Phoenix Controls FSR100 User manual

FAN STATIC RESET KIT
75 Discovery Way • Acton, Massachusetts 01720 • Telephone (978) 795-1285 • Fax (978) 795-1111
©2010 Phoenix Controls Corporation. Specifications subject to change without notice. Rev. 5/10 MKT-0266 MPC-1480 FAN STATIC RESET KIT—1 OF 12
SPECIFICATIONS (continued)
Temperature
Error
±2% of Span (Over the
Operating Temperature Range)
Enclosure
Humidity 95% non-condensing
Material Polycarbonate
Material Rating UL94, V-0
Enclosure Rating IP66
Dimensions 4.15" x 5.00" x 2.50"
(105.4 mm x 127 mm x 63.6 mm)
Tubing
ID/OD 1/8" / 1/4" (3.2 mm / 6.4 mm)
Wall Hardness Shore A 70
Temperature
Range
-137° F to 738° F
(-94° C to 392° C)
Tensile Strength 1350 PSI
Fan Static Reset Kit
The Fan Static Reset Kit accurately measures the static pressure drop
across a clean air valve and provides feedback to the Building
Management System (BMS) to optimize fan control. The sensor is
housed in a rugged polycarbonate enclosure, which mounts directly to
the valve base channel and has a 3-wire connection to the valve
mounted controller for power and signal. Two pressure pickups, two
pressure dampers and two, six foot lengths of silicon tubing are
included for mounting upstream and downstream of the valve to
obtain optimized pressure readings. One device with a range of 0.0 to
5.0" W.C. covers both medium and low pressure valves and allows for
dynamic fan control to reduce energy consumption under varying
flow conditions.
FEATURES
• Precision sensor provides accurate control feedback value
• Sensor mounts directly on valve base channel
• Pressure value is available network wide
• BMS can dynamically monitor and control fan static
• Maximize energy savings by running fans at lowest possible static
SPECIFICATIONS
Pressure Transmitter
Pressure Range 0 to 5" W.C. (0 to 1.245 Pa)
Output Voltage 0.25 to 4.0 Vdc
Zero Pressure Output 0.25 ±0.06 Vdc
Accuracy 1.5% of span (0.0 to 3.0" W.C. at 75° F)
(0 to 747 Pa at 23.9° C)
2.0% of span (3.0 to 5.0" W.C at 75° F.)
(747 to 1245 Pa at 23.9° C)
Proof Pressure 1 PSI either Port (6.9K Pa)
(performance will be affected)
Burst Pressure 1.5 PSI either Port (10.4K Pa)
(permanent damage will occur)
Corrosion Resistance Pressure sensor is suitable for clean,
non-corrosive, non-condensing air only
Supply Voltage 7 to 32 Vac or 7 to 40 Vdc
Power Consumption 0.12 VA maximum
Storage Temperature 40 °F to 203° F (-40° C to 95° C)
Operating
Temperature
32° F to 140° F (0° C to 60° C)
TABLE OF CONTENTS
Ordering Guide ............................................... 2
Applications ..................................................... 2
Installation....................................................... 3
Wiring the Pressure Sensor............................... 7
Phoenix Controls Wiring Recommendations ... 9
Maintenance .................................................... 9
Troubleshooting ............................................. 10
Phoenix Recommended Wiring ..................... 11

