●PNP output type
(Brown) +V
+
-
12 to 24V DC
±10%
Load
Main circuit
(Black) Detection output
(White)
Detection auxiliary output
(Blue) 0V
Load
7
HUMAN ERROR PREVENTION (SAFETY INTERLOCK) FUNCTION
●In case this product is removed from the at-
tachment by equipment failure after installa-
tion or maintenance (state that not detectable
leakage), This product becomes interlock
state and the output turns to OFF.
Attachment
This
product
8MAINTENANCE
WARNING
Before conduct maintenance, be sure that the system is in safety state.
●Operation when leaked
• When doing maintenance after leak detection, separate this device and the
mounting bracket set MS-SQ4-□ (the attachment and the mounting bracket.)
For removing method, refer to “ MOUNTING”.
• Wipe all liquid from the attachment, sensor and the installation surface. To avoid
scratching the detecting surface and the optional mounting bracket, use a soft cloth.
●Six months inspection
• Be sure there are no scratch, no broken, and no damage on the cable.
• Be sure there are no dust and no contamination on the detecting surface.
• Be sure the product does not oat from the attachment.
• Be sure the output is correctly detected.
• Be sure safety interlock function works properly (output OFF).
●Inspection after maintenance
• In condition below, conduct items in six months inspection.
1) After doing maintenance of this product after leakage.
2) After replacing this product.
3) After operation error of this product is occurred.
4)
After installed place of this product or installation environment is changed.
5) When changed wiring or wiring method.
9CAUTIONS
●Leak detection part of this product properly
detects the leakage in the following condition.
• Detection range: Area except backward of this product
(liquid must enter to the detection range)
• Material of installation surface:
• Hard vinyl chloride or Stainless-steel
• Surface condition for installation:
glossy surface (surface roughness: corre-
sponding 0.4μmRa) and clean surface.
• Installation surface angle: horizontal Detection range
●This product may not detect properly liquid in following element.
• liquid kind, consistency (surface tension) and air bubble incorporation.
• Material, roughness, angle, dirtiness and liquid absorption of surface of in-
stalled surface of sensor.
• Wrong selection of dedicated mounting bracket.
●Check the detecting liquid and the installation condition before use.
10
OPTIONS
Type Model No. Applicable
Sensor Description
Double
step de-
tection
type
Standard
liquid MS-SQ4-21 SQ4-A21-□
Double step detection type attachment for standard liquid: 1 pc.
(Polypropylene)
PVC Mounting Bracket : 1 pc.
Chemical
liquid A MS-SQ4-22 SQ4-A22-□
Double step detection type attachment for chemical liquid: 1 pc.
(PFA)
PFA Mounting Bracket (Stainless steel bush) : 1 pc.
Chemical
liquid B MS-SQ4-23 SQ4-A22-□
Double step detection type attachment for chemical liquid: 1 pc.
(PFA)
PVC Mounting Bracket : 1 pc.
Chemical
liquid C MS-SQ4-24 SQ4-A22-□
Double step detection type attachment for chemical liquid: 1 pc.
(PFA)
PVC Mounting Bracket : 1 pc.
Notes: 1) Chemical liquid A···Sulfuric acid, Hydrochloric acid, Phosphoric acid or Ammonia etc.
such as surface tension is stronger
Chemical liquid B···Fluorinert®,
Galden®
, high consistency of Hydrouoric acid etc. such as surface
tension is weaker
Chemical liquid C Liquid such as low consistency of Hydrouoric acid
Surface tension of chemical liquid is also depend on the temperature.
2) Further, PVC mounting bracket may not be used depending on type or viscosity etc.
Before using this device, check the detecting liquid and installation condition.
Type Model No. Description
Controller SQ4-C11
• The controller can connect 4 sensor heads maximum.
• In case output of sensor head is short or circuit of emittern or
receiver is broken, inform you them by the indicator.
• For more detail of the controller, reffer to attached instruction manual
in the controller.
11
SPECIFICATION
Type Standard liquid type Chemical liquid type
Model
No.
