Peaktronics AMI-103 User manual

PEAKTRONICS
The Peaktronics AMI-103 AC Motor Interface is
used to interface common electrical control signals to AC
actuators. The unit provides the motor drive circuits, pro-
tection circuits, and isolation between the control inputs
and motor outputs. A wide range of external control sig-
nals can be used to Open and Close the actuator. The unit
accepts commonly used 120VAC signals from PLC mod-
ules, relay circuits, triac outputs, or solid state relay cir-
cuits. Alternatively, signals from a number of electronic
sources, including TTL, CMOS, analog drivers, open col-
lector outputs, and low voltage AC outputs, can be used.
The unit has a built-in repeat cycle timer that can
be independently enabled or disabled for Open and Close.
The timer can be adjusted for 0.1 to 2 seconds "ON" time
and for 0.5 to 10 seconds "OFF" time. Since some AC
motors cannot be switched instantly from open to close
operation, the unit provides an adjustable input delay fea-
ture.
The unit can be configured for 2-wire or 3-wire
control. In 2-wire control, the control signal is applied to
the Open input to drive the actuator open. When the con-
trol signal is removed, or driven to 0V, the actuator will
automatically close. In 3-wire control, both control sig-
nals (Open and Close) are used to drive the actuator to-
ward open or closed as desired. When both signals are
removed, or driven to 0V, the actuator remains at its last
position.
The unit also features a red LED indicator (for the
open output), a green LED indicator (for the closed out-
put), an on-board fuse, two removable screw terminal
strips (for easy servicing), and on-board switches to man-
ually open or close the actuator. An auxiliary +24VDC
power output (that is isolated from the motor and control
signals) can be used to power a 4-20mA or 0-5 / 10V
AMI-103
AC Motor Interface
AMI-103
AMI-103A
AMI-103B
1
23123456789101
1
transmitter. A transmitter (such as the Peaktronics XMA-
105 or XMA-106) can be used to provide a position feed-
back signal from a feedback potentiometer (such as the
Peaktronics POT-102).
The unit comes with standoff mounts and includes
an insulating sheet that allows the unit to be mounted di-
rectly to the actuator housing or bracket. The unit is rated
for 5A at 60°C when properly mounted to a metal bracket
or metal actuator housing. The AMI-103 is rated for
117VAC ±10%, the AMI-103A is rated for 234VAC
±10%, and the AMI-103B is rated for 24VAC ±10%.
FEATURES
•On/Off Controller for 24VAC, 117VAC, or 234VAC actuators.
•Accepts wide range of AC or DC control signals.
•Accepts open collector control signal for easy interface to common bus modules.
•On-board switches for manual control.
•Configurable for 2-wire control (Open input only) or 3wire control (Open/Close inputs).
•On-board +24VDC output to power feedback transmitter and/or open collector inputs.
•Built-in repeat cycle timer for open, close, or both.
•Control inputs, motor outputs, and +24VDC output are electrically isolated from one
another.

AMI-103
2 PEAKTRONICS
OUTLINE
AMI-103
24VAC
117VAC 234VAC
AMI-103A AMI-103B
1
2
3
CLOSE OUTPUT
NEUTRAL
OPEN OUTPUT
to Motor J1
CLOSE (AC HI)
CLOSE COMMON
6
4
+24V OUTPUT
1
2
3
7
8
9
10
11
J2
SIGNAL GND
OPEN (DC/AC LO)
CLOSE (DC/AC LO)
OPEN (AC HI)
EARTH GND
L1 LINE
L2 NEUTRAL
to AC Power
to Feedback Transmitter
NOTE: The open output will be dis-
abled if neither JP1 or JP2 is installed.
Likewise, the close output is disabled if
neither JP3 or JP4 is installed.
ELECTRICAL CONNECTIONS
5
OPEN COMMON
Control Inputs
NOTE: Control Input connections are
isolated from the Feedback Transmitter
connections.
JP5 JUMPER PLUG
INSTALL for 3-wire control
(Open and Close inputs)
REMOVE for 2-wire control
(Open input only)
DISABLED
ENABLED JP2
JP1
ENABLED
DISABLED JP3
JP4
JUMPER
PLUG
JUMPER
PLUG
OPEN TIMER
CLOSE TIMER
DELAY OFF TIME
FUSE
12345678
123
JP1
JP3
JP2
JP4
910
3.50"
0.25" 0.25"
1.375"
1.375"
ON TIME
OPEN
CLOSE
J1 J2
11
GREEN
LED
(close)
RED
LED
(open)
1.40"
INSULATING
SHEET
JP5 #6 CLEAR HOLE
(2) PLACES
0.88"
0.88"
0.20"

