TROUBLESHOOTING
Load will not turn on:
• LEDdoesnotash:
 ‑Checkthesensitivityforproperconguration.
‑Checkallwireconnections.Verifythegroundwireistightlysecured.
• LEDdoesash:
 ‑PresstheON/OFFbutton.Ifloaddoesnotturnon,checkallwire
connectionsandverifytheloadwireistightlysecured.
 ‑Checkthelightleveltrimpot.Turnitfullyclockwise
• Ifloadstilldoesnotturnon,call800.223.4185fortechnicalsupport.
Load will not turn off:
• Thetimedelaycanbesetfor30seconds
(WalkTest),5,10,15,20,25,or30minutes.
Ensurethatthetimedelayissettothe
desireddelayandthatthereisnomovement
withinthesensor’sviewforthattimeperiod.
• Toquicklytesttheunitforproperoperation,
turnthetimedelaytominimum(fully
counterclockwise)andmoveoutofthe
sensor’sview.Loadshouldturnoffafter
30seconds.
• Ifloadstilldoesnotturnoff,call
800.223.4185fortechnicalsupport.
Sensing motion outside desired area:
• Opaqueadhesivetapeisincludedwiththe
sensorandcanbeusedtolimitthedetectionareas.SeeMaskingtheLens.
• Adjustsensitivitycounterclockwisetoreduceexcessivesensitivity.
WSP-250
Passive Infrared Wall Switch
Occupancy Sensor
SPECIFICATIONS
WSP-250 Voltages................................................. 120or277VAC,60Hz
   LoadRequirements
    @120VAC,60Hz............. 0‑800Wballast&tungsten,1/6hp
    @277VAC,60Hz........................................... 0‑1200Wballast
TimeDelayAdjustment...................................30seconds‑30minutes
 SensitivityAdjustment...........................................Minimum‑Maximum
 LightLevelAdjustment..................................................... 10‑200+FC
SENSOR ADJUSTMENT
DO NOT OVERTURN TRIMPOTS WHEN ADJUSTING THE SENSOR!
1. Totestunitoperation,presstheON/OFFbuttontoturntheloadon.
2. Removethebuttoncovertoaccesstheadjustmentcontrols.Useasmall,
atbladescrewdrivertopressdownthelockingtabatthetopofthebutton,
thengentlypryitoff.
a)Setthetimedelaytothe“walktest”position(fullycounterclockwise).
b)Leavetheroom.Theloadshouldgooffafter30seconds.
3. Totestsensitivity:
a) Makenomotionfor3seconds.
b) Waveyourhandsidewaysinfrontofthesensoratadistanceof
approximately12".TheLEDblinkswhenmovementisdetected.
Typically,thesensitivityshouldbeatmaximum(fullyclockwise).
4. Setthelightlevelwhenthecontrolledlightwouldnormallybeturnedoff
duetothepresenceofsufcientdaylightorotherelectriclight.[Ifthis
featureisnotneeded,leavethelightlevelatmaximum(fullyclockwise)].
a) SettheTimeDelaytoatleast5minutes.Thistakesthesensoroutof
Walk‑testmode,andenablesthelightlevelfeature.
b) SettheLightlevelto50%(12o’clockposition)whichisapproximately
100fc.Letthesensortimeoutsolightsareoff.Enterthespaceand
lightsshouldremainoff.
c) Makesureyourbodydoesnotcastashadowonthesensor,andadjust
thelightleveltrimpotclockwiseinsmallincrements.
d) Aftereachadjustment,wait5‑10secondstoseeifthelightsturnon.
Repeatuntilthelightsturnon.Atthissettingtheloadconnectedtothe
sensorwillnotturnoniflightlevelsareabovethecurrentillumination.
Note: Userscanoverridethisfunctionbyplacingtheirhandinfrontofthe
sensortoblockincominglight.Theloadwillthenremainonuntilthe
spaceisunoccupiedorthelightlevelrisesabovethesetpointandthe
timedelayexpires.
5. Resetthetimedelaytothe
desiredsetting.Thetimedelay
canbesetfrom30seconds
(seeWalk‑testfeature,light
levelfeatureisdisabled)
to30minutesin5‑minute
increments.
Call 800.223.4185 for Technical Support
WARRANTY INFORMATION
Pass&Seymour/Legrandwarrantiesitsproductstobefreeofdefects
inmaterialsandworkmanshipforaperiodofve(5)years.Thereare
noobligationsorliabilitiesonthepartofPass&Seymour/Legrandfor
consequentialdamagesarisingoutof,orinconnectionwith,theuseor
performanceofthisproductorotherindirectdamageswithrespecttolossof
property,revenueorprot,orcostofremoval,installationorreinstallation.
Installation Instructions
P.O.Box4822,Syracuse,NY13221‑4822
TechnicalSupport:800.223.4185
www.passandseymour.com
34088611343
Please
Recycle
Visit our website: www.passandseymour.com
Sensitivity (S)
shown as set
for Maximum
Light Level (L)
shown as set
for Maximum (+)
to disable
Time Delay (T)
Shown as set for
15 minutes
Time Delay (T)
Shown as set for
15 minutes
30 seconds
(Walk-test)
5 minutes
10 minutes 20 minutes
25 minutes
