from inside is then transferred to the fresh filtered outside air. This results in
significant energy savings.
The Orcon HRC is equipped with an intelligent electronic control circuit that ensures
optimum operation and protection under all circumstances. The unit can be used as
a left or right model. The unit is supplied as standard as a left model with a grounded
plug and can be converted to a perilex model with a perilex power cord (article num-
ber: 22915405). For all models it is possible to use a radio remote control 15RF, CO2
Roomsensor 15RF or a CO2 Controlsensor 15RF; these are available separately.
2.2 Unit types
The different models are listed in the table below. Each model is suitable for both left
and right mounting.
HRC-300-
EcoMax
HRC-300-
MaxComfort
HRC-400-
EcoMax
HRC-400-
MaxComfort
HRC-500-
EcoMax
HRC-500-
MaxComfort
Item no. 22000080 22000085 22000090 22000095 22000100 22000105
Air flow rate
[m³/ h] at
max. 200 Pa
300 300 400 400 500 500
Tube
connection
[mm]
ø150 ø150 ø180 ø180 ø180 ø180
Preheater no yes no yes no yes
Filter class
(ISO16890)
2x coarse
65%
supply:
ePM1 70%
extract:
coarse 65%
2x coarse
65%
supply:
ePM1 70%
extract:
coarse 65%
2x coarse
65%
supply:
ePM1 70%
extract:
coarse 65%
index

5
2.3 Scope of delivery
Before installing the HRC, check that it has been delivered complete and undamaged.
It is complete if the following parts are included:
• HRC-EcoMax or HRC-MaxComfort with 230V earthed power cord
• Wall bracket
• Mounting set with 2x M8 bolts, 2x M8 washers and 2x plugs
• Installation manual
• User manual
• Connector piece 32mm / G1¼" for condensation drain
• 2x Orcon Filter (already in unit) (depending on unit model, see Chapter 2.2)
• Optional preheater (depending on unit model, see Chapter 2.2)
2.4 Optional accessories
Item Article number
HRC chassis 22700080
Preheater 29190550
EFF ø125 Extractor valve 23121002
EFF ø160 Extractor valve 23121003
TFF ø125 Supply valve 23121012
TFF ø160 Supply valve 23121013
Dry condensation drain set 22700065
Filter set HRC 2x coarse 65% 22700002
Filter set HRC coarse 65% & ePM1 70% 22700006
Perilex power cord 22915405
CV-3 Perilex socket - surface mounted 28000005
CV-3 Perilex power socket - built-in 28000000
Remote control 15RF 21800000
CO2 Roomsensor 15RF 21800040
CO2 Controlsensor 15RF 21800045
2.5 Scope of application
The unit is only suitable for residential buildings and not for industrial use, swimming
pools or saunas. The air flow rate from the unit must match the ventilation requirements
of the home.
index

6
3. Product overview
3.1 Parts
1. Front cover
2. Heat exchanger
3. Filter (2x)
4. Ventilator module (2x)
5. EPP cap (4x)
6. Wall bracket
7. Metal back frame
8. Preheater
(only with HRC-MaxComfort)
9a. Connector flange 150mm (4x)
(HRC-300-EcoMax/MaxComfort)
9b. Connector flange 180mm (4x)
(HRC-400-EcoMax/MaxComfort)
9c. Connector flange 180mm (6x)
(HRC-500-EcoMax/MaxComfort)
10. Main circuit board, RF antenna
11. Temperature sensor (2x)
12. Humidity sensor
13. Bypass module
14. Metal front frame
15. Filter cover left & right
index

