Pepperl+Fuchs RocketLinx ICRL-U-8M12-G60 User manual

MANUAL
RocketLinx
ICRL-U-8M12-G60
FACTORY AUTOMATION

With regard to the supply of products, the current issue of the following document is applicable: The General Terms of
Delivery for Products and Services of the Electrical Industry, published by the Central Association of the Electrical Industry
(Zentralverband Elektrotechnik und Elektroindustrie (ZVEI) e.V.) in its most recent version as well as the supplementary
clause: "Expanded reservation of proprietorship".
ICRL-U-8M12-G60 Manual

ICRL-U-8M12-G60 Manual
Table of Contents
3
Table of Contents
1. Safety Instructions......................................................................................................... 5
1.1. Warning .............................................................................................................................................. 5
1.2. General Safety Instructions ............................................................................................................. 5
1.3. Certified Usage.................................................................................................................................. 5
1.4. Installation Site Requirements ........................................................................................................ 5
1.5. Device Casing.................................................................................................................................... 6
1.6. Qualification Requirements for Personnel ..................................................................................... 6
1.7. National and International Safety Regulations ..............................................................................6
1.8. Shielding Ground .............................................................................................................................. 6
1.9. Requirements For Connecting Electrical Wires............................................................................. 7
1.9.1. General Requirements for Connecting Electrical Wires.............................................................. 7
1.9.2. Requirements for Connecting the Supply Voltage ...................................................................... 7
1.9.3. Relevant for Use in Explosion Hazard Areas (Hazardous Locations, Class I, Division 2) ........... 8
1.9.4. FCC Note ................................................................................................................................... 8
2. Product Overview........................................................................................................... 9
2.1. Power Supply .................................................................................................................................... 9
2.2. Ethernet Ports (10BASE-T/100BASE-TX) ..................................................................................... 10
2.3. LEDs ................................................................................................................................................ 10
2.3.1. Device State ............................................................................................................................. 10
2.3.2. Port Status................................................................................................................................ 11
2.3.3. ACA Connector ........................................................................................................................ 11
3. Installation ....................................................................................................................12
3.1. Checking the Package Contents ................................................................................................... 12
3.2. Installing and Grounding the ICRL-U-8M12-G60 ......................................................................... 12
3.2.1. Mounting on a Flat Surface....................................................................................................... 12
3.2.2. Grounding the ICRL-U-8M12-G60............................................................................................14
3.3. Wiring the Connector for the Supply Voltage ............................................................................. 14
3.4. Connecting Data Cables................................................................................................................. 15
4. Technical Data..............................................................................................................16

2021-02
4
ICRL-U-8M12-G60 Manual
Table of Contents

ICRL-U-8M12-G60 Manual
Safety Instructions
2021-02
5
1. Safety Instructions
1.1. Warning
UNCONTROLLED MACHINE ACTIONS
To avoid uncontrolled machine actions caused by data loss, configure all the data transmission devices
individually.
Before you start any machine that is controlled through data transmission, be sure to complete the configuration
of all data transmission devices.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1.2. General Safety Instructions
Improper usage of the device entails the risk of physical injury or significant property damage.The proper and
safe operation of this device depends on proper handling during transportation, proper storage and installation,
and careful operation and maintenance procedures.
•Before connecting any cable, read this document, and the safety instructions and warnings.
•Operate the ICRL-U-8M12-G60 with undamaged components exclusively.
•The ICRL-U-8M12-G60 is a potted device and there are not any serviceable components. In the event of a
failure, turn off the supply voltage and contact Pepperl+Fuchs for return procedures.
1.3. Certified Usage
Use the following guidelines:
•Use the ICRL-U-8M12-G60 only for the application cases described in the Pepperl+Fuchs product
information, including this manual.
•Operate the product only according to the technical specifications.
•Connect to the product only components suitable for the requirements of the specific application case.
Operational environment:
•On the inside of vehicles
•On the inside of buildings
1.4. Installation Site Requirements
•When you are selecting the installation location, make sure you observe the climatic threshold values
specified in the technical data.
•Operate the device at the specified ambient temperature (temperature of the ambient air at a distance of 2
in (5 cm) from the device) and at the specified relative humidity exclusively.