30 minutes
LTS
WSP250 IS_340886 11343.indd 1-4 3/30/09 9:19:49 AM
UNIT DESCRIPTION AND OPERATION
TheWSP‑250WallSwitchOccupancySensorsturnlightingorfanloadsonand
offbasedonoccupancyandambientlightlevel.Theyaredesignedtoreplacea
standardlightswitch.TheWSP‑250operateswith120or277VAClinevoltage.
Thesensorusespassiveinfraredtechnologytosensehumanmotion,and
definesitasoccupancy.AgreenLEDonthesensorblinksuponoccupancyand
thenresets.Itwillblinkagainwhenitdetectsmotionafterthe2‑secondreset.
Thesensorturnsontheloadautomaticallywhenitdetectsoccupancy.Oncethe
spaceisvacantandthetimedelayelapses,itturnsofftheloadautomatically.
Ifadequateambientlightisalreadypresentinthearea,thesensorwillhold
offtheloaditcontrols.Whenthelightdropsbelowafieldselectableleveland
thesensordetectsoccupancy,thesensorturnsontheload.Onceturnedon,
theloadremainsonuntilthespaceisvacantorthelightlevelrisesabovethe
setpointandthetimedelayexpires.
Manual Operation: TheoccupantcanpresstheON/OFFbuttontoturntheload
onandoff.Whentheloadisturnedofforonmanually,itstaysofforonaslong
asthesensordetectsmotion.Afternomotionisdetectedforthelengthofthe
timedelay,thesensorgoesbacktoautomaticoperation.Iftheloadwason,it
turnsoff.Thenexttimethesensordetectsoccupancyandtheambientlightis
lowerthanthesetlevel,thesensorautomaticallyturnsontheload.
Walk-test feature:
WhentheTimeDelaytrimpot
isinthefullycounterclockwise
position,thesensorhasa30
secondtimedelayandtheLight
Levelfunctionisdisabled.This
allowsyoutoquicklycheckthe
sensorcoveragearea.
Override function:
Intheeventofunitfailureor
ifitisnecessarytoleavethe
loadon,removetheOverride
Jumperplug.Thisdisablesall
automaticonandofffunctions
andtheloadcanonlybe
operatedusingtheON/OFF
button.
COVERAGE PATTERNS
TheWSP‑250detectsmotioninareasupto900sq.ft.andupto35feetfrom
thesensor.Ideally,thesensorisdesignedforsmallamountsofmotionin
spacesupto300sq.ft.TheFresnellensonthesensorisamultiplesegment
viewinglenswithafieldofviewof180°.
Thesensormusthavea
clearviewofthepeoplein
thespaceinordertodetect
occupancy.Obstructions,
suchasfurnitureblocking
thesensor’slens,may
preventoccupancy
detection.
15'
(4.6m)
35'
(10.7m)
4.0'
(1.2m)
35'
(10.7m)
floor
Masking the lens
Opaqueadhesivetapeissuppliedsothat
sectionsofthesensor’sviewcanbemasked.
Thisallowsyoutoeliminatecoveragein
unwantedareas.
Sincemaskingremovesbandsofcoverage,
remembertotakethisintoaccountwhen
troubleshootingcoverageproblems.
1. Connecttheexistingwiresinthewallboxtothesensorflyingleads.
(SeeWiringDirectionsatright).
 • Donotallowbarewiretoshowbelowconnector.
 • Thegroundwiremustbetightly grounded fortheunittooperate
properly.
2. Attachthesensortothewallbymountingitinthewallboxwiththetwo
mountingscrewsprovided.
3. Turnonpoweratthecircuitbreaker.
There is an initial warm-up period after installation.Itmaytakeuptoa
minutebeforetheloadturnsonduetoasensorwarm‑upperiodduring
initialpower‑up(thisoccursduringinstallationonly).Theloadturnsonafter
thewarm‑upperiodendsifthesensordetectsmotion.
Rapid successive pressing of the ON/OFF button causes a delay in function.
Asinglepressofthebuttoncausesanimmediateresponse.Ifthebutton
ispressedagainwithin2seconds,theswitchignoresit.Waitatleasttwo
secondsbetweenbuttonpresses.
4. TestthesensorusingtheprocedureintheSensorAdjustmentssection.
5. Replacewallswitchcoverplate.
CAUTION
Turn the power off at the circuit breaker before installing the sensor.
INSTALLATION
Cover plate
WSP-250
Wall Switch
Wall
Junction Box
Load
Red Black to Line
Green
Neutral
Single-level wiring
WIRING DIRECTIONS
Fornormalinstallationofthe
WSP‑250connect:
1. LOADtoRedflyinglead.
2. LINEtoBlackflyinglead.
3. GROUNDtoGreen.
Call 800.223.4185 for Technical Support Call 800.223.4185 for Technical Support
Manual bi-level lighting wiring
Load
Load
Green
Red Black to Line
Neutral
Visit our website: www.passandseymour.com Visit our website: www.passandseymour.com
ON/OFF
Switch
Override
Jumper
Light Level
Time Delay
Sensitivity
LED
Fresnel Lens
ON/OFF Button
(Switch Cover)
Press down
on tab and
pry off Cover
(L)
(T)
(S)
Maximum = clockwise
Minimum = counterclockwise
Side View
Top View
Opaque tape
WSP250 IS_340886 11343.indd 5-8 3/30/09 9:19:52 AM

