EnglishDeutsch
 logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. pass & seymour
  6. •
  7. Accessories
  8. •
  9. pass & seymour WSP-250 User manual

pass & seymour WSP-250 User manual

Other manuals for WSP-250

1

Other pass & seymour Accessories manuals

pass & seymour RWU600B User manual

pass & seymour

pass & seymour RWU600B User manual

pass & seymour CS500 User manual

pass & seymour

pass & seymour CS500 User manual

pass & seymour CSU Series User manual

pass & seymour

pass & seymour CSU Series User manual

Popular Accessories manuals by other brands

Hillco 2810 Operator's manual

Hillco

Hillco 2810 Operator's manual

Siemens QSA2700D Basic documentation

Siemens

Siemens QSA2700D Basic documentation

Contours ZY024 manual

Contours

Contours ZY024 manual

Saivod VS621 manual

Saivod

Saivod VS621 manual

SCE ENVIRO-THERM SCE-TE170B24VSS user manual

SCE

SCE ENVIRO-THERM SCE-TE170B24VSS user manual

Z-Wave HSD-200Z user manual

Z-Wave

Z-Wave HSD-200Z user manual

turck FMX-IM-2UPLI63FX quick start guide

turck

turck FMX-IM-2UPLI63FX quick start guide

Decagon Devices 10HS manual

Decagon Devices

Decagon Devices 10HS manual

UPPAbaby Cup Holder user manual

UPPAbaby

UPPAbaby Cup Holder user manual

Elko SmartSensor Leakage Wireless manual

Elko

Elko SmartSensor Leakage Wireless manual

Grizzly H8371 instructions

Grizzly

Grizzly H8371 instructions

Panasonic HG-T Series user manual

Panasonic

Panasonic HG-T Series user manual

IFM Electronic Efector 250 Series Brief instructions

IFM Electronic

IFM Electronic Efector 250 Series Brief instructions

Virtuox VirtuCLEAN 2.0 user manual

Virtuox

Virtuox VirtuCLEAN 2.0 user manual

DigiDesign 888/24 I/O installation guide

DigiDesign

DigiDesign 888/24 I/O installation guide

PROZIS QUAY user manual

PROZIS

PROZIS QUAY user manual

patagonia PSI Vest user manual

patagonia

patagonia PSI Vest user manual

SFC Energy EFOY GO! manual

SFC Energy

SFC Energy EFOY GO! manual

https://manuals.online logo
https://manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2026 Manuals.Online. All Rights Reserved.