ICRL-U-8M12-G60 Manual
Safety Instructions
2021-02
6
•Use the device in an environment with a maximum pollution degree that complies with the specifications in
the technical data. See Technical Data on Page 16 for more information.
Note: Operation of the device in high humidity or condensing atmospheres is exclusively allowed when using
recommended accessories with IP67 rating.
1.5. Device Casing
At ambient air temperatures > 140 °F (+60 °C): The surfaces of the device housing may become hot. Avoid
touching the device while it is operating.
1.6. Qualification Requirements for Personnel
Only allow qualified personnel to work on the device. Qualified personnel have the following characteristics:
•Qualified personnel are properly trained. Training as well as practical knowledge and experience make up
their qualifications.This is the prerequisite for grounding and labeling circuits, devices, and systems in
accordance with current standards in safety technology.
•Qualified personnel are aware of the dangers that exist in their work.
•Qualified personnel are familiar with appropriate measures against these hazards in order to reduce the risk
for themselves and others.
•Qualified personnel receive training on a regular basis.
1.7. National and International Safety Regulations
Verify that the electrical installation meets local or nationally applicable safety regulations.
1.8. Shielding Ground
The overall shield of a connected shielded twisted pair cable is connected to the ground connection on the
metal housing as a conductor.
Beware of possible short circuits when connecting a cable section with conductive shielding braiding.

ICRL-U-8M12-G60 Manual
Safety Instructions
2021-02
7
1.9. Requirements For Connecting Electrical Wires
Before connecting the electrical wires, always verify that the requirements listed are complied with.
1.9.1. General Requirements for Connecting Electrical Wires
The following requirements apply without restrictions:
•The electrical wires are not connected to a power source.
•The cables used are permitted for the temperature range of the application case.
•Ground the device via the ground screw. Disconnect the grounding only after disconnecting all other
cables.
•Exclusively use 60/75 °C (140/167 °F) or 75 °C (167 °F) copper (Cu) wire.
•The power supply cable to be connected is suitable for ambient air temperature of at least 212 °F (100 °C).
•The power supply complies with the requirements for a safety extra-low voltage (SELV) as per IEC/EN
60950-1.
1.9.2. Requirements for Connecting the Supply Voltage
The following requirements apply without restrictions:
All of the following requirements are complied with:
•The supply voltage corresponds to the voltage specified on the type plate of the device.
•The power supply conforms to over-voltage category I or II.
•The power supply has an easily accessible disconnecting device (for example a switch or a plug).This
disconnecting device is clearly identified. So in the case of an emergency, it is clear which disconnecting
device belongs to which power supply cable.
•The power supply cable is suitable for the voltage, the current and the physical load. Pepperl+Fuchs
recommends a wire diameter of 0.5 mm² to 0.75 mm² (AWG20 up to AWG18).
The following requirements apply alternatively.
Requirements for Connecting the Supply Voltage
Relevant when the device is supplied via 1 voltage input
Alternative
1The power supply complies with the requirements for a limited power source (LPS) as per EN
60950-1.
Alternative
2Relevant for North America: The power supply complies with the requirements according to NEC
Class 2.
Alternative
3
All of the following requirements are complied with:The power supply complies with the
requirements for a safety extra-low voltage (SELV) as per IEC/EN 60950-1.
Install a fuse suitable for DC voltage in the plus conductor of the power supply.
Connect the minus conductor to the ground potential. If the minus conductor is not connected to
the ground potential, also install an external fuse in the minus conductor.
See the notes below.
Relevant when the device is supplied via 2 voltage inputs
Alternative
1The total voltage supply meets the requirements for a limited power source (LPS) as per EN
60950-1.

