Orion Control Systems OE217-00 Quick start guide

Digital Room Sensor
Technical Guide
www.orioncontrols.com

TABLE OF CONTENTS
OVERVIEW....................................................................................................................................... 3
BASIC OPERATION.......................................................................................................................... 4
Sensor Operation ..................................................................................................................................................... 4
LED Operation ......................................................................................................................................................... 4
MOUNTING AND WIRING ................................................................................................................ 5
Environmental Requirements ................................................................................................................................... 5
Indoor & Outdoor Reading Range ...................................................................................................................... 5
Important Wiring Considerations .............................................................................................................................. 5
Mounting .................................................................................................................................................................. 5
SENSOR OPERATION ...................................................................................................................... 6
Main Sensor Display Screens....................................................................................................6
Temperature and Humidity Status Screen .......................................................................................................... 6
Outside Air Temperature Humidity Status Screen............................................................................................... 6
Unit Information Screen ...................................................................................................................................... 6
Setpoint Adjust Screen ....................................................................................................................................... 6
TROUBLESHOOTING....................................................................................................................... 7
Temperature Sensor Testing for OE217-00 ............................................................................................................. 7
APPENDIX ....................................................................................................................................... 8
Sensor Confi guration and Test Screens .................................................................................................................. 8
Sensor Confi guration & Test Screen ................................................................................................................... 8
Pixel Test Screen ................................................................................................................................................ 8
Sensor Info & LED Test Screen .......................................................................................................................... 8
LCD Backlight Test Screens ............................................................................................................................... 9
Thermistor Averaging Screen ............................................................................................................................. 9
Display Options - Temperature/Setpoint ............................................................................................................. 9
Connecting to the HVAC Unit Controller ................................................................................................................ 10
Connecting a Remote Sensor ................................................................................................................................ 11
Mounting Plate Dimensions ................................................................................................................................... 14
AAON Controls
8500 NW River Park Drive · Parkville, MO 64152
Toll Free Phone: 866-918-1100
PH: (816) 505-1100 · FAX: (816) 505-1101 ·
E-mail: mail@wattmaster.com
Visit our web site at www.orioncontrols.com
AAON® is a registered trademark of AAON, Inc., Tulsa, OK.
AAON assumes no responsibility for errors or omissions.
This document is subject to change without notice.
Form: OR-DRS-TGD-01M
Copyright August 2018 AAON, Inc.
www.orioncontrols.com
PART NUMBER CROSS REFERENCE TABLE
PART DESCRIPTION ORION
Digital Room Sensor Temp Only OE217-00
Digital Room Sensor Temp & Humidity OE217-01
Mounting Plate BK000081
Space CO2 Sensor OE256-01
Duct Mounted CO2 Sensor OE256-02
Return Air Temperature Sensor OE231
VCM-X E-BUS Controller OE332-23E-VCMX

Digital Room Sensor Technical Guide 3
OVERVIEW
Overview
The OE217 series of Digital Room Sensors are used to sense Space Tem-
perature only or Space Temperature & Space Humidity. See Figure 1.
They can be used with the VCM-X E-BUS Controller (OE332-23E-
VCMX), RNE Controller (OE332-23E-RNE), and SA E-BUS Controller
(OE332-23E-VCMX-SA).
The sensor provides the following useful functions:
• Provides 112 x 64 monochrome Graphical LCD display with
LED backlight
• Displays the Current Space Temperature or Cooling/Heating
Setpoint on the Main Display Screen
• Displays Outdoor Air Temperature (if controller is confi gured
with OA Temperature Sensor)
• Displays the Current Space Humidity (OE217-01 Model
Only)
• Displays Outdoor Air Relative Humidity (OE217-01 Model if
controller is confi gured with OA Humidity Sensor)
• Displays the Current Zone Setpoint Temperature
Features
Figure 1: Digital Room Sensor
• Equipped with Push Buttons for changing the Zone Setpoint
Temperature
• Equipped with an Override Button for forcing the VCM-X /
RNE / SA Controller into Occupied Operation from
Unoccupied Operation
• Provides graphics to indicate the Mode of Operation
• Allows connection of a remote 10K Ohm, Type III thermistor
temperature sensor (or 4 sensor averaging array). See
Connecting a Remote Sensor section in the Appendix on page
11 for details.
• Provides LEDs to indicate Schedule Override, Button Push,
and Alarms
• Can display Temperature reading from a Remote Sensor (see
Figures 18 & 19, pages 11 & 12 for instructions)
• Can be used with the OE256-01 or OE256-02 CO2 Sensor (see
note in Figure 17, page 10 for instructions)
Both sensors connect to the controllers using various lengths of
TSDRSC modular cables connected between the controller and the
sensor. The TSDRSC modular cables should not run in conduit with
other AC line voltage wiring or with any conductors carrying highly
inductive loads.
Display Override
OVERRIDE ALARM

