manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. pass & seymour
  6. •
  7. Accessories
  8. •
  9. pass & seymour WSP-250 User manual

pass & seymour WSP-250 User manual

Other manuals for WSP-250

1

Other pass & seymour Accessories manuals

pass & seymour CSU Series User manual

pass & seymour

pass & seymour CSU Series User manual

pass & seymour RWU600B User manual

pass & seymour

pass & seymour RWU600B User manual

pass & seymour CS500 User manual

pass & seymour

pass & seymour CS500 User manual

Popular Accessories manuals by other brands

Quincy lab 140AE-1 operating manual

Quincy lab

Quincy lab 140AE-1 operating manual

HomePro ZIR000 user manual

HomePro

HomePro ZIR000 user manual

DOL 20SCR Technical user guide

DOL

DOL 20SCR Technical user guide

RAB Smart Task installation manual

RAB

RAB Smart Task installation manual

Kemppi KMS 300 quick guide

Kemppi

Kemppi KMS 300 quick guide

Stearns 57,500 Series Installation and service instructions

Stearns

Stearns 57,500 Series Installation and service instructions

iGuzzini TWILIGHT COPENAGHEN manual

iGuzzini

iGuzzini TWILIGHT COPENAGHEN manual

Adelaide Annexe & Canvas Avan Deluxe installation guide

Adelaide Annexe & Canvas

Adelaide Annexe & Canvas Avan Deluxe installation guide

OHAUS 5000 instruction manual

OHAUS

OHAUS 5000 instruction manual

HOME8 WLS1300 quick start guide

HOME8

HOME8 WLS1300 quick start guide

MAXBOTIX MaxSonar quick start guide

MAXBOTIX

MAXBOTIX MaxSonar quick start guide

ioSmart iSmart56 Installation and user guide

ioSmart

ioSmart iSmart56 Installation and user guide

Focusrite Scarlett 18i8 user guide

Focusrite

Focusrite Scarlett 18i8 user guide

Velleman ED38105 user manual

Velleman

Velleman ED38105 user manual

JumpSport SkyBounce user manual

JumpSport

JumpSport SkyBounce user manual

Prima-Temp PRIYA Instructions for use

Prima-Temp

Prima-Temp PRIYA Instructions for use

Tefcold BC85I-BC85I W user manual

Tefcold

Tefcold BC85I-BC85I W user manual

Vaisala WMS302 user guide

Vaisala

Vaisala WMS302 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

TROUBLESHOOTING
Load will not turn on:
• LEDdoesnotash:
 ‑Checkthesensitivityforproperconguration.
‑Checkallwireconnections.Verifythegroundwireistightlysecured.
• LEDdoesash:
 ‑PresstheON/OFFbutton.Ifloaddoesnotturnon,checkallwire
connectionsandverifytheloadwireistightlysecured.
 ‑Checkthelightleveltrimpot.Turnitfullyclockwise
• Ifloadstilldoesnotturnon,call800.223.4185fortechnicalsupport.
Load will not turn off:
• Thetimedelaycanbesetfor30seconds
(WalkTest),5,10,15,20,25,or30minutes.
Ensurethatthetimedelayissettothe
desireddelayandthatthereisnomovement
withinthesensor’sviewforthattimeperiod.
• Toquicklytesttheunitforproperoperation,
turnthetimedelaytominimum(fully
counterclockwise)andmoveoutofthe
sensor’sview.Loadshouldturnoffafter
30seconds.
• Ifloadstilldoesnotturnoff,call
800.223.4185fortechnicalsupport.
Sensing motion outside desired area:
• Opaqueadhesivetapeisincludedwiththe
sensorandcanbeusedtolimitthedetectionareas.SeeMaskingtheLens.
• Adjustsensitivitycounterclockwisetoreduceexcessivesensitivity.
WSP-250
Passive Infrared Wall Switch
Occupancy Sensor
SPECIFICATIONS
WSP-250 Voltages................................................. 120or277VAC,60Hz
   LoadRequirements
    @120VAC,60Hz............. 0‑800Wballast&tungsten,1/6hp
    @277VAC,60Hz........................................... 0‑1200Wballast