2 OF 12—FAN STATIC RESET KIT MKT-0266 MPC-1480 ©2010 Phoenix Controls Specifications subject to change without notice. Rev. 5/10
ORDERING GUIDE
APPLICATIONS
The Fan Static Reset (FSR) kit measures the pressure drop across select Accel II valves and passes this value across the network to
allow the BMS to potentially save energy by optimizing fan speed control. By continuously monitoring the static pressure at the
lowest point in the system, the BMS can trim fan speed as flow conditions and static pressure in the system changes. The intent is
to control the fans at the lowest practical speed to gain whatever energy savings is possible while ensuring there is sufficient static
pressure for the pressure independent cone assembly to maintain the desired flow.
The FSR is intended to be installed across the valves in the duct runs believed to be the "worst case" in terms of pressure loss. These
are typically the furthest from the fans or with the greatest number transitions, turns, or obstructions such as filter coils or dampers.
A review of the duct layout drawings can provide clues to the location of the valve that will see the lowest system pressure, however,
the lowest point may change based on different operational conditions. Spot checking may be the best way to determine the low
point or it may be prudent to select a number of locations to install FSRs and perform a low-select as system conditions vary.
The FSR100 is intended for installation on "Clean air" (Supply or General Exhaust) valves. The materials of construction of the
pressure pickup, tubing and the pressure sensor itself are not suitable for applications with corrosive or condensing vapors.
Additionally, the fume hood valve controller does not have inputs available for connecting the pressure sensor or network variables
for passing the value across the network. Therefore it should not be used on fume hood applications.
The FSR mounts on the valve base channel. The pressure pickups are installed in the duct work upstream and downstream of the
valve and the pressure sensor is connected to the power source and available universal input of the valve controller. Then the
Universal Input (UI) signal is scaled in the Configuration Plug-in program according to actual field measurements of pressure from
the sensor.
It is important to recognize accuracies, errors and tolerances, as well as response times throughout the entire sensing and control
system when choosing a static pressure control setpoint. If the total potential error (transmitter accuracy and temperature error) is
±0.1 inch W.C. and the valves have a 1 second speed of response while the fan speed controller may require 20 to 30 seconds to
respond to a change in setpoint, there must be sufficient safety margin in the setpoint to ensure the static pressure at the valve is
never compromised.
BASE NUMBER
FSR100 = Fan Static Reset Kit (includesthe following)
1 - 0 to 5 inch W.C. differential pressure sensor with 0.25 to 4.00 Vdc output
2 - Pressure pickup
2 - Pressure dampers
2 - 6 foot (1.83 m) sectionssilicon tubing
1 - Mounting bracket
1 - Miscellaneous mounting hardware
FSR100

©2010 Phoenix Controls Specifications subject to change without notice. Rev. 5/10 MKT-0266 MPC-1480 FAN STATIC RESET KIT—3 OF 12
INSTALLATION
The Fan Static Reset kit comes complete with all the components and mounting hardware necessary for installation. The pressure
sensor mounts to the valve base channel and gets its power from the valve controller and connects to any available UI on the valve
controller. The pressure pickups are mounted upstream and downstream of the valve and connected using the two supplied sets of
silicon tubing and pressure dampers. Nylon wire ties and self-adhesive mounts may be used to secure the silicon tubing to the duct.
Mounting the sensor
The sensor is attached to a mounting bracket that can be mounted in several locations on the base channel depending on the size of
the valve, its actuator type and what options are installed. Two locations, opposite the electronics enclosure have existing holes and
are preferred for mounting the sensor (see 1 and 2 below). Two alternate locations, on opposite corners of the base channel (3 and 4
below) require the use of self-drilling, "Zip" screws. Use care when using the "Zip" screws so they do not pierce the valve body.
1May be used if the preferred locations are obstructed by other components on the base channel
NOTE: Mount the sensor bracket using two screws in an orientation that allows access to the electrical connection port and
permits the enclosure door to open allowing access to the internal wire connections.
Guidelines for locating the pressure pickups
For stable and accurate readings the duct runs immediately upstream and downstream must be straight and free of any obstructions
such as bends, transitions, filters, dampers and coils. Per ANSI/ASHRAE 130-2008 Methods of Testing Air Terminal Units, the duct
immediately upstream and downstream of the valve must be uniform in shape with no obstructions for a minimum of 3.0
equivalent duct diameters upstream, and 3.5 equivalent duct diameters downstream of the valve. Anything less than the 3
uninterrupted duct diameters upstream and 3.5 diameters downstream is highly suspect and should not be used. The longer the
straight uninterrupted duct runs upstream and downstream of the valve, the better the flow profile and the more stable and accurate
the readings you will achieve.
Additionally, the pressure pickups must be a minimum of 1.5 equivalent duct diameters upstream and 2.5 equivalent duct
diameters downstream away from the valve. Any closer to the valve and turbulence from the valve components in the flow stream
will likely compromise the stability and accuracy of any readings. As a general rule, the area within a minimum of 1.5 equivalent
duct diameters downstream or upstream of any obstruction would be a poor location for the pressure pickup. The further away the
pressure pickups are located from the valve and any other obstruction, the more stable and accurate the readings will be.
Table 1: Sensor Mounting Location and Actuator Type
Number Location Type Valve Size Actuator Type
1PreferredAll All
2 Preferred All HiSEA and Pneumatic
3Alternate1All All
4Alternate112" and 14" All
123
4