BASIC OPERATION
Digital Room Sensor Technical Guide4
Figure 2: Digital Room Sensor Components
Sensor Operation
When power is fi rst applied to the OE217-00 Digital Room Sensor, the
sensor will display the Current Room Temperature or the Cooling/Heat-
ing Setpoint and the current setting of the slide off set. The OE217-01
model will also display Relative Humidity.
NOTE: The sensor readings are not accurate until the controller
that the sensor is connected to is done calibrating.
The sensor has 4 buttons—<Display>, <Override>, <Up>, and
<Down>. You can also access certain functions by touching the area
below the <Display> and <Override> buttons. The sensor has 3
LEDs—one to indicate an Override, one to indicate an Alarm, and one
to indicate that a button has been pressed. See Figure 2 for LED and
Button Descriptions.
An icon for the current mode of operation will appear in the sensor
display. The operation mode icons are a Snowfl ake for Cooling Mode,
a Flame for Heating Mode, a Fan in motion for Vent Mode, and a Moon
for Unoccupied Mode. When the unit is in Unoccupied Mode, the
screen’s background will turn dark. See Figure 8, page 6 for examples
of operation modes.
Buttons and LEDs
LED Operation
Refer to Figure 2 below for LED locations.
Alarm LED: The Alarm LED will blink when there is an alarm from
the Controller.
Sense LED: The Sense LED will blink when the sensor gets a valid
touch.
Override LED: The Override LED is inoperable when in Occupied
Mode. In Unoccupied Mode, if you touch the <Override> button, the
Override LED will blink, indicating an override request. The Control-
ler will respond by sending the unit into override. The Override LED
will then stay on for the duration of the Override. Any time the Unit
is in Override, you can request to cancel the override by touching the
<Override> button, and the Override LED will blink. The Unit will
then cancel the override. The Override LED will then turn off .

Digital Room Sensor Technical Guide
MOUNTING AND WIRING
5
Mounting
CAUTION: Do not touch the front face of the sensor while you
are plugging in the modular sensor cable. Touching the front face
of the sensor while plugging in the cable may prevent proper initial-
ization and keep the buttons on the sensor from working properly.
The Digital Room Sensor is designed to be mounted to a vertical 2” x
4” electrical box recessed in the wall. If the wall cannot be penetrated,
a plastic surface mount box such as those made by WiremoldTM may be
used to mount the sensor to the wall surface.
The Sensor is mounted by removing the front cover and fastening the
housing base to the electrical box using the supplied (2) 6/32” x 1” machine
screws. The modular cable is then plugged into the phone jack located
on the circuit board that is mounted on the cover. The cover is then
placed onto the housing base, and the Allen Screw on the bottom of the
base is adjusted to hold the cover in place. A locking screw secures the
sensor to the wall. See Figure 3 for Digital Room Sensor dimensions.
Optional Mounting Plate
Included with the Digital Room Sensor is a mounting plate that
can be used, if necessary, to cover the sensor sheet rock opening.
This mounting plate screws onto the back of the housing base.
The mounting plate is then mounted and covers the recessed space
in the wall. A locking screw secures the sensor to the wall. See
Figure 19, page 12 for dimensions.
Environmental Requirements
The Digital Room Sensor needs to be installed in an environment that
does not exceed a temperature greater than 150°F or less than -30°F and
does not exceed 90% relative humidity levels (non-condensing).
Indoor Reading Range
The Digital Room Sensor’s Indoor Reading Range is 40°F to 120°F and
0-100% RH (RH is available on the OE217-01 Model). Its temperature
reading accuracy is +/- .8°F, and its RH reading accuracy is +/- 3%. Its
sensor element is the integral communicating digital sensing device or
external Type III Thermistor 10K Ohm @ 77°F.
Outdoor Reading Range
If your Digital Room Sensor is set up to read an Outdoor Air Temperature
Sensor, any outdoor air temperature below -40°F will not appear on the
Digital Room Sensor’s display.
Important Wiring Considerations
The OE217-00 and OE217-01 Space Sensors connect to the VCM-X
Controller, RNE, or SA-E-BUS using various lengths of TSDRSC
modular cables connected between the controller and the sensor. The
TSDRSC modular cables should not run in conduit with other AC line
voltage wiring or with any conductors carrying highly inductive loads.
See Figure 17, page 10 for wiring.
Dimensions and Mounting
Figure 3: Digital Room Sensor Dimensions

