Orcon HRC-425 EcoSmart User guide

Installer's manual
HRC-EcoSmart / HRC-SmartComfort
Balanced ventilation with heat recovery &
solar control
This manual is intended for installers of the HRC-EcoSmart and HRC-
SmartComfort balanced ventilation system. The manual contains important
information about the installation and configuration of the ventilation unit.
These instructions belong to the versions:
HRC-425-EcoSmart
HRC-425- SmartComfort
HRC-570-EcoSmart
HRC-570-SmartComfort

2

index
4
1. Precautions and safety instructions
•Only a professional installer may install, connect, commission and service the
unit unless otherwise specified in this document;
• The installation of the device must be carried out in accordance with the
general and locally applicable building, safety and installation regulations of
the municipality and the electricity supply company;
•When carrying out work on the unit, ensure that the power is off and cannot be
switched on accidentally. Bear in mind that the motor continues to run for
approx. 20 seconds after being switched off;
• The unit must be connected to an earthed and fused wall socket;
• Modification of the device other than as described in this documentation is not
permitted;
• It must not be possible to touch the fans by hand, which is why ductwork of at
least 900 mm in length must be connected.
• The unit is not suitable for use in an environment where the following
conditions are present or may occur:
• Corrosive or flammable gases, liquids or vapours.
• Overwhelmingly greasy atmosphere.
• Room air temperature above 40°C or below 5°C.
• Relative humidity higher than 90%.
• The appliance is not suitable for connection to a cooker hood or tumble
drier
• The device is only suitable for indoor use.
• The device is not suitable for industrial use, such as swimming pools,
saunas or workshops.
•Check that the device is complete and undamaged when it is removed from
the packaging.
Indicates a risk of personal injury and/or material damage to the
product, the system or the environment.
Risk of electric shock.

index
5
2. Product Information
2.1.General Product Description
The HRC-EcoSmart / SmartComfort is a balance fan with heat recovery and zone
control. This means that the same amount of fresh, filtered outside air is supplied
to the living rooms and bedrooms as is removed from the kitchen, bathroom and
toilet. In this process, only the heat of the extract air is transferred to the incoming
outside air by means of a heat exchanger. With the zone control, the living and
sleeping areas are ventilated according to requirements, which are determined by
the CO2 sensor in the respective area.
2.2.Device types
The table below lists the different versions. Each version is suitable for both left and
right-hand mounting.
1 In accordance with Article 3.29 Paragraph 5 of the 2012 Building Decree
2 Optional perilex mains cable available, see chapter 7.2 Service parts
HRC-425
EcoSmart
(300)
HRC-425
SmartComfor
t (300)
HRC-570
EcoSmart
(400)
HRC-570
SmartComfor
t (400)
Article no.
22001090
22001095
22001100
2200110
5
Maximum
flow rate at
200 Pa [m³/h]
300
300
400
400
Supply air
volume
according to
70% rule1 [m3/h]
425
425
570
570
Power cord2:
Earthing
Earthing
Earthing
Earthing
Channel
connection
[mm]
4 x
ø160
2 x
ø160
Zone
valve
4 x
ø160
2 x
ø160
Zone
valve
4 x
ø180
2 x
ø160
Zone
valve
4 x
ø180
2 x
ø160
Zone
valve
Pre-heater
no
yes
no
yes
Filter class
(ISO16890)
2x coarse
65%
Supply:
ePM1 70%
drain:
coarse 65%
2x coarse
65%
Supply:
ePM1 70%
drain:
coarse 65%

index
7
2.3.Scope of delivery
Before installing the HRC, check that it has been delivered complete and
undamaged. It is complete if the following parts have been supplied:
• HRC-EcoSmart or HRC-SmartComfort with shock-proof power cord
• Wall bracket
• Suspension set with 2x M8 bolts, 2x M8 washers and 2x dowels
• Installation guide
• User Manual
• Coupling 32mm / G1¼" for condensate drain
•2x Orcon Filter (already in unit) (depending on unit version, see chapter 2.2)
•Optional pre-heater (depending on unit version, see chapter 2.2)
• 2x Zone valve
• Adapter 5V for zone control
•4x Connection flanges 160 or 180 mm (depending on unit version, see chapter 2.2)
• 2x Connection flange Zone valve
• EcoDesign stickers.