Other manuals for WSP-250

1

Other pass & seymour Accessories manuals

pass & seymour CS500 User manual

pass & seymour

pass & seymour CS500 User manual

pass & seymour CSU Series User manual

pass & seymour

pass & seymour CSU Series User manual

pass & seymour RWU600B User manual

pass & seymour

pass & seymour RWU600B User manual

Popular Accessories manuals by other brands

TUYA laxihub 6972055684105 user manual

TUYA

TUYA laxihub 6972055684105 user manual

Rohde & Schwarz R&S RT-ZC10B user manual

Rohde & Schwarz

Rohde & Schwarz R&S RT-ZC10B user manual

Hubbell KILLARK ACCEPTOR UGR Series INSTALLATION, OPERATION & MAINTENANCE DATA SHEET

Hubbell

Hubbell KILLARK ACCEPTOR UGR Series INSTALLATION, OPERATION & MAINTENANCE DATA SHEET

Sonoff DW2-RF user manual

Sonoff

Sonoff DW2-RF user manual

Dini Argeo WLB-KSD user manual

Dini Argeo

Dini Argeo WLB-KSD user manual

Philips HR 2577 user manual

Philips

Philips HR 2577 user manual

Girard Systems G-Link G-2000 Owners Operation, Adjustment, Repair & Installation Manual

Girard Systems

Girard Systems G-Link G-2000 Owners Operation, Adjustment, Repair & Installation Manual

Wimberley CK-200 instructions

Wimberley

Wimberley CK-200 instructions

EluneVision Luna user manual

EluneVision

EluneVision Luna user manual

Larson Electronics SLEDB-277V-30C-XMS manual

Larson Electronics

Larson Electronics SLEDB-277V-30C-XMS manual

Lucci CONNECT 299042 installation instructions

Lucci CONNECT

Lucci CONNECT 299042 installation instructions

Chariot Multi-Functional Handlebar Console Instruction

Chariot

Chariot Multi-Functional Handlebar Console Instruction

SICK LMS1 Series operating instructions

SICK

SICK LMS1 Series operating instructions

PS Audio PerfectWave DAC Mk II Upgrade kit

PS Audio

PS Audio PerfectWave DAC Mk II Upgrade kit

Everbilt DF4WHD Use and care guide

Everbilt

Everbilt DF4WHD Use and care guide

Baumer OADM 20U2472/S14C manual

Baumer

Baumer OADM 20U2472/S14C manual

B+B Sensors DS18S20 Operation manual

B+B Sensors

B+B Sensors DS18S20 Operation manual

Markilux 710 manual

Markilux

Markilux 710 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.