7
3.2 Operation
Bypass
In the summer, or when heat recovery is not desirable, the air is not passed through,
but past the heat exchanger thanks to a bypass module. This makes it possible to
ventilate the home with fresh outside air in the summer situation, during the night,
so that the home is relatively cool again in the morning. The bypass opens when the
inside temperature exceeds the set comfort temperature of 23°C and the outside
temperature exceeds 15°C.
Frost protection
When the outside temperature in winter is around freezing, it is possible for ice to
form in the exchanger. Cold air is blown into your house as a result. To prevent this,
the HRC will heat the exchanger in time using the warm indoor air from your home.
The unit will temporarily create an imbalance to achieve this.
For the MaxComfort models, the built-in preheater switches on and warms up the cold
incoming outside air.
Constant volume
The unit is equipped with a constant volume control. This ensures that deviations
in the air flow rates between the supply and extract air, for example due to weather
conditions or when the filters become contaminated, are corrected automatically.
In this way the unit remains constantly balanced and you are assured of sufficient air
with maximum efficiency.
index

9
3.4 Duct indicator
When connecting the ducts it is important to take into consideration which
model is being used - left or right mounting. The connections are indicated on the top
of the unit with icons. The unit is supplied as a left model as standard.
You can change your apparatus into a right mounted model (see Section 4.3).
Air ducts on the home side Air ducts on the outside
Supply air from the unit to
the home
Supply air from outside to
the unit
Return air from the home to
the unit
Extractor air from the unit to
the outside
Left model
Home HomeOutside
Right model
index

10
4. Installation
4.1 Brief installation instructions
Step-by-step assembly:
1. Mount the wall bracket level on a wall with sufficient mass (200 kg/m2) with the
supplied bolts and plugs, or mount the unit on the optional base in the case of
floor mounting
2. Mount the Orcon extractor and supply valves in the various rooms
3. Configure the unit in the desired direction (see Chapter 4.3)
4. If desired, replace the earthed power cord with a perilex power cord
5. Set the required flow rate with the help of the DIP switches on the main circuit
board (see Chapter 6)
6. Hang the unit on the wall bracket, or position the unit with the base in the
desired location
7. Adjust the levelling feet so that the unit is hanging (wall mounting) or standing
(floor mounting) level
8. Install 2 silencers of at least 1 metre (ducts to and from interior spaces)
9. Mount the ventilation ducts and conduits with as little air resistance as possible
and free from leaks. Make sure no residual material from the pipes is able to reach
the device.
10. Mount the condensation extractor (preferably dry siphon) under the unit
11. Mount the desired remote controls, CV-3 switch (for perilex) and/or CO2 sensors
(see Chapter 5)
12. Switch on the voltage of the HRC-EcoMax or HRC-MaxComfort unit
13. Report separately supplied remote controls and/or CO2 sensors on
(see Chapter 5), the supplied remote control is already registered to the unit as
standard
4.2 Installation instructions
The HRC must be installed in compliance with:
• Quality requirements for residential ventilation systems, ISSO 61 quality requirements
for balanced ventilation in homes, ISSO 62
• The capacity calculation in compliance with the Netherlands Building Decree
• Requirements for ventilation of buildings - determination methods for new buildings
NEN 1087:2018
• The safety provisions for low-voltage installations, NEN 1010
• The requirements for connection to indoor drainage - design and implementation
guidelines, NTR 3216:2012. Any additional requirements from the local energy
companies
• The installation instructions for the HRC-EcoMax and/or HRC-MaxComfort
index

11
4.3 Changing the unit direction
The HRC is available in a left or right model. The HRC is by default supplied as a left
model. The ducts are therefore are connected to the home on the left side of the unit,
and the ducts on the right side of the unit go outside. If you wish to use the HRC as a
right model, it can be configured as follows:
1. Remove the plug from the socket
2. Place the device on a flat surface if the device is already suspended
3. Remove both filter covers
4. Remove the plastic front plate
5. Remove the metal front plate of the device by removing the 5 screws
(wrench size T25)
6. Take the power cord out of the cable clamp on the metal back plate
7. Remove the metal back plate of the device by removing the 5 screws.
8. Move the metal front plate to the other side of the device and fasten the 5 screws
9. Move the metal back plate to the back of the device and fasten the 5 screws
10. Remove the circuit board cover on the top. Keep an eye on the length of the display
cable when removing the circuit board cover. If necessary, temporarily separate it
from the connector on the circuit board
11. Move the earthing cable to the new back of the device. Move the strain relief
towards the recesses at the other wide of the circuit board as well
12. Reinstall the top cover such that the display is located at the front and fasten the 2
screws.
13. Return the earthing cable to the cable clamp on the metal back plate
14. Place the plastic front plate back to cover the metal front plate. Secure the front
plate by pressing on the four outer corners
15. Reinstall the filter covers.
The device is now suitable for installation in a right-handed setup.
index

