
Fairbanks Nijhuis™ 11/12/12
2Intelliboost™ Water Booster System
Basic Operation Manual
MULTIPLE PUMP CONTROLLER WITH UP TO 4 DRIVES:
The controller will have a power OFF/ON selector switch to power up system. The normal operation of the controller,
as well as the staging of the pumps, is controlled by an independent processor. The VFD(s) act as “signal follower”
and do not independently control the speed of the pumps in Auto On mode. For initial setup and in the event of a
system failure, the VFD(s) can run the pumps in Hand On control at a user selected fixed speed, ignoring all signals
from the pump controller.
VFD OPERATION:
4-2 drives operate in the same manner. Hand On, Off, Auto On and Reset are the basic operations for the Local
Control Panel. Hand On selection is for independent drive operation. Off will turn off VFD, stopping pump rotation.
Auto On is selected when PLC is ready for testing and operation. Reset, in case of VFD fault, refers to the
operation manual.
VFD PARAMETERS AND COMMUNICATION SETTINGS:
VFD parameters set as described below should be entered when VFD is in the Off position. PLC and VFD are master
slave configured using Mod Bus RTU communication. Loss of communication will stop drive after Timeout. Each drive
shares the same parameter set except where drive name is required (Drive1 = 2, Drive2 = 3, Drive3 = 4, Drive4 = 5).
A Master Local Control Panel, LCP, is used to Copy and Download parameters from VFD to VFD.
Danfoss VLT AQUA FC 200 VFD (Factory Settings)
Parameter Set Designation Default
0-01 Manual Language US English
0-02 Manual Motor Speed Units, RPM or Hz Hz
0-03 Manual Regional Settings North America
1-03 Manual Torque Characteristics Auto EnergyOptim VT
1-23 Manual Motor Frequency Nameplate
1-24 Manual Motor Current Nameplate
1-25 Manual Motor Speed Nameplate
3-03 Manual Maximum Reference 60 Hz
3-41 Manual Ramp-Up Time 5 sec.
3-42 Manual Ramp-Down Time 2 sec.
4-14 Manual Motor High Speed Limit 60 Hz
4-19 Manual Maximum Output Frequency 60.1 Hz
4-12 Manual Motor Speed Low Limit 0 Hz
5-12 Manual Terminal 27 No Operation
8-01 Manual Control Site Control Word Only
8-03 Manual Control Time Out Limit 20 sec.
8-04 Manual Control Time Out Function Stop
8-10 Manual Control Word Profile FC Profile
8-30 Manual Protocol Mod Bus RTU
8-31 Manual Addresses Drive1 = 2, Drive2 = 3, Drive3 = 4, Drive4 = 5
8-32 Manual FC Port Baud Rate 19200
8-33 Manual Parity Even Parity, 1 Stop Bit
8-50 Manual Thru 56 Bus
0-50 Manual LCP Copy All to LCP
0-50 Manual LCP Download Download all to LCP
INTELLIBOOST™ WATER BOOSTER SYSTEM
BASIC OPERATION MANUAL