TROUBLESHOOTING
Load will not turn on:
• LEDdoesnotash:
 ‑Checkthesensitivityforproperconguration.
‑Checkallwireconnections.Verifythegroundwireistightlysecured.
• LEDdoesash:
 ‑PresstheON/OFFbutton.Ifloaddoesnotturnon,checkallwire
connectionsandverifytheloadwireistightlysecured.
 ‑Checkthelightleveltrimpot.Turnitfullyclockwise
• Ifloadstilldoesnotturnon,call800.223.4185fortechnicalsupport.
Load will not turn off:
• Thetimedelaycanbesetfor30seconds
(WalkTest),5,10,15,20,25,or30minutes.
Ensurethatthetimedelayissettothe
desireddelayandthatthereisnomovement
withinthesensor’sviewforthattimeperiod.
• Toquicklytesttheunitforproperoperation,
turnthetimedelaytominimum(fully
counterclockwise)andmoveoutofthe
sensor’sview.Loadshouldturnoffafter
30seconds.
• Ifloadstilldoesnotturnoff,call
800.223.4185fortechnicalsupport.
Sensing motion outside desired area:
• Opaqueadhesivetapeisincludedwiththe
sensorandcanbeusedtolimitthedetectionareas.SeeMaskingtheLens.
• Adjustsensitivitycounterclockwisetoreduceexcessivesensitivity.
WSP-250
Passive Infrared Wall Switch
Occupancy Sensor
SPECIFICATIONS
WSP-250 Voltages................................................. 120or277VAC,60Hz
   LoadRequirements
    @120VAC,60Hz............. 0‑800Wballast&tungsten,1/6hp
    @277VAC,60Hz........................................... 0‑1200Wballast
TimeDelayAdjustment...................................30seconds‑30minutes
 SensitivityAdjustment...........................................Minimum‑Maximum
 LightLevelAdjustment..................................................... 10‑200+FC
SENSOR ADJUSTMENT
DO NOT OVERTURN TRIMPOTS WHEN ADJUSTING THE SENSOR!
1. Totestunitoperation,presstheON/OFFbuttontoturntheloadon.
2. Removethebuttoncovertoaccesstheadjustmentcontrols.Useasmall,
atbladescrewdrivertopressdownthelockingtabatthetopofthebutton,
thengentlypryitoff.
a)Setthetimedelaytothe“walktest”position(fullycounterclockwise).
b)Leavetheroom.Theloadshouldgooffafter30seconds.
3. Totestsensitivity:
a) Makenomotionfor3seconds.
b) Waveyourhandsidewaysinfrontofthesensoratadistanceof
approximately12".TheLEDblinkswhenmovementisdetected.
Typically,thesensitivityshouldbeatmaximum(fullyclockwise).
4. Setthelightlevelwhenthecontrolledlightwouldnormallybeturnedoff
duetothepresenceofsufcientdaylightorotherelectriclight.[Ifthis
featureisnotneeded,leavethelightlevelatmaximum(fullyclockwise)].
a) SettheTimeDelaytoatleast5minutes.Thistakesthesensoroutof
Walk‑testmode,andenablesthelightlevelfeature.
b) SettheLightlevelto50%(12o’clockposition)whichisapproximately
100fc.Letthesensortimeoutsolightsareoff.Enterthespaceand
lightsshouldremainoff.
c) Makesureyourbodydoesnotcastashadowonthesensor,andadjust
thelightleveltrimpotclockwiseinsmallincrements.
d) Aftereachadjustment,wait5‑10secondstoseeifthelightsturnon.
Repeatuntilthelightsturnon.Atthissettingtheloadconnectedtothe
sensorwillnotturnoniflightlevelsareabovethecurrentillumination.
Note: Userscanoverridethisfunctionbyplacingtheirhandinfrontofthe
sensortoblockincominglight.Theloadwillthenremainonuntilthe
spaceisunoccupiedorthelightlevelrisesabovethesetpointandthe
timedelayexpires.
5. Resetthetimedelaytothe
desiredsetting.Thetimedelay
canbesetfrom30seconds
(seeWalk‑testfeature,light
levelfeatureisdisabled)
to30minutesin5‑minute
increments.
Call 800.223.4185 for Technical Support
WARRANTY INFORMATION
Pass&Seymour/Legrandwarrantiesitsproductstobefreeofdefects
inmaterialsandworkmanshipforaperiodofve(5)years.Thereare
noobligationsorliabilitiesonthepartofPass&Seymour/Legrandfor
consequentialdamagesarisingoutof,orinconnectionwith,theuseor
performanceofthisproductorotherindirectdamageswithrespecttolossof
property,revenueorprot,orcostofremoval,installationorreinstallation.
Installation Instructions
P.O.Box4822,Syracuse,NY13221‑4822
TechnicalSupport:800.223.4185
www.passandseymour.com
34088611343
Please
Recycle
Visit our website: www.passandseymour.com
Sensitivity (S)
shown as set
for Maximum
Light Level (L)
shown as set
for Maximum (+)
to disable
Time Delay (T)
Shown as set for
15 minutes
Time Delay (T)
Shown as set for
15 minutes
30 seconds
(Walk-test)
5 minutes
10 minutes 20 minutes
25 minutes