SENSOR SCREENS
Digital Room Sensor Technical Guide
6
LCD Display Screens
Main Sensor Display Screens
There are 3 Main Sensor Display Screens. The fi rst screen displays
the Current Room Temperature or Cooling/Heating Setpoint, Opera-
tion Mode, Slide Off set, and RH (RH is available on the OE217-01
Model). The second screen displays the Outside Air Temperature and/
or Humidity if Outdoor Air Temperature and/or Outdoor Air Humidity
is being monitored. The third screen displays the unit information for
the controller that the Digital Room Sensor is connected to.
Temperature and Humidity Status
Screen
The Main Display Screen dis-
plays the current room tem-
perature or Cooling/Heating
Setpoint, the humidity in the
room (RH is available on the
OE217-01 Model), the current
setting of the slide off set, and an
icon for the current mode of op-
eration once the controller it is
connected to is done calibrating.
The diff erent icons shown are a
Snowfl ake for cooling mode, a Flame for heating mode, a Fan in mo-
tion for vent mode, and a Moon for unoccupied mode. When the unit is
in unoccupied mode, the screen’s background will turn dark. Refer to
Figure 8 for operation mode screen examples.
Outside Air Temperature Humidity
Status Screen
If the connected controller is
receiving an outdoor air tempera-
ture and/or humidity broadcast,
touching <Display> will fi rst
bring up the Outdoor Status
Screen.
Unit Information
Screen
Touching <Display> again will
bring up the Unit Information
Screen which contains the con-
troller’s address or ID number,
screen ID, and software version
of the controller connected to
the sensor.
Figure 8: Operation Mode Screens
Cooling Mode
with Snowfl ake Icon
Heating Mode
with Flame Icon
Vent Mode
with Fan in Motion Icon
Figure 4: Main Display
Screen
Figure 5: Outdoor Status Screen
Figure 6: Unit
Information Screen
Figure 7: Setpoint Adjust
Screen
Unoccupied Mode
with Moon Icon
Setpoint Adjust Screen
Touching <> or <> will dis-
play the Setpoint Adjust Screen.
You can adjust the cooling
and heating setpoints from this
screen based on the VCM-X
controller’s slide off set setpoint.
For example, if the connected
controller’s Max Slide Offset
Setpoint is set for five, you
can adjust the setpoint up fi ve
degrees and down fi ve degrees.
NOTE: If the VCM-X Controller’s slide off set setpoint is set to
Zero, this screen will not appear when you touch <>
or <>.