AMI-103
PEAKTRONICS 3
BLOCK DIAGRAM
MOTOR
J1
J2
NOTE:
See Wiring Diagrams
for more information.
11
10
9
8
6
+24V OUTPUT
SIGNAL GND
OPEN (DC/AC LO)
CLOSE (DC/AC LO)
OPEN (AC HI)
4
3
L2 NEUTRAL
EARTH GND
L1 LINE
optional
brake
coil
LIMIT SWITCH
LIMIT SWITCH
THERMAL SWITCH
CLOSE
OPEN
CLOSE
OUTPUT
3
MOTOR
NEUTRAL
2
OPEN
OUTPUT
1
AMI-103
1
2
5
CLOSE COMMON
CLOSE (AC HI)
POWER / SIGNAL
OPEN COMMON
7
DESCRIPTION
The AMI-103 comes in three versions to accom-
modate different voltage applications. The AMI-103 is
rated for 117VAC ±10%; the AMI-103A is rated for
234VAC ±10%, and the AMI-103B is rated for 24VAC
±10%. The units come with standoff mounts for direct
mounting to a bracket (insulating sheet is included).
The AMI-103 units are rated for 5A motors when
properly mounted to a suitable metal plate or bracket. To
provide sufficient heatsinking, these units require screw
mounting through all four standoffs.
CAUTION ! These units are intended to be
mounted in an appropriate enclosure to avoid electrical
shocks. High voltages are present on the outside of the
unit when power is applied. AC power should be discon-
nected prior to any wiring of these units. A heater and
thermostat should be used where condensation may occur.

AMI-103
4 PEAKTRONICS
POWER / SIGNAL (J2)
Power is connected to pins 1, 2, and 3 as shown in
the Block Diagram. The fuse installed on the unit is rated
for maximum output current that can be safely delivered
by the AC outputs. To prevent damage to the unit, re-
placement fuses must not exceed a rating of 6.3A. Small-
er fuse sizes can be used with smaller motors - consult the
actuator manufacturer for appropriate fuse size and type.
The control signal to open the actuator is connect-
ed to either pin 7 or pin 9 (do not connect both inputs at
the same time) using pin 5 (OPEN COMMON) as the re-
turn. The close control signal is connected to either pin 6
or pin 8 (do not connect both at the same time) using pin
4 (CLOSE COMMON) as the return. The AC HI inputs
(pins 6 and 7) are suitable for 120VAC control signals,
while the DC/AC LO inputs are used for either DC elec-
tronic signals (such as TTL, CMOS, etc.) or AC control
signals up to 90VAC. Open collector control signals can
also be used - see Wiring Diagrams for details.
Pin 11 of J2 provides an auxiliary +24VDC output
which can be used to power an output transmitter. SIG-
NAL GND (pin 10) is used as the return line for the
transmitter. SIGNAL GND (pin 10), OPEN COMMON
(pin 5), and CLOSE COMMON (pin 4) are isolated from
the motor outputs on J1 as well as from each other. Pin 4
and 5 should not be connected to pin 10 when using con-
trol signals that are not isolated from the AC power line
(pins 1, 2, and 3).
MOTOR (J1)
Pin 1 should be connected to the motor winding
that moves the actuator toward the open position, and
conversely, pin 3 is connected to the winding that moves
the actuator toward the closed position. Pin 2 is the neu-
tral or common wire to the motor windings. The AMI-
103 is suitable for powering most dynamic brakes used
with electric actuators; however, consult the actuator
manufacturer for more information.
OUTPUT INDICATORS
The AMI-103 units have on-board indicators that
identify when one of the motor outputs is turned on.
When the open output is turned on, the red LED indicator
will turn on, and when the close output is turned on the
green LED indicator will turn on (see Outline).
Many actuators are equipped with limit switches
at the open and closed positions which are intended to dis-
connect power to the motor to prevent mechanical dam-
age. For this reason, it is possible that the AMI-103 will
indicate that one of the motor outputs is turned on when
the actuator is not in motion. However, it should be noted
that when the indicator is on, power is applied to the mo-
tor output.
INPUT DELAY
Since some AC motors do not operate correctly
when power is instantaneously switched between the
Open and Close windings, the AMI-103 provides an input
delay. If one output is on and the control signal inputs are
switched to reverse the motor, the unit will delay turning
on the other output. This delay is adjustable; see Specifi-
cations under "Control Adjustments" for delay period and
Outline for location of the adjustment. When both outputs
are off and a control input signal is applied, the Input De-
lay setting causes a delay in turning on the associated out-
put. If the control signal is removed before the end of the
delay period, the associated output will not turn on.
OPEN and CLOSE SWITCHES
The AMI-103 provides on-board switches that
allow manual operation from the unit - see Outline for
location of the switches. Pressing the open switch will
turn on the Open output (J1 pin 1), while pressing the
close switch turns on the Close output (J1 pin 3). Since
the OPEN and CLOSE switches replace the control signal
inputs, the Input Delay function effects the switch opera-
tion in the same manner as a control signal - refer to IN-
PUT DELAY for more details.
To protect against turning on both outputs at the
same time, the AMI-103 will not turn on one of the out-
puts until the other output has turned off. Additionally, if
both control signals are applied at the same time, the unit
will turn off both outputs. This is true of any combination
of control signals or on-board switch operation. For ex-
ample, if a PLC is applying a control signal to the CLOSE
input while someone is pressing the open switch, both
outputs will be turned off.
2-WIRE / 3-WIRE CONTROL (JP5)
JP5 is used to configure the unit for either 2-wire
or 3-wire control - see Outline for location and setting of
JP5. In 3-wire control, the Open input signal is used to
turn on the Open output (J1 pin 1), and the Close input
signal is used to turn on the Close output (J1 pin 3).

