Panaconic SQ4-A Series User manual

INSTRUCTION MANUAL
Safety Liquid Leakage Sensor SQ4-A series
MJE-SQ4A No.0050-09V
Thank you very much for purchasing Panasonic products.
Please read this Instruction Manual carefully and thoroughly for the correct and
optimum use of this product.
Kindly keep this manual in a convenient place for quick reference.
English and Japanese are original instructions.
WARNING
● This product is a sensor for detecting leak of uids.
●When this product is used with safety devices, construct the system such that
the device itself.
1ATTENTION MARKS
This instruction manual employs the following attentions marks “ WARNING”, and
“CAUTION”, depending on the degree of the danger.
WARNING
If you ignore the advice with this mark, death or serious injury could result.
CAUTION
If you ignore the advice with this mark, injury or material damage could result.
2SAFETY PRECAUTIONS
●Use this device as per its specifications. Do not modify this device since its
functions and capabilities may not be maintained and it may malfunction.
●This device has been developed / produced for industrial use only.
●This device is suitable for indoor use only.
●Use of this device under the following conditions or environment is not presupposed.
1)
Operating this device under conditions and environment not described in this manual.
2)
Using this device in the following elds: nuclear power control, railroad, aircraft,
automobiles, combustion facilities, medical systems, aerospace development, etc.
●Use this device by installing suitable protection equipment as a countermea-
sure for failure, damage, or malfunction of this device.
●Before using this device, check whether the device performs properly with the
functions and capabilities as per the design specications.
●In case of disposal, dispose this device as industrial waste.
WARNING
♦Machine designer, installer, employer and operator
• The machine designer, installer, employer and operator are solely responsi-
ble to ensure that all applicable legal requirements relating to the installation
and the use in any application are satised and all instructions for installa-
tion and maintenance contained in the instruction manual are followed.
• Whether this device functions as intended to and systems including this de-
vice comply with safety regulations depends on the appropriateness of the
application, installation, maintenance and operation. The machine designer,
installer, employer and operator are solely responsible for these items.
• The engineer would be a person who is appropriately educated, has wide-
spread knowledge and experience, and can solve various problems which
may arise during work, such as a machine designer, or a person in charge
of installation or operation etc.
• The operator should read this instruction manual thoroughly, understand its
contents, and perform operations following the procedures described in this
manual for the correct operation of this device.
• In case this device does not perform properly, the operator should report this to
the person in charge and stop the machine operation immediately. The machine
must not be operated until correct performance of this device has been conrmed.
♦Installation
• There is the detection mount difference by directivity of a liquid leakage. When there
are a direction from which a liquid leakage happens, and an inclination, please in-
stall the nose-of-cam side (opposite side of a cable) of a sensor towards a top.
• Use the mounting bracket MS-SQ4-□ (optional) which suits the liquid to de-
tect. If selecting mounting bracket is wrong, it does not work properly.
• Periodical checking of operation is recommended with the liquids which are
not dangerous (water, alcohol, etc.).
• The amount of detection may change with the conditions of the installation surface.
• Be sure to use the mounting bracket MS-SQ4-□ (optional) when installing this device to avoid
human error, etc. Reliable detection cannot be guaranteed when this sensor is used alone.
• After installing this product, x the cable at 100mm of base of this product on oor. Use the
material which does not be effected by the chemical liquid for the xing bracket for cable.
♦Wiring
• In case dangerous operation of the system installed this product by no wir-
ing to ground is not considered , it may cause serious injure or death.
• To avoid turning the power ON by no wiring to ground, wire it to ground 0V
side when using PNP and wire it to ground +24V when using NPN.
♦Environment
• Avoid using this device in an explosive atmosphere because this product
does not have an explosive-proof protective construction.
• Do not use a mobile phone or a radio phone near this device.
• In case this device is used where electrostatic charge is present, use a
metal leak pan, which should be connected to an actual ground.