Digital Room Sensor Technical Guide
TROUBLESHOOTING
7
Temperature/Resistance Chart
Table 1: Temperature/Resistance for Type III 10K Ohm Thermistor Sensors
Temperature – Resistance – Voltage for
Type III 10K Ohm Thermistor Sensors
Temp
(ºF)
Resistance
(Ohms)
-10 93333
-5 80531
0 69822
5 60552
10 52500
15 45902
20 40147
25 35165
30 30805
35 27140
40 23874
45 21094
50 18655
52 17799
54 16956
56 16164
58 15385
60 14681
62 14014
64 13382
66 12758
68 12191
69 11906
70 11652
Figure 9: Temperature/Resistance Testing
+
-
T
Digital Room Sensor
Back View
9302
MICROCHIP
PIC24HJ
256GP206
NOTE: ,
Table 1
For This Test The Sensor Must Be Disconnected From
Its TSDRSC Cable As Shown. The Meter Must Be Set To
Measure Resistance in Ohms. Use To Determine If The
Sensor Is Reading The Correct Resistance Value For The
Ambient Temperature. This Resistance Value Should Match The
Temperature Value Listed Next To The Resistance Value In The
Table. The Temperature Should Be Measured With A Separate
Accurate Temperature Measuring Device Located In The Area
Where The Sensor Is Currently Located.
Test Points Labeled
“Extern Therm” On
Sensor Circuit Board
+
-
TSDRSC Cable
From
Sensor To The
VAV/Zone or VCM-X
Controller Modular
Sensor Port
Disconnected
Temperature – Resistance – Voltage for
Type III 10K Ohm Thermistor Sensors
Temp
(ºF)
Resistance
(Ohms)
71 11379
72 11136
73 10878
74 10625
75 10398
76 10158
78 9711
80 9302
82 8893
84 8514
86 8153
88 7805
90 7472
95 6716
100 6047
105 5453
110 4923
115 4449
120 4030
125 3656
130 3317
135 3015
140 2743
145 2502
150 2288

APPENDIX
Digital Room Sensor Technical Guide
8
Pixel Test Screen
To select the first option—
Pixels—touch <> while at
the Sensor Configuration &
Test Screen (Figure 11). The
Pixel Test Screen tests the pixels
of the LCD display, allowing
you to make the screen white
with black characters, black
with white characters, or a
black or white screen. To exit
this screen, touch <Display>.
Sensor Info & LED Test Screen
To select the second option—
Info & LEDS—touch <>
while at the Sensor Configura-
tion & Test Screen (Figure 11).
The Sensor Info & LED Test
Screen shows the version of
software that the sensor is run-
ning and allows you to test the
LEDs that are used on the con-
troller. Touching <> will turn
the LEDs on and touching <>
will turn the LEDs off . To exit
this screen, touch <Display>.
Sensor Configuration and Test Screens
Sensor Configuration and Test
Screens
To access the Sensor Configuration & Test Screens, you fi rst need to
access the Unit Information Screen by touching <Display> while at
the Main Display Screen.
NOTE: While in the Sensor Configuration & Test Screens, the
<Display> button functions as an exit key to return to the
previous screen or menu. After a few seconds, however,
the sensor will automatically revert to the Main Display
Screen. Refer to Figure 10 when reading the instructions
that follow.
Sensor Configuration & Test Screen
While the Unit Information
Screen is being displayed, you
can enter the Sensor Configura-
tion & Test Screen options by
touching simultaneously below
the <Display> and <Over-
ride> buttons. (See Figure 10
which shows where to touch to
access this option.)
Figure 10: Digital Room Sensor Buttons
Figure 11: Sensor
Confi guration & Test
Screen
Figure 13: Sensor Info &
LED Test Screen
Figure 12: Sensor Info &
LED Test Screen