NPN output type
SQ4-A21-N SQ4-A22-N
PNP output type
SQ4-A21-P SQ4-A22-P
Detection object (Note 1)
Water (Standard liquid)
Sulfuric acid, Hydrochloric acid, Phosphoric acid, Ammonia,
Fluorinert®, Galden®, Hydrofluoric acid etc. (Note 2)
Supply voltage 12 to 24V DC ±10% Ripple P-P 10% or less
Current consumption 30mA or less
Utilization category DC-12, DC-13
Detection output
(Leakage detection)
<NPN output type>
NPN open-collector transistor
• Maximum sink current: 50mA
• Applied voltage: Same as the supply voltage
(between detection output and 0V)
• Residual voltage: 2V or less
(at 50mA
sink current)
<PNP output type>
PNP open-collector transistor
• Maximum source current: 50mA
• Applied voltage: Same as the supply voltage
(between detection output and +V)
• Residual voltage: 2.5V or less
(at 50mA source current)
Response time 10ms or less
Output operation ON when initial detection, OFF when detection leakage or wrong installation
Short-circuit protection
Incorporated
Detection auxiliary
output
(Initial detecting)
<NPN output type>
NPN open-collector transistor
• Maximum sink current: 50mA
• Applied voltage: Same as the supply voltage
(between detection auxiliary output and 0V)
• Residual voltage: 2V or less
(at 50mA sink current)
<PNP output type>
PNP open-collector transistor
• Maximum sink current: 50mA
• Applied voltage: Same as the supply voltage
(between detection auxiliary output and +V)
• Residual voltage: 2.5V or less
(at 50mA sink current)
Response time 50ms or less
Output operation ON when normal condition, OFF when Initial detection or accidental leakage
Short-circuit protection
Incorporated
Protection IP65 / IP67 (IEC)
Ambient temperature -10 to +55°C (No dew condensation or icing allowed) (Note 3), Storage: -10 to +55°C
Ambient humidity 35 to 85% RH, Storage: 35 to 85% RH
Ambient illuminance Incandescent light: 1,000ℓx at the light-receiving face
Altitude for use 2000m or less above sea level (Note 4)
Vibration resistance
Malfunction: 10 to 55 Hz multiple amplitude 0.75mm 2 hours for each X, Y and Z directions (in power supply)
Shock resistance
Malfunction: Peak acceleration 294m/s2 (Approx. 30G), 3 times for each X, Y and Z direction
PFHd (Note 5) NPN output type: 1.57 × 10-8, NPN output type: 1.79× 10-8
SFF (Note 6) NPN putput type: 94%, PNP output type: 95%
HFT (Note 7) 0
Sub-system time Type A (IEC 61508-2)
Mission time 20 years
Detectable failure modes by connect-
ing to SQ4-C11 (exclusive controller)
Output short, broken internal circuit and etc.
Emitting element Infrared LED (modulated)
Material Enclosure: Polypropylene Enclosure: PFA
Cable
0.18mm2 4-core PVC cabtire cable, 2m long
0.1mm2 4-core PFA cabtire cable, 2m long
Weight Approx. 45g
Notes: 1) Highly viscous liquid may not be stably detected.
2) The agents mentioned above are examples. It may not be detected depending on viscosity the agent.
Before using this device, check the detecting liquid and installation condition.
3) Liquid being detected should be also kept within the rated ambient temperature range.
4) Do not use or storage in environment of atmospheric pressure or more.
5) PFHd: Probability of dangerous failure per hour.
6) SSF: Safe failure fraction
7) HFT: Hardware failure tolerance
12
CAUTIONS
●Make sure that the power supply is OFF while wiring. Also wrong wiring cause damage of the sensor.
●If power is supplied from a commercial switching regulator, ensure that the frame
ground (F.G.) terminal of the power supply is connected to an actual ground.
●Do not use during the initial transient time (approx. 50ms) after the power supply is switched ON.
●Extension up to total 30m is possible with a 0.3mm2, or more of conductor cross-section
area cable. However, in order to reduce noise, make the wiring as short as possible.
●Do not run the wires together with high-voltage lines or power lines or put them
in the same raceway. This can cause malfunction due to induction.
●In case a surge is generated from power supply, take countermeasures such
as connecting a surge absorber to the origin of the surge.
●In case air bubbles are drawn into the detection part, take care that it may take
some time for detection to stabilize, or detection may even become unstable.
●When liquid or oil remains or there is scratch on the detection surface or the
attachment, It may not work properly.
13
DIMENSIONS (unit: mm)
●Standard liquid type sensor SQ4-21-□
35.8
ø35
18 (7.5)
ø8 25
0.5
7.5 13.5
ø3.7 cable 2m
1
1
2.2
<Attached with MS-SQ4-21>
2 × ø4.3
13
35.8
ø35
25 4.5
5.6
12.7 18.7
ø3.7 cable 2m
22 31