9-7. Table of Self-Diagnostic Functions and Corrections (E1 Type)
Wired remote
controller
display
Indoor unit
receiver lamp
Cause
Correction
1:1 connection (single type) Group connection Simultaneous-operation multi system
(flexible combination) Control by main-sub
remote controllers
Nothing is
displayed Nothing is
displayed
●Remote controller is not connected
correctly.
●Indoor unit power is not ON.
●Remote controller is not connected
with indoor unit correctly
●Indoor unit power is not ON.
●Same at left ●Same at left Connect the remote controller correctly.
Turn ON the indoor unit power.
E01 displayed
Operating lamp
is blinking.
●Automatic address setting has not been
completed.
●Inter-unit control wiring is cut or is not
connected correctly.
●Remote controller is not connected
correctly (remote controller receiving
failure).
●Automatic address setting has not
been completed.
●Inter-unit control wiring is cut or is
not connected correctly.
●Remote controller is not connected
with indoor unit correctly.
●Same at left ●Same at left Check the remote controller and inter-
unit control wiring.
Perform automatic address setting (See
9-8-4).
E02 displayed
●Remote controller is not connected
correctly (failure in transmission from
remote controller to indoor unit).
●Remote controller is not connected
with indoor unit correctly.
●Same at left ●Same at left Connect the remote controller correctly.
E09 displayed —————— —————— ——————
●2 remote
controllers are
set as the main
remote controller.
Refer to 9-8-6 Main-sub remote
Control, and make the correct settings.
E14 displayed —————— ——————
●Remote controller crossover wiring
is cut or is not connected correctly.
●Same at left Check the remote controller crossover
wiring.
Perform automatic address setting
again.
E04 displayed
Standby lamp is
blinking.
●Indoor-outdoor inter-unit wiring is not
connected correctly.
●Same at left ●Same at left ●Same at left Connect the wiring correctly.
E06 displayed ●Indoor-outdoor inter-unit wiring is
cut or is not connected correctly.
●Same at left ●Same at left Refer to 9-8 System Control, and make
the correct settings.
E15 displayed ●Indoor unit capacity is too low. ●Same at left ●Same at left ●Same at left Check that the total capacities of
the indoor and outdoor units are
appropriate.
E16 displayed ●Indoor unit capacity is too high.
E20 displayed
●No serial signal is being received at all
from the indoor units. Check that the indoor unit power is ON,
and that the inter-unit control wiring is
connected correctly.
P05 displayed
Operation lamp
and Standby
lamp are blinking
alternately.
●Reversed phase in the outdoor unit
single-phase or open phase in the
outdoor unit 3-phase power.
●Insufficient gas
●Reversed phase in the outdoor
unit single phase or open phase
in the 3-phase power at one of the
outdoor units in the group.
●Reversed phase in the outdoor unit
single-phase or open phase in the
outdoor unit 3-phase power.
●CT sensor is disconnected or there
is a problem with the circuit.
●Same at left Reverse 2 phases of the outdoor unit
3-phase power and connect them
correctly.
Check that the CT sensor is not
disconnected, and make sure it is
inserted.
Fill up the gas appropriately.
L02 displayed
L13 displayed Both the
Operation lamp
and Standby
lamp are blinking
together.
●Indoor-outdoor unit type mismatch. ●Same at left ●Same at left —————— Check that the indoor and outdoor unit
types are correct.
L07 displayed —————— ——————
●Remote controller crossover wiring
is connected to the indoor unit,
however it is set for individual
operation.
●Same at left Perform automatic address setting (See
9-8).
P09 displayed Timer lamp and
Standby lamp are
blinking
alternately.
●The indoor unit ceiling panel connector
is not connected correctly.
●Ceiling panel connector at one of
the indoor units in the group is not
connected correctly.
●Indoor unit ceiling panel connector
is not connected correctly.
●Same at left Connect the indoor unit ceiling panel
connector correctly.
P12 displayed
●Indoor unit DC fan trouble. ●DC fan trouble at one of the indoor
units in the group.
●Indoor unit fan trouble. ●Same at left Check whether the fan holder is loose.
Check the wiring between the DC fan
and the PCB.
P15 displayed
Operation lamp
and Standby
lamp are blinking
alternately.
●No gas ●Same at left ●Same at left
——————
Check the refrigerant cycle (for gas
leaks).