Digital Room Sensor Technical Guide
APPENDIX
9
LCD Backlight Test Screens
To select the third option—
BACKLT—touch <Override>
while at the Sensor Configuration
& Test Screen (Figure 11). This
option allows you to control
when the LCD backlight turns
on and off . You can confi gure the
backlight to stay on at all times,
remain off at all times, or to come
on when any button is touched on
the sensor.
To exit this screen, touch <Dis-
play>.
Thermistor Averaging Screen
To select the fourth and fi nal op-
tion—THRM AVG—, while at
the Sensor Configuration & Test
Screen (Figure 11), touch simul-
taneously below the <Display>
and <Override> buttons. (See
Figure 10 which shows where to
touch to access this option.)
This option allows you to set the
rate—from 1-15 seconds—at
which the sensor takes a new
temperature reading. Touch <>
to increase the number of seconds
and touch <> to decrease the
number of seconds.
To exit this screen, touch <Dis-
play>.
NOTE: The sensor takes the average of the last 10 readings based
on the number that is entered in this screen. For example,
if you want a 3-second sample, the sensor will take the
average of the last 10 readings every 3 seconds over a
30-second span. Therefore, if you have your sensor next
to an outside doorway, you would want to enter a higher
number for your sample to give a more accurate read-
ing for the room temperature in case the outside door is
opened often.
Sensor Configuration and Test Screens
Figure 14: Backlight Test
& Confi guration Screen
Figure 15: Temperature
Averaging Screen
Display Options - Temperature/Setpoint
To access the Display Options
Screen, while at the Thermistor
Averaging Screen, (Figure 15),
touch the <Override> button.
This option allows you to set the
main screen display. Touch <>
to display the Cooling/Heating
Setpoint on the Main Display
Screen. Touch <> to display
the current room temperature on
the Main Display Screen. The
default is temperature.
If the Setpoint option is chosen,
when the unit is in the Cooling
Mode, the Cooling Setpoint
will appear on the Main Display
Screen. When the unit is in the
Heating Mode, the Heating Set-
point will appear on the Main
Display Screen. When the unit
is in Unoccupied Mode or Vent
Mode, the setpoint that appears
on the Main Display Screen will
be half way between the Cooling
and Heating Setpoint.
To exit this screen, touch
<Display>.
Figure 16: Address
Screen
DSPLY OPTIONS
TEMPERATURE
UP = SETPOINT
DOWN = TEMP

APPENDIX
Digital Room Sensor Technical Guide
10
HVAC Unit Controller Wiring
OE217-00 Or OE217-01
Digital Room Sensor
OE332-23E-VCMX
VCM-X E-BUS Controller
TSDRSC Cable
Display Override
OVERRIDE ALARM
NOTE: If Also Using An OE256-01
Or OE256-02 CO Sensor, The CO
Sensor Always Connects To The
VCM-X Controller First Using A
TSDRSC Cable Of The Required
Length. The Digital Room Sensor
Then Connects To The CO Sensor
With Another TSDRSC Cable.
The Total Length Of Cable For Either
One Or Both Cables Combined
Cannot Exceed 160 Feet. See The
For
Further Wiring Details.
22
2
CO2Sensor Technical Guide
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102033-01
OE332-23-VCMX-A VCM-X CONTROLLER
WARNING
OBSERVE
POLARITY
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102073-01-A
Rev.: 1A
www.aaon.com
www.orioncontrols.com
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AAON No.:
V07150
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
LED BLINK CODES
LED NAME STATUS1 STATUS2
NORMAL OPERATION 0 1
SAT FAIL 1 2
OAT FAIL 2 2
SPC FAIL 3 2
MODULE ALARM 4 2
MECH COOL FAIL 1 3
MECH HEAT FAIL 2 3
FAN PROOF FAIL 3 3
DIRTY FILTER 4 3
EMERGENCY SHUTDOWN 5 3
LOW SAT 1 4
HIGH SAT 2 4
CONT. TEMP COOL FAIL 3 4
CONT. TEMP HEAT FAIL 4 4
PUSH BUTTON OVR 1 5
ZONE OVR 2 5
OUTPUT FORCE ACTIVE 0 6
E-BUS
CONNECTOR
Figure 17: Digital Room Sensor to HVAC Unit Controller Wiring (VCM-X E-BUS Shown)