AMI-103
PEAKTRONICS 5
In 2-wire control, only the Open input signal is
used, and the Close input terminals (J2 pins 4, 6, and 8)
must not be connected. The Close output will always be
turned on until the Open input signal is applied, at which
time the Close output is turned off and the Open output
will turn on. When the Open input signal is applied, the
manual Open switch will have no effect, while the manual
Close switch will turn off both outputs. When the Open
input signal is not applied, the manual Close switch will
have no effect, while the manual Open switch will turn off
the Close output and turn on the Open output.
REPEAT CYCLE TIMER
The AMI-103 has a built-in repeat cycle timer that
can be used to adjust the actuator speed. The timer auto-
matically cycles the output on and off whenever the asso-
ciated control input is applied. The ON time is adjustable
from 0.1 to 2 seconds, while the OFF time is adjustable
from 0.5 to 10 seconds. The timer function can be ena-
bled or disabled for each output independently by in-
stalling jumpers for the desired operation. See Outline for
location of adjustments and jumpers.
SPECIFICATIONS
POWER REQUIREMENTS
AMI-103: 117VAC ±10%, 50/60 Hz
AMI-103A: 234VAC ±10%, 50/60 Hz
AMI-103B: 24VAC ±10%, 50/60 Hz
3.6 VA typical (not including output load)
Fuse Type: 6.3A 3AG Time Delay
AC HI CONTROL SIGNAL INPUTS
Maximum Input Voltage:
130VAC 50/60 Hz (20 mA typical @ 60 Hz)
Minimum ON Voltage:
85VAC 50/60 Hz (13 mA typical @ 60 Hz)
Maximum OFF Voltage:
60VAC 50/60 Hz (8.8 mA typical @ 60 Hz)
Maximum OFF State Input Current:
7.5 mA @ 60 Hz / 6 mA @ 50 Hz
DC/AC LO CONTROL SIGNAL INPUTS
Maximum Input Voltage:
130VDC (4 mA typical)
90VAC 50/60 Hz (3.3 mA typical)
Minimum ON Voltage:
2.4VDC (0.4 mA maximum), TTL compatible
1.9VAC (0.16 mA typical)
Maximum OFF Voltage:
1.8VDC
1.3VAC
Maximum OFF State Input Current:
0.25 mA DC / 0.1 mA AC
+24V OUTPUT
24VDC ±5% @ 45mA max
AC MOTOR OUTPUTS
Off-state Leakage Current: <15mA
Maximum Load Current @ 60°C:
5A (when properly mounted)
CONTROL ADJUSTMENTS
Cycle Timer, ON Time: 0.1 to 2 seconds
Cycle Timer, OFF Time: 0.5 to 10 seconds
Input Delay:
0.056 to 1.5 second, switching inputs (3-wire)
0.017 to 1 second, single input (3-wire)
0.04 to 1.5 second (2-wire)
ENVIRONMENTAL
Operating Temperature Range: 0 °C to 60 °C
Storage Temperature Range: -40 °C to 85 °C
Relative Humidity Range: 0 to 90 % (noncondensing)