ICRL-U-8M12-G60 Manual
Safety Instructions
2021-02
8
1.9.3. Relevant for Use in Explosion Hazard Areas (Hazardous Locations, Class I,
Division 2)
This equipment is exclusively suitable for use in Class I, Division 2,
Groups A, B, C, and D or non-hazardous locations.
WARNING – EXPLOSION HAZARD – DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN
SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF ANY COMPONENT MAY IMPAIR SUITABILITY
FOR CLASS I, DIVISION 2.
Avertissement - Risque d'explosion - Ne pas débrancher tant que le circuit est sous tension à moins que
l'emplacement soit connu pour ne contenir aucune concentration de gaz inflammable.
Avertissement - Risque d'explosion - La substitution de tout composant peut rendre ce matériel incompatible
pour une utilisation en classe I, division 2.
This device is an open-type device that is to be installed in an enclosure suitable for the environment.
Exclusively use the device for the application cases specified by the manufacturer. Failure to follow these
instructions can impair device protection.
1.9.4. FCC Note
The ICRL-U-8M12-G60 complies with part 15 of the FCC rules. Operation is subject to the following two
conditions: (1) this device may not cause harmful interference; (2) this device must accept any interference
received, including interference that may cause undesired operation.
Appropriate testing has established that this device fulfills the requirements of a class A digital device in line
with part 15 of the FCC regulations.
These requirements are designed to provide sufficient protection against interference when the device is being
used in a business environment.The device creates and uses high frequencies and can also radiate these
frequencies. If it is not installed and used in accordance with this operating manual, it can cause radio
transmission interference.The use of this device in a residential area can also cause interference, and in this
case the user is obliged to cover the costs of removing the interference.
Alternative
2Relevant for North America: The total voltage supply complies with the requirements as per NEC
Class 2.
Alternative
3
All of the following requirements are complied with: The power supply complies with the
requirements for a safety extra-low voltage (SELV) as per IEC/EN 60950-1. In both voltage inputs,
install a fuse suitable for DC voltage in the plus conductor of the power supply. In both voltage
inputs, connect the minus conductor to the ground potential. If the minus conductor is not
connected to the ground potential, also install an external fuse in the minus conductor. See the
note below.
Note: Back-up fuse for each voltage input when supplied via 1 input.
Nominal rating: 1 A ... 4 A
Characteristic: slow blow
Note: Back-up fuse for each voltage input when supply is via 2 inputs.
Nominal rating: 1A ... 2 A
Characteristic: slow blow
Requirements for Connecting the Supply Voltage

ICRL-U-8M12-G60 Manual
Product Overview
2021-02
9
2. Product Overview
The RocketLinx ICRL-U-8M12-G60 is an 8-port unmanaged field-mountable Ethernet switch designed for use
in industrial applications. With eight 10/100 Mbps Ethernet ports and redundant power inputs all utilizing M12
connections, it achieves an IP65/67 protection rating. Its passively cooled design ensures long-term reliability
while supporting a wide operating temperature range from -40 to +70 °C making it appropriate for use in
extreme conditions. Further flexibility is provided by its wide input voltage range of 9.6 to 45 VDC.
2.1. Power Supply
The supply voltage is connected by means of a 5-pin, A-coded M12 connector (PG7). See Wiring the
Connector for the Supply Voltage on Page 14 for more information.
ICRL-U-8M12-G60
1 Mounting hole
2 8 × Indicator plate
3
8 × 4-pin, D-coded M12 socket
for 10/100 Mbps twisted pair
connections.
See Connecting Data Cables on
Page 15 for more information.
4
8 × Port Status LEDs.
See Port Status on Page 11 for
more information.
5
Power supply LEDs.
See Device State on Page 10 for
more information.
6M12 interface used during
manufacture at Pepperl+Fuchs
7
Ground connection.
See Installing and Grounding the
ICRL-U-8M12-G60 on Page 12
for more information.
8 Mounting hole
9
Supply voltage connector.
See Wiring the Connector for the
Supply Voltage on Page 14 for
more information.

ICRL-U-8M12-G60 Manual
Product Overview
2021-02
10
2.2. Ethernet Ports (10BASE-T/100BASE-TX)
You can connect terminal devices and other segments at the ports of the ICRL-U-8M12-G60 using twisted pair
cables.The Ethernet ports are 4-pin, D-coded M12 sockets.
The 10/100 Mbps twisted pair port allows you to connect network components according to the IEEE 802.3
10BASE-T/100BASE-TX standard.This port supports:
•Auto-negotiation
•Auto-polarity
•Auto-crossing
•100 Mbps half-duplex mode, 100 Mbps full duplex mode
•10 Mbps half-duplex mode, 10 Mbps full duplex mode
The screw threads of the M12 ports are electrically connected to the device casing.
2.3. LEDs
After the supply voltage is set up, the software starts and initializes itself. During this process, various LEDs
light up.
2.3.1. Device State
These LEDs provide information about conditions which affect the
operation of the ICRL-U-8M12-G60.
Ethernet Pin Assignment ICRL-U-8M12-G60
1 TD+ Transmit Data+
2 RD+ Receive Data+
3 TD- Transmit Data-
4 RD- Receive Data-
Housing: shield
LED Display Color Activity Meaning
P1 Supply
voltage 1
green lights up Supply voltage is on
none Supply voltage is too low
P2 Supply
voltage 2
green lights up Supply voltage is on
none Supply voltage is too low