30 minutes
LTS
WSP250 IS_340886 11343.indd 1-4 3/30/09 9:19:49 AM
UNIT DESCRIPTION AND OPERATION
TheWSP‑250WallSwitchOccupancySensorsturnlightingorfanloadsonand
offbasedonoccupancyandambientlightlevel.Theyaredesignedtoreplacea
standardlightswitch.TheWSP‑250operateswith120or277VAClinevoltage.
Thesensorusespassiveinfraredtechnologytosensehumanmotion,and
definesitasoccupancy.AgreenLEDonthesensorblinksuponoccupancyand
thenresets.Itwillblinkagainwhenitdetectsmotionafterthe2‑secondreset.
Thesensorturnsontheloadautomaticallywhenitdetectsoccupancy.Oncethe
spaceisvacantandthetimedelayelapses,itturnsofftheloadautomatically.
Ifadequateambientlightisalreadypresentinthearea,thesensorwillhold
offtheloaditcontrols.Whenthelightdropsbelowafieldselectableleveland
thesensordetectsoccupancy,thesensorturnsontheload.Onceturnedon,
theloadremainsonuntilthespaceisvacantorthelightlevelrisesabovethe
setpointandthetimedelayexpires.
Manual Operation: TheoccupantcanpresstheON/OFFbuttontoturntheload
onandoff.Whentheloadisturnedofforonmanually,itstaysofforonaslong
asthesensordetectsmotion.Afternomotionisdetectedforthelengthofthe
timedelay,thesensorgoesbacktoautomaticoperation.Iftheloadwason,it
turnsoff.Thenexttimethesensordetectsoccupancyandtheambientlightis
lowerthanthesetlevel,thesensorautomaticallyturnsontheload.
Walk-test feature:
WhentheTimeDelaytrimpot
isinthefullycounterclockwise
position,thesensorhasa30
secondtimedelayandtheLight
Levelfunctionisdisabled.This
allowsyoutoquicklycheckthe
sensorcoveragearea.
Override function:
Intheeventofunitfailureor
ifitisnecessarytoleavethe
loadon,removetheOverride
Jumperplug.Thisdisablesall
automaticonandofffunctions
andtheloadcanonlybe
operatedusingtheON/OFF
button.
COVERAGE PATTERNS
TheWSP‑250detectsmotioninareasupto900sq.ft.andupto35feetfrom
thesensor.Ideally,thesensorisdesignedforsmallamountsofmotionin
spacesupto300sq.ft.TheFresnellensonthesensorisamultiplesegment
viewinglenswithafieldofviewof180°.
Thesensormusthavea
clearviewofthepeoplein
thespaceinordertodetect
occupancy.Obstructions,
suchasfurnitureblocking
thesensor’slens,may
preventoccupancy
detection.
15'
(4.6m)
35'
(10.7m)
4.0'
(1.2m)
35'
(10.7m)
floor
Masking the lens
Opaqueadhesivetapeissuppliedsothat
sectionsofthesensor’sviewcanbemasked.
Thisallowsyoutoeliminatecoveragein
unwantedareas.
Sincemaskingremovesbandsofcoverage,
remembertotakethisintoaccountwhen
troubleshootingcoverageproblems.
1. Connecttheexistingwiresinthewallboxtothesensorflyingleads.
(SeeWiringDirectionsatright).
 • Donotallowbarewiretoshowbelowconnector.
 • Thegroundwiremustbetightly grounded fortheunittooperate
properly.
2. Attachthesensortothewallbymountingitinthewallboxwiththetwo
mountingscrewsprovided.
3. Turnonpoweratthecircuitbreaker.
There is an initial warm-up period after installation.Itmaytakeuptoa
minutebeforetheloadturnsonduetoasensorwarm‑upperiodduring
initialpower‑up(thisoccursduringinstallationonly).Theloadturnsonafter
thewarm‑upperiodendsifthesensordetectsmotion.
Rapid successive pressing of the ON/OFF button causes a delay in function.
Asinglepressofthebuttoncausesanimmediateresponse.Ifthebutton
ispressedagainwithin2seconds,theswitchignoresit.Waitatleasttwo
secondsbetweenbuttonpresses.
4. TestthesensorusingtheprocedureintheSensorAdjustmentssection.
5. Replacewallswitchcoverplate.
CAUTION
Turn the power off at the circuit breaker before installing the sensor.
INSTALLATION
Cover plate
WSP-250
Wall Switch
Wall
Junction Box
Load
Red Black to Line
Green
Neutral
Single-level wiring
WIRING DIRECTIONS
Fornormalinstallationofthe
WSP‑250connect:
1. LOADtoRedflyinglead.
2. LINEtoBlackflyinglead.
3. GROUNDtoGreen.
Call 800.223.4185 for Technical Support Call 800.223.4185 for Technical Support
Manual bi-level lighting wiring
Load
Load
Green
Red Black to Line
Neutral
Visit our website: www.passandseymour.com Visit our website: www.passandseymour.com
ON/OFF
Switch
Override
Jumper
Light Level
Time Delay
Sensitivity
LED
Fresnel Lens
ON/OFF Button
(Switch Cover)
Press down
on tab and
pry off Cover
(L)
(T)
(S)
Maximum = clockwise
Minimum = counterclockwise
Side View
Top View
Opaque tape
WSP250 IS_340886 11343.indd 5-8 3/30/09 9:19:52 AM