• Do not install this device in the following environments.
1)
Areas exposed to intense interference (extraneous) light such as high-
frequency uorescent lamp (inverter type), rapid starter uorescent lamp,
stroboscopic lights, ash beacon lights or direct sunlight.
2) Areas with high humidity where condensation is likely to occur
3)
Areas exposed to too much steam or dust. Areas exposed to corrosive or explo-
sive gases. And do not use this device where oil or grease splashes to this device
4) Areas exposed to vibration or shock of levels higher than that specied.
♦Maintenance
• When using chemical liquid, use proper protections such as groves, masks,
goggles, helmets etc. When using protections, me sure to read manuals of
them and use properly.
• Dispose or reinstall in different environment, ush with DI water.
3STANDARDS / REGULATIONS
●This product complies with following standards / regulations.
<International Standard>
IEC 61508-1 to 7(SIL1), EN ISO 13849-1: 2008 (Category 1, PLc)
IEC 60947-5-2 (Note)
Note: The conformity to IEC 60947-5-2 for this device has been evaluated by ourselves.
<Regulations in Korea>
S1-G-1-2009, S2-W-5-2009
●This product is pursuant to following standard.
<SEMI standard>
SEMI-S2-0310a
4PART DESCRIPTION
Detection output
indicator (Red)
Detection leakage
and wrong installation:
Light up
Detection auxiliary output indicator (Orange)
Initial detection, leakage detection and
wrong installation: Light up
Detection output indicator (Green)
Normal or Initial detection: Light up
CAUTION
In case of installation error, detection output indicator (red) and detection auxil-
iary output indicator (Orange) light up
5MOUNTING
CAUTION
Keep enough space for maintenance when mount-
ing this product. Space
Mounting method
1.
Mount the mounting bracket set MS-SQ4-□ (optional)
with M4 stud-bolts or adhesive.
<Mounting with M4 stud-bolts>
1-1 Weld the M4 stud-bolts (length: 10mm or
more) to your system.
1-2
Insert the M4 stud-bolts (length 10mm or more)
welded on the user’s facilities into the mounting
hole of the mounting bracket and screw with an
M4 nut (purchase separately). The tightening
torque should be 0.98N·m or less.
<Mounting the PVC mounting bracket with adhesive>
1-1
Put the adhesive to underside of the mounting
bracket and stick it on surface of the system.
Thickness of the adhesive after sticking is set
to 0.1mm or less. And use adhesive for vinyl
chlovide (PVC).
Notes: 1) If the excess adhesive from the bottom surface of the exclu-
sive mounting bracket is remained, the detection capability
may be affected.
2. The attachment is set according to A part of the
mounting bracket.
3. Inserts from a top by holding knob part. Then
press in downward in the attachment.
Notes: 2) In case the attachment incline on the oor, malfunction can be
occurred. Also, malfunction can be occurred by changing of the
shape of attachment and scratch or dust etc.
M4 nut
M4 stud-bolt
Mounting
bracket
Adhesive face
Mounting
bracket
3. Press
Attachment 2. Insert
A part
Chase
This
product
Knob part
Dismounting method
1. Hold the knob part of this product and pull out
from mounting bracket upward.
Notes: 1) When pulling out this product, it may cause break of cables. Be
careful.
2) When detaching part, do not use tool etc. Malfunction can be
occurred by changing of the shape of the attachment and scratch
etc.
2.
Pull out
the attachment upward from the mounting
bracket.
3. In case the mounting bracket is mounted with the
M4 stud-bolts, remove M4 nuts.
In case the mounting bracket is mounted with the
M4 stud-bolts, do not remove.