Digital Room Sensor Technical Guide
APPENDIX
11
Connecting a Remote Sensor
Connecting a Remote Sensor
If the job requires this Sensor to be mounted outside of a conditioned
space, a remote OE210 Space Sensor or OE231 Return Air Temperature
Sensor (or any 2-wire 10K Ohm, Type III thermistor temperature sen-
sor) can be hard-wired to the Digital Room Sensor. Other versions of
the space sensors (OE211, OE212, or OE213) with slide adjust and/or
override button should not be used as the remote sensor.
Contact AAON Controls for wiring information if a four sensor averag-
ing array will be used as the “remote sensor”.
See Figure 19 for OE231 Return Air Temperature Sensor wiring. See
Figure 20 for OE210 Space Sensor wiring.
OE217-00 - Digital Room Temperature Only Sensor
Disconnect the modular cable from the Digital Room Sensor before
performing the following modifi cations.
If using the OE217-00 Temperature Only version of the sensor, you must
fi rst remove the Digital Sensor’s back cover. You will see a loop of wire
hanging off of the sensor circuit board. See Figure 21. This is the external
thermistor loop wire. Clip the external thermistor loop wire so that the
sensor will read the remote temperature input. Be sure to cut the ends
of the wire close to the circuit board so that the sensor loop wire ends
Figure 18: OE231 Return Air Temperature Sensor Wiring
MICROCHIP
PIC24HJ
256GP206
OE217-00 & OE217-01
Digital Room Sensor
Back View
Sensor Shown With
Back Cover Removed
Mount Sensor In Return Air
Duct As Shown. Route Wires
To Digital Room Sensor
Location And Connect To
Terminal Block.
Return
Air Duct
OE231 Return Air
Temperature Sensor
won’t short between each other. The remote sensor then wires to the
remote sensor terminal block on the back of the Digital Room Sensor.
If using the OE210 type Space Sensor as the remote sensor, you must
clip off the C1 capacitor from the back of the OE210. Be sure to cycle
power to begin reading the remote sensor. See Figure 20.
OE217-01 - Digital Room Temperature and Humidity
Sensor
Disconnect the modular cable from the Digital Room Sensor before
performing the following modifi cations.
If using the OE217-01 Temperature and Humidity version of the Digital
Room Sensor, you only need to wire the remote sensor to the remote
sensor terminal block on the digital sensor. DO NOT CLIP OFF OR
REMOVE the temperature/humidity sensing element on the Digital Sen-
sor. See Figure 22. When the remote temperature sensor is wired in, it
will override the on-board temperature value of the OE217-01 sensor,
even though the sensor element remains attached.
If using the OE210 type Space Sensor as the remote sensor, you must
clip off the C1 capacitor from the back of the OE210. Be sure to cycle
power to begin reading the remote sensor. See Figure 20.

APPENDIX
Digital Room Sensor Technical Guide
12
Connecting a Remote Sensor
Figure 19: Attaching the OE210 Space Room Sensor
MICROCHIP
PIC24HJ
256GP206
OE217-00 & OE217-01
Digital Room Sensor
Back View
Sensor Shown With
Back Cover Removed
Remove
C1 Capacitor
OE210 Space
Temperature Sensor
Back View
TMP
GND
AUX
OUT

Digital Room Sensor Technical Guide
APPENDIX
13
Connecting a Remote Sensor
Figure 20: Wire Clipping Instructions For OE217-00 - Digital Room Temperature Only Sensor
MICROCHIP
PIC24HJ
256GP206
OE217-00 Digital Room
Temperature Sensor Only
Back View
Sensor Shown With
Back Cover Removed
Cut Wire Loop As Shown.
Make Sure That The Wires
Are Cut Close Enough To
The Circuit Board So They
Can’t Touch Each Other.
Figure 21: Instructions For OE217-01 - Digital Room Temperature & Humidity Sensor
MICROCHIP
PIC24HJ
256GP206
OE217-01 Digital Room
Temperature & Humidity Sensor
Back View
Sensor Shown With
Back Cover Removed
WARNING: DO NOT CLIP OFF OR REMOVE THE
TEMPERATURE & HUMIDITY SENSING ELEMENT
Sensing Element

APPENDIX
Digital Room Sensor Technical Guide
14
Mounting Plate Dimensions
Optional Mounting Plate
Included with the Digital Room Sensor is a mounting plate that
can be used, if necessary, to cover the sensor sheet rock opening.
This mounting plate screws onto the back of the housing base.
The mounting plate is then mounted and covers the recessed space
in the wall. A locking screw secures the sensor to the wall. See
Figure 23, below for dimensions.
Figure 22: BK000081 Mounting Plate Dimensions
1.638
1.810
0.882
1.407
1.842
0.733
2.110
2.920
0.810
R0.220
3.275
0.060
0.160
5.037
3.278
3.766
4.153

Digital Room Sensor Technical Guide
NOTES
15

Form: OR-DRS-TGD-01M Printed in the USA August 2018
All rights reserved. Copyright 2018
AAON Controls • 8500 NW River Park Drive • Parkville, MO • 64152
Phone: 866-918-1100 www.orioncontrols.com Fax (816) 505-1101
This manual suits for next models
1
Table of contents