index
8
2.4.Optional accessories
HRC chassis
22700080
EFF ø125 Exhaust valve
23121002
EFF ø160 Exhaust valve
23121003
TFF ø125 Supply valve
23121012
TFF ø160 Supply valve
23121013
MKL-T ø125 Supply valve plastic
23120125
MKL-T ø160 Supply valve plastic
23120160
Dry condensation drain set
22700065
Filter set HRC 2x coarse 65%
22700009
Filter set HRC coarse 65% & ePM1 70%
22700006
Perilex cable
29190405
CV-3 Perilex switch - construction
28000005
CV-3 Perilex switch - flush-mounted
28000000
Remote control 15RF
21800000
CO2 room sensor 15RF
21800040
CO2 control sensor 15RF
21800045
CO2 sensor 15RF
21800050
HRC Display Built-in15RF
21800060
Articl
Article

index
9
3. Product overview
3.1.Parts
1. Plastic front cover
2. Heat exchanger
3. Filter (2x)
4. Fan module (2x)
5. EPP cap (4x)
6. Wall bracket
7. Metal backing plate
8. Pre-heater
(only with HRC- SmartComfort)
9a. Connection flange 160mm (4x)
(HRC 425-EcoSmart/MaxComfort)
9b. Connection flange 180mm (4x)
(HRC 570-EcoSmart/
SmartComfort)
10. Main board, RF antenna
11. Temperature sensor (2x)
12. Humidity sensor
13. Bypass module
14. Metal front plate
15. Filter handle left & right
16. Zone valve 1 & 2
(incl. Printed Circuit Board,
Motors, Adapter + Cable
Connection)
17. Connection flange Zone valve (2x)

index
10
3.2.Appliance operation
Zone control
The HRC-EcoSmart and HRC-SmartComfort are equipped with two zone valves.
With these, the supply air can be divided over two different zones. The CO2 sensors,
which are placed in the two zones, determine where ventilation is required. By
applying zone control, ventilation is minimised in rooms where it is not necessary
and maximised where it is. This results in a considerable reduction in energy
consumption and noise, creating a pleasant indoor climate.
Bypass
In summer situations, or when heat recovery is not desired, the air is not led
through, but past the heat exchanger thanks to a bypass module. This makes it
possible to ventilate the house with fresh outside air during the night in summer, so
that the house is relatively cool again in the morning. The bypass opens when the
indoor temperature exceeds the comfort temperature of 23°C and the outdoor
temperature is higher than 15°C.
Frost protection
When the outside temperature is around freezing point in winter, it is possible that
ice will form in the exchanger. To prevent this, the HRC will heat the exchanger in
time using the warm air from the house. To do this, the unit will temporarily create
an imbalance between the supply and return air fans.
In the SmartComfort versions, the built-in pre-heater will kick in and temporarily warm
up the cold incoming outside air to prevent freezing.
Constant volume
The fans are equipped with a constant volume control. This ensures that,
regardless of the resistance in the system, the fans always ventilate the set air
volume. In this way, the supply and return flows are always balanced and the user is
assured of sufficient air and the heat exchanger operates at maximum efficiency.

index
12
4. Installation
4.1.Requirements for installation
The installation of the HRC must be carried out in accordance with:
• Quality requirements for domestic ventilation systems, ISSO 61
• Quality requirements for balanced ventilation in dwellings, ISSO 62
•The capacity calculation according to the Building Act
•Requirements for ventilation of buildings - Determination methods for new
buildings NEN 1087:2018
• The safety regulations for low voltage installations, NEN 1010
• The regulations for connection to indoor sewers - guidelines for design and
implementation, NTR 3216:2012. Any additional regulations from the local energy
supply companies
• Installation instructions for the HRC-EcoSmart/SmartComfort

index
13
4.2.Brief installation instructions
Step 1 Mount the wall bracket level to a wall of sufficient mass
(200kg/m2), or mount the unit on the optional stand in
case of floor mounting.
see 4.6
Step 2 Install the Orcon exhaust and supply valves in the
various rooms.
see 4.8
Step 3 Install the ventilation ducts and lead-throughs with as little
air resistance as possible and free from leaks.
see 4.3
Step 4 Determine where the channels on the device should end
up, configure the device in the desired orientation.
see 4.4
Step 5 Replace the randaarde cable with a perilex cable if required.
Place the zone valves directly on the HRC supply openings
or in the supply duct to the house.
see 4.5
Step 6 Set the required flow rate using the dipswitches on the main
board.
see 6.1
Step 7 Hang the unit on the wall bracket, or place the unit with the
stand in the desired location.
see 4.6
Step 8 Install silencers of at least 1 metre (ducts to and
from the indoor areas)
see 4.3
see 4.7

index
14
Step 9 Install the condensate drain (preferably dry siphon)
under the appliance
see 4.9
Step 10 Place the desired controls in the house.
At least one CO2 sensor must be installed per zone.
see 4.10
Step 11 Connect the zone valves het toestel. see 5.1
Step 12 Connect the CO2 sensors to the zone valves of the
respective zone where the sensor is located.
see 5.2
Step 13 Determine how the total capacity is distributed over the
zones and enter this on the zone valve 1.
see 6.2

index
15
Step 14 Adjust the supply valves for each zone in accordance with
the ventilation calculation made.
see 6.3
Step 15 Adjust the drain valves over the entire house by
opening both zone valves
see 6.4
4.3.Installing channels
1. Exhaust to the outside.
2.Supply from outside.
3.Appliance fitted with appropriate filters.
4. HRC (levelling).
5. Connect condensate drain as per installation instructions.
6.Acoustically insulated connection of the Zone 1 supply duct to the flat.
7.Acoustically insulated connection of the Zone 2 supply duct to the flat.
8. Acoustically insulated connection of the flue from the house.