Knob part
Attachment
This
product
1. Pull out
2. Pull out
6I/O CIRCUIT DIAGRAMS
●NPN output type
Main circuit
(Brown) +V
(Black) Detection output
(White) Detection auxiliary output
+
-
12 to 24V DC
±10%
Load
(Blue) 0V
Load
056 222 38 18 mailbox@sentronic.com www.sentronic.com
SENTRONIC AG

●PNP output type
(Brown) +V
+
-
12 to 24V DC
±10%
Load
Main circuit
(Black) Detection output
(White)
Detection auxiliary output
(Blue) 0V
Load
7
HUMAN ERROR PREVENTION (SAFETY INTERLOCK) FUNCTION
●In case this product is removed from the at-
tachment by equipment failure after installa-
tion or maintenance (state that not detectable
leakage), This product becomes interlock
state and the output turns to OFF.
Attachment
This
product
8MAINTENANCE
WARNING
Before conduct maintenance, be sure that the system is in safety state.
●Operation when leaked
• When doing maintenance after leak detection, separate this device and the
mounting bracket set MS-SQ4-□ (the attachment and the mounting bracket.)
For removing method, refer to “ MOUNTING”.
• Wipe all liquid from the attachment, sensor and the installation surface. To avoid
scratching the detecting surface and the optional mounting bracket, use a soft cloth.
●Six months inspection
• Be sure there are no scratch, no broken, and no damage on the cable.
• Be sure there are no dust and no contamination on the detecting surface.
• Be sure the product does not oat from the attachment.
• Be sure the output is correctly detected.
• Be sure safety interlock function works properly (output OFF).
●Inspection after maintenance
• In condition below, conduct items in six months inspection.
1) After doing maintenance of this product after leakage.
2) After replacing this product.
3) After operation error of this product is occurred.
4)
After installed place of this product or installation environment is changed.
5) When changed wiring or wiring method.
9CAUTIONS
●Leak detection part of this product properly
detects the leakage in the following condition.
• Detection range: Area except backward of this product
(liquid must enter to the detection range)
• Material of installation surface:
• Hard vinyl chloride or Stainless-steel
• Surface condition for installation:
glossy surface (surface roughness: corre-
sponding 0.4μmRa) and clean surface.
• Installation surface angle: horizontal Detection range
●This product may not detect properly liquid in following element.
• liquid kind, consistency (surface tension) and air bubble incorporation.
• Material, roughness, angle, dirtiness and liquid absorption of surface of in-
stalled surface of sensor.
• Wrong selection of dedicated mounting bracket.
●Check the detecting liquid and the installation condition before use.
10
OPTIONS
Type Model No. Applicable
Sensor Description
Double
step de-
tection
type
Standard
liquid MS-SQ4-21 SQ4-A21-□
Double step detection type attachment for standard liquid: 1 pc.
(Polypropylene)
PVC Mounting Bracket : 1 pc.
Chemical
liquid A MS-SQ4-22 SQ4-A22-□
Double step detection type attachment for chemical liquid: 1 pc.
(PFA)
PFA Mounting Bracket (Stainless steel bush) : 1 pc.
Chemical
liquid B MS-SQ4-23 SQ4-A22-□
Double step detection type attachment for chemical liquid: 1 pc.
(PFA)
PVC Mounting Bracket : 1 pc.
Chemical
liquid C MS-SQ4-24 SQ4-A22-□
Double step detection type attachment for chemical liquid: 1 pc.
(PFA)
PVC Mounting Bracket : 1 pc.
Notes: 1) Chemical liquid A···Sulfuric acid, Hydrochloric acid, Phosphoric acid or Ammonia etc.
such as surface tension is stronger
Chemical liquid B···Fluorinert®,
Galden®
, high consistency of Hydrouoric acid etc. such as surface
tension is weaker
Chemical liquid C Liquid such as low consistency of Hydrouoric acid
Surface tension of chemical liquid is also depend on the temperature.
2) Further, PVC mounting bracket may not be used depending on type or viscosity etc.
Before using this device, check the detecting liquid and installation condition.
Type Model No. Description
Controller SQ4-C11
• The controller can connect 4 sensor heads maximum.