TimeDelayAdjustment...................................30seconds‑30minutes
 SensitivityAdjustment...........................................Minimum‑Maximum
 LightLevelAdjustment..................................................... 10‑200+FC
SENSOR ADJUSTMENT
DO NOT OVERTURN TRIMPOTS WHEN ADJUSTING THE SENSOR!
1. Totestunitoperation,presstheON/OFFbuttontoturntheloadon.
2. Removethebuttoncovertoaccesstheadjustmentcontrols.Useasmall,
atbladescrewdrivertopressdownthelockingtabatthetopofthebutton,
thengentlypryitoff.
a)Setthetimedelaytothe“walktest”position(fullycounterclockwise).
b)Leavetheroom.Theloadshouldgooffafter30seconds.
3. Totestsensitivity:
a) Makenomotionfor3seconds.
b) Waveyourhandsidewaysinfrontofthesensoratadistanceof
approximately12".TheLEDblinkswhenmovementisdetected.
Typically,thesensitivityshouldbeatmaximum(fullyclockwise).
4. Setthelightlevelwhenthecontrolledlightwouldnormallybeturnedoff
duetothepresenceofsufcientdaylightorotherelectriclight.[Ifthis
featureisnotneeded,leavethelightlevelatmaximum(fullyclockwise)].
a) SettheTimeDelaytoatleast5minutes.Thistakesthesensoroutof
Walk‑testmode,andenablesthelightlevelfeature.
b) SettheLightlevelto50%(12o’clockposition)whichisapproximately
100fc.Letthesensortimeoutsolightsareoff.Enterthespaceand
lightsshouldremainoff.
c) Makesureyourbodydoesnotcastashadowonthesensor,andadjust
thelightleveltrimpotclockwiseinsmallincrements.
d) Aftereachadjustment,wait5‑10secondstoseeifthelightsturnon.
Repeatuntilthelightsturnon.Atthissettingtheloadconnectedtothe
sensorwillnotturnoniflightlevelsareabovethecurrentillumination.
Note: Userscanoverridethisfunctionbyplacingtheirhandinfrontofthe
sensortoblockincominglight.Theloadwillthenremainonuntilthe
spaceisunoccupiedorthelightlevelrisesabovethesetpointandthe
timedelayexpires.
5. Resetthetimedelaytothe
desiredsetting.Thetimedelay
canbesetfrom30seconds
(seeWalk‑testfeature,light
levelfeatureisdisabled)
to30minutesin5‑minute
increments.
Call 800.223.4185 for Technical Support
WARRANTY INFORMATION
Pass&Seymour/Legrandwarrantiesitsproductstobefreeofdefects
inmaterialsandworkmanshipforaperiodofve(5)years.Thereare
noobligationsorliabilitiesonthepartofPass&Seymour/Legrandfor
consequentialdamagesarisingoutof,orinconnectionwith,theuseor
performanceofthisproductorotherindirectdamageswithrespecttolossof
property,revenueorprot,orcostofremoval,installationorreinstallation.
Installation Instructions
P.O.Box4822,Syracuse,NY13221‑4822
TechnicalSupport:800.223.4185
www.passandseymour.com
34088611343
Please
Recycle
Visit our website: www.passandseymour.com
Sensitivity (S)
shown as set
for Maximum
Light Level (L)
shown as set
for Maximum (+)
to disable
Time Delay (T)
Shown as set for
15 minutes
Time Delay (T)
Shown as set for
15 minutes
30 seconds
(Walk-test)
5 minutes
10 minutes 20 minutes
25 minutes
30 minutes
LTS
WSP250 IS_340886 11343.indd 1-4 3/30/09 9:19:49 AM
UNIT DESCRIPTION AND OPERATION
TheWSP‑250WallSwitchOccupancySensorsturnlightingorfanloadsonand
offbasedonoccupancyandambientlightlevel.Theyaredesignedtoreplacea
standardlightswitch.TheWSP‑250operateswith120or277VAClinevoltage.
Thesensorusespassiveinfraredtechnologytosensehumanmotion,and
definesitasoccupancy.AgreenLEDonthesensorblinksuponoccupancyand
thenresets.Itwillblinkagainwhenitdetectsmotionafterthe2‑secondreset.
Thesensorturnsontheloadautomaticallywhenitdetectsoccupancy.Oncethe
spaceisvacantandthetimedelayelapses,itturnsofftheloadautomatically.