AMI-103
6 PEAKTRONICS
WIRING DIAGRAMS
Input Signal Configurations
(connect OPEN input only for 2-Wire Control)
DC Control Inputs using TTL, CMOS,
or Sourcing Outputs
AMI-103
OPEN
DC/AC LO
CLOSE
DC/AC LO
OPEN
COMMON
CLOSE
COMMON
TTL or CMOS
or Sourcing
Outputs
Ground
J2-9
J2-8
J2-5
J2-4
Close
Open
AMI-103
OPEN
DC/AC LO
CLOSE
DC/AC LO
OPEN
COMMON
CLOSE
COMMON
2.4 to 130 VDC
or
1.9 to 90 VAC
Ground
J2-9
J2-8
J2-5
J2-4
Close
Relay 1
Open
Relay 2
DC or AC Control Inputs using relays
NOTE: Form C relay output card can
also be used in this application.
AMI-103
OPEN
DC/AC LO
CLOSE
DC/AC LO
OPEN
COMMON
SIGNAL
GND
J2-9
J2-8
J2-4
J2-10
DC Control Inputs using open collector outputs
CLOSE
COMMON
J2-5
+24V
OUTPUT J2-11
Both outputs are nor-
mally off.
Turn on Open output
to open actuator.
Turn on Close output
to close actuator.
Open
Close
Ground
Open Collector
Outputs
AMI-103
OPEN
AC HI
CLOSE
AC HI
OPEN
COMMON
CLOSE
COMMON
J2-7
J2-6
J2-5
J2-4
AC Control Inputs using 120VAC
Line
120VAC
Neutral
Open
Close
Neutral
Triac or
Solid State Relay
Outputs
Off State Leakage
Current
7.5mA max (60Hz)
6mA max (50Hz)
NOTE: Form C relay output card can
also be used in this application.

AMI-103
PEAKTRONICS 7
WIRING DIAGRAMS
Special Applications
Powering a Feedback Transmitter
J2-10
J2-11
Feedback
Potentiometer
1K ohms
MONITOR
INPUT
POT-102
XMA-105
OPEN
7.5V
W
Output
AMI-103
SIGNAL GND
+24V OUTPUT
4-20mA Transmitter
5/10V Transmitter
XMA-106
Connecting a Local/Remote Station using AC HI inputs
J2-1
AMI-103
CLOSE
COMMON
L2
NEUTRAL
OPEN
COMMON
L1
LINE
OPEN
AC HI
CLOSE
AC HI
Line
120VAC
Neutral
Neutral
Close REMOTE
LOCAL
REMOTE
LOCAL
OPEN
OFF
CLOSE
Local/Remote Station
Open
J2-4
J2-5
J2-6
J2-2
J2-7
(117VAC ONLY)
NOTE: Form C relay output card can
also be used in this application.
Triac or
Solid State Relay
Outputs
Off State Leakage
Current
7.5mA max (60Hz)
6mA max (50Hz)

AMI-103
www.peaktronics.com
PEAKTRONICS, Inc.
1363 Anderson Clawson, MI 48017 Phone (248) 542-5640 FAX (248) 542-5643
800-181A
WIRING DIAGRAMS
Special Applications
Connecting a Local/Remote Station using DC/AC LO inputs
J2-10
AMI-103
CLOSE
COMMON
SIGNAL
GND
OPEN
COMMON
+24V
OUTPUT
OPEN
DC/AC LO
CLOSE
DC/AC LO
Ground
Close REMOTE
LOCAL
REMOTE
LOCAL
OPEN
OFF
CLOSE
Local/Remote Station
Open
J2-4
J2-5
J2-8
J2-11
J2-9
Relay 1
Relay 2
2.4 to 130 VDC
or
1.9 to 90 VAC
NOTE: Form C relay output card can
also be used in this application.
Connecting a Local/Remote Station using open collector outputs
J2-10
AMI-103
CLOSE
COMMON
SIGNAL
GND
OPEN
COMMON
+24V
OUTPUT
OPEN
DC/AC LO
CLOSE
DC/AC LO
Ground
REMOTE
LOCAL
REMOTE
LOCAL
OPEN
OFF
CLOSE
Local/Remote Station
J2-4
J2-5
J2-8
J2-11
J2-9
Open
Close
Open Collector
Outputs
Both outputs are nor-
mally off.
Turn on Open output
to open actuator.
Turn on Close output
to close actuator.
This manual suits for next models
2
Table of contents