• In case output of sensor head is short or circuit of emittern or
receiver is broken, inform you them by the indicator.
• For more detail of the controller, reffer to attached instruction manual
in the controller.
11
SPECIFICATION
Type Standard liquid type Chemical liquid type
Model
No.
NPN output type
SQ4-A21-N SQ4-A22-N
PNP output type
SQ4-A21-P SQ4-A22-P
Detection object (Note 1)
Water (Standard liquid)
Sulfuric acid, Hydrochloric acid, Phosphoric acid, Ammonia,
Fluorinert®, Galden®, Hydrofluoric acid etc. (Note 2)
Supply voltage 12 to 24V DC ±10% Ripple P-P 10% or less
Current consumption 30mA or less
Utilization category DC-12, DC-13
Detection output
(Leakage detection)
<NPN output type>
NPN open-collector transistor
• Maximum sink current: 50mA
• Applied voltage: Same as the supply voltage
(between detection output and 0V)
• Residual voltage: 2V or less
(at 50mA
sink current)
<PNP output type>
PNP open-collector transistor
• Maximum source current: 50mA
• Applied voltage: Same as the supply voltage
(between detection output and +V)
• Residual voltage: 2.5V or less
(at 50mA source current)
Response time 10ms or less
Output operation ON when initial detection, OFF when detection leakage or wrong installation
Short-circuit protection
Incorporated
Detection auxiliary
output
(Initial detecting)
<NPN output type>
NPN open-collector transistor
• Maximum sink current: 50mA
• Applied voltage: Same as the supply voltage
(between detection auxiliary output and 0V)
• Residual voltage: 2V or less
(at 50mA sink current)
<PNP output type>
PNP open-collector transistor
• Maximum sink current: 50mA
• Applied voltage: Same as the supply voltage
(between detection auxiliary output and +V)
• Residual voltage: 2.5V or less
(at 50mA sink current)
Response time 50ms or less
Output operation ON when normal condition, OFF when Initial detection or accidental leakage
Short-circuit protection
Incorporated
Protection IP65 / IP67 (IEC)
Ambient temperature -10 to +55°C (No dew condensation or icing allowed) (Note 3), Storage: -10 to +55°C
Ambient humidity 35 to 85% RH, Storage: 35 to 85% RH
Ambient illuminance Incandescent light: 1,000ℓx at the light-receiving face
Altitude for use 2000m or less above sea level (Note 4)
Vibration resistance
Malfunction: 10 to 55 Hz multiple amplitude 0.75mm 2 hours for each X, Y and Z directions (in power supply)
Shock resistance
Malfunction: Peak acceleration 294m/s2 (Approx. 30G), 3 times for each X, Y and Z direction
PFHd (Note 5) NPN output type: 1.57 × 10-8, NPN output type: 1.79× 10-8
SFF (Note 6) NPN putput type: 94%, PNP output type: 95%
HFT (Note 7) 0
Sub-system time Type A (IEC 61508-2)
Mission time 20 years
Detectable failure modes by connect-
ing to SQ4-C11 (exclusive controller)
Output short, broken internal circuit and etc.
Emitting element Infrared LED (modulated)
Material Enclosure: Polypropylene Enclosure: PFA
Cable
0.18mm2 4-core PVC cabtire cable, 2m long
0.1mm2 4-core PFA cabtire cable, 2m long
Weight Approx. 45g
Notes: 1) Highly viscous liquid may not be stably detected.
2) The agents mentioned above are examples. It may not be detected depending on viscosity the agent.
Before using this device, check the detecting liquid and installation condition.
3) Liquid being detected should be also kept within the rated ambient temperature range.
4) Do not use or storage in environment of atmospheric pressure or more.
5) PFHd: Probability of dangerous failure per hour.
6) SSF: Safe failure fraction
7) HFT: Hardware failure tolerance
12
CAUTIONS
●Make sure that the power supply is OFF while wiring. Also wrong wiring cause damage of the sensor.