Ifadequateambientlightisalreadypresentinthearea,thesensorwillhold
offtheloaditcontrols.Whenthelightdropsbelowafieldselectableleveland
thesensordetectsoccupancy,thesensorturnsontheload.Onceturnedon,
theloadremainsonuntilthespaceisvacantorthelightlevelrisesabovethe
setpointandthetimedelayexpires.
Manual Operation: TheoccupantcanpresstheON/OFFbuttontoturntheload
onandoff.Whentheloadisturnedofforonmanually,itstaysofforonaslong
asthesensordetectsmotion.Afternomotionisdetectedforthelengthofthe
timedelay,thesensorgoesbacktoautomaticoperation.Iftheloadwason,it
turnsoff.Thenexttimethesensordetectsoccupancyandtheambientlightis
lowerthanthesetlevel,thesensorautomaticallyturnsontheload.
Walk-test feature:
WhentheTimeDelaytrimpot
isinthefullycounterclockwise
position,thesensorhasa30
secondtimedelayandtheLight
Levelfunctionisdisabled.This
allowsyoutoquicklycheckthe
sensorcoveragearea.
Override function:
Intheeventofunitfailureor
ifitisnecessarytoleavethe
loadon,removetheOverride
Jumperplug.Thisdisablesall
automaticonandofffunctions
andtheloadcanonlybe
operatedusingtheON/OFF
button.
COVERAGE PATTERNS
TheWSP‑250detectsmotioninareasupto900sq.ft.andupto35feetfrom
thesensor.Ideally,thesensorisdesignedforsmallamountsofmotionin
spacesupto300sq.ft.TheFresnellensonthesensorisamultiplesegment
viewinglenswithafieldofviewof180°.
Thesensormusthavea
clearviewofthepeoplein
thespaceinordertodetect
occupancy.Obstructions,
suchasfurnitureblocking
thesensor’slens,may
preventoccupancy
detection.
15'
(4.6m)
35'
(10.7m)
4.0'
(1.2m)
35'
(10.7m)
floor
Masking the lens
Opaqueadhesivetapeissuppliedsothat
sectionsofthesensor’sviewcanbemasked.
Thisallowsyoutoeliminatecoveragein
unwantedareas.
Sincemaskingremovesbandsofcoverage,
remembertotakethisintoaccountwhen
troubleshootingcoverageproblems.
1. Connecttheexistingwiresinthewallboxtothesensorflyingleads.
(SeeWiringDirectionsatright).
 • Donotallowbarewiretoshowbelowconnector.
 • Thegroundwiremustbetightly grounded fortheunittooperate
properly.
2. Attachthesensortothewallbymountingitinthewallboxwiththetwo
mountingscrewsprovided.
3. Turnonpoweratthecircuitbreaker.
There is an initial warm-up period after installation.Itmaytakeuptoa
minutebeforetheloadturnsonduetoasensorwarm‑upperiodduring
initialpower‑up(thisoccursduringinstallationonly).Theloadturnsonafter
thewarm‑upperiodendsifthesensordetectsmotion.
Rapid successive pressing of the ON/OFF button causes a delay in function.
Asinglepressofthebuttoncausesanimmediateresponse.Ifthebutton
ispressedagainwithin2seconds,theswitchignoresit.Waitatleasttwo
secondsbetweenbuttonpresses.
4. TestthesensorusingtheprocedureintheSensorAdjustmentssection.
5. Replacewallswitchcoverplate.
CAUTION
Turn the power off at the circuit breaker before installing the sensor.
INSTALLATION
Cover plate
WSP-250
Wall Switch
Wall
Junction Box
Load
Red Black to Line
Green
Neutral
Single-level wiring
WIRING DIRECTIONS
Fornormalinstallationofthe
WSP‑250connect:
1. LOADtoRedflyinglead.
2. LINEtoBlackflyinglead.
3. GROUNDtoGreen.
Call 800.223.4185 for Technical Support Call 800.223.4185 for Technical Support
Manual bi-level lighting wiring
Load
Load
Green
Red Black to Line
Neutral
Visit our website: www.passandseymour.com Visit our website: www.passandseymour.com
ON/OFF
Switch
Override
Jumper
Light Level
Time Delay
Sensitivity
LED
Fresnel Lens
ON/OFF Button
(Switch Cover)
Press down
on tab and
pry off Cover
(L)
(T)
(S)
Maximum = clockwise
Minimum = counterclockwise
Side View
Top View
Opaque tape