4 OF 12—FAN STATIC RESET KIT MKT-0266 MPC-1480 ©2010 Phoenix Controls Specifications subject to change without notice. Rev. 5/10
NOTE: These guidelines should provide adequate readings. However, the only way to confirm the suitability of the pressure
pickup location is to perform a full duct traverse following the procedures outlined in the ANSI/ASHRAE 111-2008
Measurement, Testing, Adjusting, and Balancing of Building HVAC Systems. If the pressure reading at the pressure
pickup is within 5% of the values measured when the duct was traversed, this is the optimum location.
The pressure pickups must be located in a position on the duct that will not be susceptible to becoming clogged or allow
condensation to enter the sensing tubes. On round or oval duct, it is recommended the pressure pickups be placed in the upper
portion of the circumference of the duct between 8 and 4 o'clock. On rectangular duct, the preferred placement of pressure pickups
is on top of the duct, well away from the corners. Other acceptable locations are at least 2-3" (51-76 mm) up the side wall of the
duct and not near any corner of the duct. Mounting the pressure pickups on the bottom of the duct is not permitted.
Mounting the pressure pickups
The pressure pickups are mounted directly to the duct using 2 self-drilling "Zip" screws (included). A closed cell foam gasket seals
the pressure pickup to the duct.
Once you have determined the proper location of the pressure pickup, you will need an area free of any insulation. The pressure
pickups must be mounted directly on the duct surface. The pressure pickups may not be used on double-walled or lined duct. If the
duct is double-walled, contact your Phoenix Controls Representative for recommendations.
1. Orient the pressure pickup so that the arrow etched on the mount plate indicates the airflow direction.
NOTE: It is important that the top and bottom mounting screws are oriented perpendicular to the direction of airflow so as
not to cause obstructions near the pickup.
Min. 3.0 straight
duct diameters
Min. 4.0* straight
duct diameters
Min. 1.5 duct
diameters
downstream of
any obstruction
Min. 2.5 duct
diameters
downstream
Min. 1.5 duct
diameters
upstream
Min. 1.5 duct
diameters
downstream of
any obstruction
*ANSI/ASHRAE standard exceeded by FSR100 product requirement

©2010 Phoenix Controls Specifications subject to change without notice. Rev. 5/10 MKT-0266 MPC-1480 FAN STATIC RESET KIT—5 OF 12
2. Using 4 of the Zip screws (included) attach first one, then the other pressure pickup to the duct compressing the gasket evenly
top and bottom.
NOTE: Be careful not to over-tighten the screws and deform the plate or strip the mounting holes.
We recommend tightening to no more then 12 in.-lb. (1.35 Newton-meters).
3. Next, using the pressure pickup barb as a guide, drill a hole between 5/64" (.078"/1.98 mm) and 7/64" (.109"/2.77 mm) in
the duct wall.
WARNING: Use care so as not to damage the barb with the drill bit.
4. Attach the short length of silicon tube containing the pressure damper, to the pressure pickup barb.
NOTE: Make certain that the pressure damper is oriented in the proper direction (arrow pointing AWAY from the pickup) as
it is not bi-directional.
5. Connect one end of the longer piece of silicon tubing to the pressure damper.