ICRL-U-8M12-G60 Manual
Product Overview
2021-02
11
2.3.2. Port Status
These LEDs provide port-related information.
2.3.3. ACA Connector
The ACA connector is a 5-pin, A-coded M12 socket with shielding that used by Pepperl+Fuchs during the
manufacture process.
LED Display Color Activity Meaning
L/D Link state/
data traffic
—noneDevice detects an
invalid or missing link
green lights up Device detects a valid
link
yellow flashing Device is transmitting
and/or receiving data
green/
yellow flashing
alternately
Update of the
configuration via the
M12 interface

ICRL-U-8M12-G60 Manual
Installation
2021-02
12
3. Installation
The ICRL-U-8M12-G60 has been developed for practical application in a harsh industrial environment. On
delivery, the device is ready for operation.
Perform the following steps to install the ICRL-U-8M12-G60:
•Checking the package contents
•Installing and grounding the device
•Wiring the connector for the supply voltage
•Operating the device
•Connecting data cables
3.1. Checking the Package Contents
Before installation, verify that the following are available.
•ICRL-U-8M12-G60 switch
•1 × Transport protection cap for supply voltage connection
•7 × Protection screws for M12 socket, plastic
•15 × Indicator plates
•1 x Right-angle cable socket (PG7, 4 Pin, Female connector)
•Safety and general information sheet
3.2. Installing and Grounding the ICRL-U-8M12-G60
3.2.1. Mounting on a Flat Surface
The following requirements should be met to mount the ICRL-U-8M12-G60 on a flat surface:
•Select the installation site so that the climatic threshold values listed in the technical data are observed.
See Technical Data on Page 16.
•Protect the exposed uninstalled contacts of the components from dirt and connect the individual system
components in a dry and clean working area.
•Make sure to seal all unused connections and ports with the provided plastic protection screws to maintain
the IP65/67 suitability for your device,
•Make sure to only connect components with degree of protection IP65/67 to sustain the IP65/67 suitability
for your device.
Note: The torque for tightening the protection screws on the device is 5.3 lb- in (0.6 Nm).

ICRL-U-8M12-G60 Manual
Installation
2021-02
13
Install the ICRL-U-8M12-G60 accordingly.
1. Prepare the drill holes at the installation point.
2. Mount the device on a level surface with two M4 screws.

ICRL-U-8M12-G60 Manual
Installation
2021-02
14
3.2.2. Grounding the ICRL-U-8M12-G60
Use the following information to ground the ICRL-U-8M12-G60:
•Use a suitable wire diameter for the functional grounding. Pepperl+Fuchs recommends a wire diameter of
0.5 mm² (AWG20).
•Use toothed washers to ensure good electrical conductivity at the connection.
•Ground the device via an M4 screw.
Note: The grounding screw is not included with the product and
must be supplied by the installation personnel.
Use the following information to ground the ICRL-U-8M12-G60:
•Ground the ICRL-U-8M12-G60 is by means of a separate
ground connection on the ICRL-U-8M12-G60.
•Ground the ICRL-U-8M12-G60 before connecting any other
cables.
•Disconnect the ground only after disconnecting all of the other
cables.
3.3. Wiring the Connector for the Supply
Voltage
The following requirements need to be met before wiring the power supply.
•The power supply cable is suitable for the voltage, the current and the physical load. Pepperl+Fuchs
recommends a wire diameter of 0.5 mm² to 0.75 mm² (AWG20 up to AWG18).
•The permitted cable diameter for connector PG7 is 0.15 in (4 mm) to 0.23 in (6 mm). To ensure the
watertightness of the ICRL-U-8M12-G60, only use voltage supply cables with a diameter within the
specified range.
•Make sure that you can easily disconnect the ICRL-U-8M12-G60 from the main voltage.
Note: The supply voltage can be connected redundantly. Both plus connections are uncoupled. There is no
distributed load. With redundant supply, the power supply unit with the higher output voltage supplies
the device on its own.
When you connect the supply voltage, the ICRL-U-8M12-G60 starts up.
Pin assignment ICRL-U-8M12-G60 (5-Pin, A-Coded)
Pin Description
1 Power supply (1): + 12/24/36 V DC (1)
2 Not connected
3P-
4 Power supply (2): + 12/24/36 V DC (2)
5 Not connected