12
4.4 Electric connectors
The HRC is equipped with a earthed
power cord as standard. Optionally,
you can replace the earthed power
cord with a perilex cord (article
number: 22915405).
The place where the wall socket
needs to be fitted is indicated in
the figure below. The electrical
installation must comply with
NEN1010 and the requirements
of the local energy company.
• Only place the plug in the
wall socket when the entire
installation is ready and no
building material is present
• The unit is not suitable for
3-phase current
• Supply voltage:
230 Volt ~50 Hz
Fitting the HRC with a perilex cord
Caution: ensure that the unit is always disconnected from the power supply
when changing the earthed power cord.
If you want to replace the earthed power cord with a perilex power cord, follow these steps:
1. Place the unit on a flat surface.
2. Remove the earthed power cord from the cable clamp on the metal rear frame
3. Remove the printed circuit board cover on the top of the unit by unscrewing the 2
screws using a Torx screwdriver (key size T25)
4. Remove the connector from connection X27
5. Remove the earthed power cord from the cable recess.
6. Using a flat screwdriver, attach the black wire of the perilex cord to position 2
(centre) of screw connector X9.
7. Using a flat screwdriver, attach the black wire of the perilex cord to position 3
(under) of screw connector X9.
Location of socket
outlet relative to
wall bracket
index

13
8. Place the white connector of the perilex cord on connection X27.
9. Feed the perilex cord through the cable recess. Place the strain relief in the
appropriate recess.
10. Screw the strain relief hand tight using a Torx screwdriver (key size T20)
11. Replace the top cover and re-tighten the 2 screws
12. Reinsert the earthed perilex cord into the cable clamp on the metal back frame
13. Place the plug in a perilex wall socket which is connected as shown in the
diagram below.
Speed control for perilex connection
A 230 Volt power supply (terminals L3 and N) must be
connected to the perilex wall socket. The speed is con-
trolled by means of a 3-position switch, which receives
power (L3) from the perilex socket (wire diameter 1.5
mm)2). A black (L2) and grey (L1) wire leads from the
switch back to the perilex wall socket. It is important
that terminal L3 is always supplied with voltage. For
the correct way to connect the cabling, see the wiring
diagram below. Optionally, an RF Remote Control, CO2
Controlsensor or a CO2 Roomsensor can be combined
with the CV-3 switch. If several switches or controls are
used in the home, the last selected ventilation position
always takes precedence.
Explanation of 3 ventilation settings
Setting 1 Low Absent setting For use during absence during a long
period
Setting 2 Medium Present setting For daily use with normal use within
the home
Position 3 High High setting For use during cooking, showering
or parties
index

14
Connections to printed circuit board
No. Function Pin function
X1 RF antenna connection
X9 Perilex input
L – 230V
2 – L2 (black, 230V) Medium setting
3 – L1 (grey, 230V) High setting
X10 Modbus Communication duct to
ventilators
1- RSA (2x White)
2- RSB (2x Brown)
3- GND (2x green)
X13 Supply ventilator power supply 1 – L2 – PE3 – N
X14 Extractor ventilator power supply 1 – L2 – PE3 – N
X15 Bypass stepper motor control
X18 Humidity sensor input
X22 Temperature sensor 1 input
(return air from inside)
1 – Earth
2 – Sensor
X23 Temperature sensor 2 input
(supply air from outside)
1 – Earth
2 – Sensor
X27 230V mains 1 – L(3)2 – PE3 – N
X33* Display connection Flat cable
X34* DIP switches extractor 8 dip switches
X35* DIP switches supply 8 dip switches
*on top board
index