6 OF 12—FAN STATIC RESET KIT MKT-0266 MPC-1480 ©2010 Phoenix Controls Specifications subject to change without notice. Rev. 5/10
6. Cut it to length and connect it to the appropriate port on the sensor.
• Upstream or "fan side" of the valve connects to the "H" (high) port on the sensor.
• Downstream or "room side" of the valve connects to the "L" (low) port on the sensor.
NOTE: Make certain the tubing is not kinked and not in a position where moving parts on the valve could pinch or cut it.
7. Secure the tubing to the duct using the enclosed tie wraps and adhesive backed holders, or duct tape so that it cannot become
tangled with any moving equipment in the area.
WARNING: Phoenix Controls recommends a "drip loop" somewhere along the tubing run to prevent moisture or
condensation from reaching the ports on the pressure sensor. Moisture will damage the sensor beyond repair.

©2010 Phoenix Controls Specifications subject to change without notice. Rev. 5/10 MKT-0266 MPC-1480 FAN STATIC RESET KIT—7 OF 12
WIRING THE PRESSURE SENSOR
The pressure sensor is a 3-wire device; power, signal and circuit common. Three white crimp-on connectors are provided with the
kit and are used to connect the wires coming off of the sensor printed circuit board (PCB) with a 3-conductor cable (provided by
others) that terminates in the valve mounted controller enclosure. This cable leaves the sensor housing via the pre-drilled conduit
port opposite the pressure ports so no enclosure modifications are required in the field.
A 3-conductor cable must be run between the pressure sensor enclosure and the valve mounted controller enclosure. Wiring details
follow.
NOTE: Lead wire lengths will impact signal output/accuracy. Cable length should be limited to 5 to 10 feet (1.5 to 3 meters).
At the Sensor
• Red wire is for power
• White wire is for signal "+"
• Black wire is for circuit common
At the Celeris High-Speed Electric Controller
• FSR power wire terminates on TB4, Terminal 1 (L1)
• FSR signal "+" wire terminates on TB1, Terminals 1, 3 or 5 (+)
• FSR circuit common wire terminates on TB1, Terminals 2, 4 or 6 (-)
Celeris high-speed electric: any available UI (1, 2 or 3)
+1
-2
UI1
TB1
-4
5
+
UI3
UI2 3
+
-6
-8
DI1 +7
L2
L1
GND
WHITE (SIGNAL)
BLACK (CIRCUIT COMMON)
RED (POWER)
TB4

8 OF 12—FAN STATIC RESET KIT MKT-0266 MPC-1480 ©2010 Phoenix Controls Specifications subject to change without notice. Rev. 5/10
At the Celeris Pneumatic or Low-Speed Electric, or LON TP/SO Controller
• FSR power wire terminates on TB4, Terminal 1 (L1)
• FSR signal "+" wire terminates on TB1, Terminals 1, 3 or 5 (+)
• FSR circuit common wire terminates on TB1, Terminals 2, 4 or 6 (-)
NOTE: A jumper wire must be added between the circuit common termination and TB4, Terminal 2 (L2)
Celeris pneumatic, or low-speed electric, or LON TP/SO: any available UI (1, 2 or 3)
At the LON TX controller
• FSR power wire terminates on TB4, Terminal 1 (L1)
• FSR signal "+" wire terminates on TB1, Terminals 1, 3 or 5 (+) or TB8, Terminals 1 or 3 (+)
• FSR circuit common wire terminates on TB1, Terminals 2, 4 or 6 (-) or TB8, Terminals 2 or 4 (-)
NOTE: A jumper wire must be added between the circuit common termination and TB4, Terminal 2 (L2).
LON TX: any available UI (see LON TP/SO for 1, 2 or 3; see below for 4 or 5)
+1
-2
UI1
TB1
-4
5
+
UI3
UI2 3
+
-6
-8
DI1 +7
L2
L1
GND
WHITE (SIGNAL)
BLACK (CIRCUIT COMMON)
RED (POWER)
JUMPER WIRE
TB4
+
-
UI4
TB1
-
UI5 +
L2
L1
GND
WHITE (SIGNAL)
BLACK (CIRCUIT COMMON)
RED (POWER)
JUMPER WIRE
TB4