ICRL-U-8M12-G60 Manual
Installation
2021-02
15
3.4. Connecting Data Cables
Use the following guidelines when connecting the data cables.
•Shielded CAT5e cable or better.
•SF/UTP cables as per ISO/IEC 11801:2002.
•Shielded D-coded, 4-pin M12 connectors.
•Keep the length of the data cables as short as possible.
•When using copper cables, provide a sufficient separation between the power supply cables and the data
cables.
•Verify that power supply cables and data cables do not run parallel over longer distances, and that ideally
they are installed in separate cable channels. If reducing the inductive coupling is necessary, verify that the
power supply cables and data cables cross at a 90° angle.
•Seal all unused connections and ports with the provided plastic protection screws.
•Make sure the cable shielding is connected to the M12 plug thread.
Note: The torque for tightening the protection screws on the device is 5.3 lb- in (0.6 Nm).
D-Coded, M12
Pin Signal
1Tx+
2Rx+
3Tx-
4Rx-

ICRL-U-8M12-G60 Manual
Technical Data
2021-02
16
4. Technical Data
ICRL-U-8M12-G60 General Technical Data
Power supply
Safety extra-low voltage
(SELV) Relevant for North
America: NEC Class 2 power source max. 2A.
Rated voltage DC: 12/24/36V DC
Voltage range DC incl.
maximum tolerances: 9.6V DC ... 45V DC
Connection type 5-pin, “A”-coded M12 connector
Power loss buffer >10 ms
Peak inrush current <1.4 A (1ms)
Current integral I²t 0.15 A2s
Climatic
conditions during
operation
Ambient air temperature
(Temperature of the ambient
air at a distance of 2 in (5 cm)
from the ICRL-U-8M12-G60)
up to 6562 ft ASL (2000 m ASL) -40°F to +158°F
(-40°C to +70°C)
6562 ft ASL to 13123 ft ASL -40°F to +149°F
(2000 m ASL to 4000 m ASL) (-40°C to +65°C)
Humidity 5% to 100% (also in condensing atmospheres)
Air pressure without de-rating
Air pressure with de-rating
min. 795 hPa (+6562 ft; +2000 m)
max. 1060 hPa (-1312 ft; -400 m)
Climatic
conditions during
storage
Ambient air temperature
(Temperature of the ambient
air at a distance of 2 in (5 cm)
from the ICRL-U-8M12-G60)
up to 3 months: -40 °F to +185 °F (-40 °C to +85 °C)
up to 1 year: -40 °F to +158 °F (-40 °C to +70 °C)
up to 2 years: -40 °F to +122 °F (-40 °C to +50 °C)
up to 10 years: +32 °F to +86 °F (0 °C to +30 °C)
Humidity 5% to 100% (also in condensing atmospheres)
Air pressure min. 700 hPa (+9842 ft; +3000 m)
max. 1060 hPa (-1312 ft; -400 m)
Protection class Degree of protection IP65/67
Pollution degree 4

Subject to modifications
Copyright PEPPERL+FUCHS • Printed in Germany
www.pepperl-fuchs.com
FACTORY AUTOMATION –
SENSING YOUR NEEDS
Worldwide Headquarters
Pepperl+Fuchs Group
68307 Mannheim · Germany
Tel. +49 621 776-0
E-mail: [email protected]
USA Headquarters
Pepperl+Fuchs Inc.
Twinsburg, Ohio 44087 · USA
Tel. +1 330 4253555
E-mail: [email protected]
Asia Pacific Headquarters
Pepperl+Fuchs Pte Ltd.
Company Registration No. 199003130E
Singapore 139942
Tel. +65 67799091
E-mail: [email protected]
DOCT-7053
2021-02
Table of contents
Other Pepperl+Fuchs Network Router manuals