index
17
Please observe the following points when installing the channels:
1. To prevent condensation on the ducts from and to the outside, these should
always be insulated externally vapour-tight to the appliance. Preferably
pre-insulated plastic channels made of PE or PUR are used, try to keep these
channels as short as possible.
2. It is recommended to install silencers with a minimum length of 100 cm
on the supply and return channels to the house.
3. Attach the duct system to the wall with metal brackets, with a maximum
distance of 2 m between the brackets.
4. Ensure that the resistance in the supply and extract air ducts is as low as
possible. The resistance of the entire installation should preferably not
exceed 100 Pa.
5. Ensure that the duct diameter corresponds to the desired flow rate in the ducts,
so that the air velocity in the duct does not exceed 3 m/s See table in section
4.3.
6. The supply air duct system is designed so that NEN 1070, table 4, is
complied with in the nominal position. Consider crosstalk and installation
noise, also in the case of intake ducts. This can be prevented by installing
a sound absorber.
7. The exhaust and supply ducts must be led through the roof boarding in
such a way that no condensation is formed in the roof boarding and the
whole is airtight.
8. The air intake or air outlet ducts should be laid with a slight incline to the
outside via the façade and should be wind and watertight so that no water can
penetrate from outside.
9. The intake of outside air should preferably take place on the shadow side of the
house.
10. The position of the outlet and supply of the mechanical ventilation air
and sewerage venting in relation to the supply is selected in such a way
that no nuisance occurs.
Desired flow rate (m3/h)
Minimum recommended duct diameter (mm)
0 - 30
>100
30 - 150
> 125
150 - 350
>150
350 - 450
> 180
400 - 500
2x 180 (use side and top connection)
Selecting air ducts

index
18
4.4.Change device orientation
When connecting the ducts, it is important to take into account where the ducts
should be placed. The connections are indicated on top of the device by icons. The
appliance is delivered as a left-hand model, which means that the ducts to and from
the house are placed on the left-hand side.
Caution: When inserting the ducts, make sure that no residual material
enters the unit, as this may damage it.
Supply air from the unit to the
dwelling
Supply air from outside to the
unit
Return air from the house to the
unit
Exhaust air from the unit to the
outside
Left-hand
Right-hand
Wall
Propert
Outside
Propert
Air ducts on the flat side
Air ducts on the outside

index
19
Change the appliance to the right-hand version:
Step 1 Remove the plug from the socket.
Step 2 Place the unit on a flat surface, if the unit is already hung.
Step 3 Remove both filter handles. Step 4
Remove the plastic front plate.
Step 5 Remove the metal front plate of the unit by loosening the 5 screws. (bit
size T25).
Step 6 Remove the power cord from the cable clamp on the metal back plate.
Step 7 Remove the metal back plate of the unit by removing the 5 screws
(T25).
Step 8 Move the metal front plate to the other side of the unit and retighten
the 5 screws.
Step 9 Move the metal back plate to the back of the unit and retighten the 5
screws.
Step 10 Remove the top circuit board cover by removing the 2 screws. (T25) Note
the length of the display cable when removing the circuit board cover, if
necessary remove it temporarily from the connector on the circuit board.
Step 11 Move the grounding cable to the new back of the device. Also move the
strain relief to the recess on the other side of the PCB.
Step 12 Replace the top cover so that the display is at the front and tighten the
2 screws.
Step 13 Replace the earthed cable in the cable clamp on the metal back plate.
Make sure that the cable does not come under the suspension bracket.
Step 14 Replace the plastic front plate in front of the metal front plate. Then press
the front plate firmly onto the four outer corners.
Step 15 Replace the filter handles.

index
20
!"#$%&!
4.5. Electrical connections HRC
The HRC is equipped as standard with a mains lead with shock-proof plug.
Optionally, you can replace the rim-earth cord by a perilex cord (article number:
22915405). The zone control is provided with its own 5 volt power supply and must
be connected to a wall socket by means of the supplied adapter. Place a double wall
socket for the HRC and the zone control within 1 meter around the device.
The electrical installation must comply with NEN1010 and the requirements of the
local energy company.
• Do not insert the plug into the wall socket until the entire installation is complete
and there is no construction dust.
• The unit is not suitable for three-phase current
• Power supply HRC-EcoSmart/SmartComfort: 230 Volt ~50/60 Hz
• Connection voltage Zone valve: 5VDC, 1A via supplied adapter (connection
voltage 230V 50/60 Hz)
Max. 1m
This manual suits for next models
7
Table of contents
Other Orcon Fan manuals
Popular Fan manuals by other brands

Minka-Aire
Minka-Aire Alva F852L Instruction manual warranty certificate

Chore-Time
Chore-Time TURBO Installation & operator's instruction manual

Vents
Vents VK Series user manual

ZyXEL Communications
ZyXEL Communications FAN500 installation guide

Bestron
Bestron SUMMER BREEZE DDF27Z instruction manual

Vortice
Vortice ARIETT HABITAT 15/30 LL Instruction booklet