15
4.5 Installing the unit
Transformer
Add-on PCB
Menu
button
Wall mounting
The unit can be hung on the supplied wall bracket. But only if the wall has a minimum
mass of 200 kg/m2 is available.
1. Attach the wall bracket to the wall using the bolts and plugs supplied. Caution:
mount the wall bracket using a spirit level before you connect the ducts!
Sufficient space must be left underneath the wall bracket for the condensation
extractor (see chapter 4.7).
2. Place the HRC in the left or right configuration over the wall bracket, by hooking
the hook on the back of the unit over the wall bracket.
3. Turn the levelling feet on the back of the unit so that it hangs level against the
wall. This ensures that the condensation extractor works optimally.
index

16
Floor mounting
If there is no wall that is suitable for wall mounting, the HRC can also be placed on
a concrete floor using the optional Orcon base (article number: 22700080) for floor
mounting.
1. Place the legs in the recesses on the bottom of the unit (Figure A). This works best
when the unit is on its side.
2. If necessary, use a spirit level to adjust the levelling feet so that the unit is level on
the floor (Figure B).
A. B.
4.6 Connecting ducts to the unit
Once the unit is fitted, the ducts can be mounted. The ducts (return) from and to
the home (supply) are on one side of the unit, and the ducts from and to the outside
are on the other side. In order to prevent condensation on the ducts from and to the
outside, these must always be insulated externally to ensure that they are damp-
proof. It is preferable to use preinsulated plastic ducts made of PE or PUR. Try to keep
these ducts as short as possible.
It is advisable to connect the ducts to and from the home to the unit using sound
dampers with a minimum length of 100 cm. When measuring the ducts, bear in mind
that not too much energy is lost when transporting the air through ducts that are
too narrow. It is preferable not to have the total resistance of both the supply system
and the discharge system exceed 100 Pascals. The supply duct system must be fitted
in such a way that NEN 1070, table 4 is complied with in the nominal setting. Think
of crosstalk and installation noise, also with underfloor ducts. Ensure that the supply
ducts are insulated if necessary, e.g. if they are installed outside the insulated skin.
Attention: make sure no residual material is able to reach the device while
installing the pipes to prevent it from damaging the device.
index

17
1. Air outlet
2. Air supply
3. Unit fitted with correct
filters
4. HRC (install using spirit level)
5. Connect condensation
drain according to
installation instructions
6. Connect the supply duct
using acoustic insulation
7. Connect the extractor duct
using acoustic insulation
Feed exhaust and supply duct through the roof boarding in such a way that no
condensation water is created in the roof boarding and everything is airtight; also
install the exhaust duct between the HRC and the roof outlet so that surface
condensation is prevented. Select the extractor location for the mechanical ventilation
air and sewer ventilation so that no hindrance occurs with regard to the supply.
Select the location of the supply valves so that pollution and draft are prevented.
A Extractor valve ø125 plastic (MKL) or metal (EFF-125/ EFF-150/160)
B Supply valve ø125 (TFF-125) or ø160 (TFF-160)
a 2 cm slit under the door. Install sufficient overflow openings.
1
3
4
5
6
7
2
index