●If power is supplied from a commercial switching regulator, ensure that the frame
ground (F.G.) terminal of the power supply is connected to an actual ground.
●Do not use during the initial transient time (approx. 50ms) after the power supply is switched ON.
●Extension up to total 30m is possible with a 0.3mm2, or more of conductor cross-section
area cable. However, in order to reduce noise, make the wiring as short as possible.
●Do not run the wires together with high-voltage lines or power lines or put them
in the same raceway. This can cause malfunction due to induction.
●In case a surge is generated from power supply, take countermeasures such
as connecting a surge absorber to the origin of the surge.
●In case air bubbles are drawn into the detection part, take care that it may take
some time for detection to stabilize, or detection may even become unstable.
●When liquid or oil remains or there is scratch on the detection surface or the
attachment, It may not work properly.
13
DIMENSIONS (unit: mm)
●Standard liquid type sensor SQ4-21-□
35.8
ø35
18 (7.5)
ø8 25
0.5
7.5 13.5
ø3.7 cable 2m
1
1
2.2
<Attached with MS-SQ4-21>
2 × ø4.3
13
35.8
ø35
25 4.5
5.6
12.7 18.7
ø3.7 cable 2m
22 31
056 222 38 18 mailbox@sentronic.com www.sentronic.com
SENTRONIC AG

●Chemical liquid type sensor SQ4-22-□
35.8
ø35
18 (7.5)
ø
5.6
25
0.5
7.5 13.5
ø2.8 cable 2m
1
1
2.2
<Sensor with attachment set>
D
13 22 31
35.8
ø35
25 4.5
A
BC
ø2.8 cable 2m
Attachement set type A B C D
MS-SQ4-22 5.4 12.7 18.7 2 × ø4.2
MS-SQ4-23 3.4 10.5 16.5 2 × ø4.3
MS-SQ4-24 5.6 12.7 18.7 2 × ø4.3
●Mounting bracket set MS-SQ4-□
<Attachment>
E
35
Model No.
A E
MS-SQ4-21
5.6 2.5
MS-SQ4-22
5.4 2.5
MS-SQ4-23
3.4 0.3
MS-SQ4-24
2.5 2.5
<PVC / PFA Mounting bracket>
4.5
13
22
31
A
2 × ø4.2
(Note 2)
Stainless steel bush
(Note 1)
Notes: 1) Drawing above is for PFA mounting bracket.
PVC mounting brackets M-SQ4-11,M-SQ4-21
and M-SQ4-23 do not incorporate stainless steel
bushs.
2)
The mounting holes size of PVC mounting
bracket is ø4.3.
14
CE MARKING DECLARATION OF CONFORMITY
Itemized Essentials of EU Declaration of Conformity
Manufacturer’s Name: Panasonic Industrial Devices SUNX Co., Ltd.
Manufacturer’s Address:
2431-1, Ushiyama-cho, Kasugai, Aichi 486-0901, Japan
EU Representative’s Name:
Panasonic Marketing Europe GmbH Panasonic Testing Center
EU Representative’s Address: Winsbergring 15, 22525 Hamburg, Germany
Product: Safety Liquid Leakage Sensor
Model Name: SQ4 Series
Trade Name: Panasonic
Application of Council Directive:
- 2006/42/EC Machinery Directive
- 2004/108/EC EMC Directive (Valid until April 19, 2016)
- 2014/30/EU EMC Directive (Valid from April 20, 2016)
- 2011/65/EU RoHS Directive
Harmonized standards:
- EN ISO 13849-1: 2008
- EN 55011: 2009+A1: 2010
- EN 61000-6-2: 2005
- EN 50581: 2012
Type Examination: Certied by TÜV SÜD Product Service GmbH
Ridlerstrasse 65 80339 München Germany
http://panasonic.net/id/pidsx/global
Overseas Sales Division (Head Ofce)