18
4.7 Condensation extractor
The HRC must always be fitted with a condensation extractor underneath the unit.
It is preferable to use a dry siphon (article number: 22700065), which can be ordered
separately. Because this requires less space underneath the unit, there is less chance
of air leaks and it does not dry out on hot days, which prevents odour issues. When
connecting the siphon, always use PFTE tape to prevent leaks.
Standard siphon
The unit is supplied with a standard 32 mm connector with threaded end. This can be
connected to the bottom of the unit on internal thread (G1 ¼"). The condensation water
must be extracted through the inner sewer system free of frost and on a slight incline.
A water trap of at least 80 mm must be installed to prevent an air leak and sewer
odour from spreading into the ventilation system. A siphon with a diameter of 40 mm
must be placed under the water trap. Preferably use a threaded connector and rubber
gasket for easy cleaning of the siphon. When connecting the siphon, always use PFTE
tape to prevent leaks.
Standard siphon Dry siphon
index

19
5. Installation components
5.1 Remote control 15RF (optional)
Mounting
The remote control can be opened using the push button at the bottom (image
below). The wall frame can then be mounted with the 2 screws and plugs supplied
or glued. Caution: the "UP" mark on the wall frame must always be at the top. Keep
enough space at the bottom so that the push button can be easily reached from
below. It is recommended to place the remote control in an easily accessible place
in the living room, kitchen or toilet. Never place the remote control near large metal
objects. Large metal objects can disrupt the radio-controlled signal.
Battery position
Push button open control
Registration
The remote control must be registered. In total, up to 20 RF components can be
connected to the unit.
• On 1 unit
Unplug the unit from the wall outlet for 10 seconds. Then put the plug back
in the socket. The unit will remain in set-up mode for 3 minutes and you can
register the remote control. Press the keys <1> and <auto> simultaneously until
the LED on the remote control flashes red, green and red alternately. The LED
on the remote control will now flash green 10 times, the remote control is ready
for use. Registering an extra remote control is done in the same way.
• On multiple units
To register 1 remote control on more than one unit, the above registration
procedure is repeated, just press the key <2> and <auto> until the LED on the
remote control flashes alternately red, green and red.
index

20
• Resetting remote control 15RF
To replace a remote control, all components on the unit must be de-registered.
All components must then be registered again. A remote control can be reset
(and thus de-registered) by simultaneously pressing the ‹absent› and ‹timer› keys
for 3 seconds. The remote control indicates that the reset is complete when it
flashes orange twice.
Remote control
The remote control for the unit has 6 buttons. The functions of these buttons are
explained in the table below.
• Absent setting
In the absent position, the unit runs in an extra energy-efficient low setting and
does not respond to demand from the sensors.
• Timer setting
In the timer mode, the unit runs the desired time in the high position, after the
time has elapsed, the unit returns to the last selected position. The timer can be
cancelled by selecting another setting.
• Automatic mode
In car mode, the unit runs based on the moisture content in the home or based
on the optional CO2 sensors. If there is no ventilation demand, the unit runs as
standard in position 1. When there is a ventilation demand from the humidity
sensor or the optional CO2, the unit will modulate the ventilation to the medium
setting (setting 2).
Explanation of remote control buttons
Button Operation Function
1x short Absent setting (same as low setting)
1 1x short Setting 1 (low setting)
2 1x short Setting 2 (medium setting)
3 1x short Setting 1 (low setting)
1x short Setting 3 (timer mode) temporary 15 minutes
2x short Setting 3 (timer mode) temporary 30 minutes
3x short Setting 3 (timer mode) temporarily 60 minutes
auto 1x short Automatic mode
index
Other manuals for HRC-EcoMax Series
1
This manual suits for next models
7
Table of contents
Other Orcon Fan manuals
Popular Fan manuals by other brands

Brandson
Brandson 303052 user manual

Monte Carlo Fan Company
Monte Carlo Fan Company 14PRR62XXD Series Owner's guide and installation manual

Xpelair
Xpelair XIM100+ Installation and maintenance instructions

DELTA BREEZ
DELTA BREEZ SIG80-110ELED Package Contents

Suntec Wellness
Suntec Wellness Klimatronic CoolBreeze 9.500 Tri-Vario TV+ manual

emerio
emerio FN-110139.1 instruction manual