©2010 Phoenix Controls Specifications subject to change without notice. Rev. 5/10 MKT-0266 MPC-1480 FAN STATIC RESET KIT—9 OF 12
At the BACnet TX controller (BACnet TP, SO and EO controllers cannot be used with FSR100)
• FSR power wire terminates on Terminal 25 (24VAC)
• FSR signal "+" wire terminates on Terminals 6 or 9 (MULTI_AI)
• FSR circuit common wire terminates on Terminals 7 or 10 (COM)
NOTE: A jumper wire is not required on this controller.
BACnet TX: any available MULTI_AI
PHOENIX CONTROLS WIRING RECOMMENDATIONS
• All circuits must conform to the requirements of an NEC Class 2 (dry) circuit
• Use multiple transformers instead of larger transformers when more than 100 VA is required
• Each pressurization zone should have either a dedicated single-phase primary circuit, or a secondary circuit disconnect
• Use cable sizes recommended by Phoenix Controls (see Table 2)
• Use stranded wire for ease of installation
• Follow good wiring practices:
• Locate cables away from sources of electrical interference (EMI/RFI)
• Do not run signal or communication cable in the same conduit or wire way as power cables
• If signal cable must cross power cables place these at a 90-degree angle
• Shield or drain wires, if required, should be wrapped with insulating tape to prevent contact with exposed conductors or
contacts
• Maintain a consistent color code or polarity all the way through the wiring system
• Power supply and signal isolation on I/O devices vary from manufacturer to manufacturer. Verify the wiring device manufac-
turer's recommendations for isolating power and signal common connections and maintain polarity
• Local and national electrical codes take precedence
• Strip 0.25" (6.4 mm) of insulation from each conductor, twist the strands, insert the conductor fully into the terminal block,
and tighten the terminal
• Test the wire connection by pulling on each conductor
• See “Phoenix Recommended Cables” on page 11, for approved cable manufacturers and wire types
MAINTENANCE
There are no user serviceable components in the Fan Static Reset Kit. If you suspect the pressure sensor is not sending out a signal,
first check the power wiring to ensure the sensor has power.
Table 2: Recommended Cable Sizes
Minimum Maximum
22 AWG 16 AWG
6
7
WHITE (SIGNAL)
BLACK (CIRCUIT COMMON)
RED (POWER)
MULTI-A1
COM
9
MULTI-A1
10
COM
25
24 VAC
TERMINALS

10 OF 12—FAN STATIC RESET KIT MKT-0266 MPC-1480 ©2010 Phoenix Controls Specifications subject to change without notice. Rev. 5/10
TROUBLESHOOTING
There is no signal input • Check for power between the red and black wires
• Power should be between 7 to 40 Vdc or 7 to 32 Vac
• If no voltage is present check power source at the controller and interconnecting
cable
• If voltage is present, disconnect all other devices from the controller to see if the
signal returns
• Disconnect the white signal wire going to the controller and using a volt meter,
check for a signal voltage
If the device has a proper power source and there is no output signal with all other
devices disconnected, it must be returned to the factory for replacement.
The output signal appears to be
incorrect
• With no differential pressure across the sensor, the output signal should be 0.25
Vdc ±0.06 Vdc
• Disconnect the tubing and connect a short piece of tubing across both the high
and low pressure ports to shunt the high and low to the same value. The voltage
output should be 0.25 Vdc
- If the signal is 0.25 Vdc but the pressure variable does not read 0, make
sure the scaling in the Configuration Plug-in indicates 0.25 Vdc = 0" W.C.
- If the zero output has shifted, there are no user adjustments on the sensor
itself so the Configuration Plug-in must be used to rescale the input voltage
(ex. 0.45 Vdc = 0" W.C.)
• With differential pressure across the sensor if you suspect the signal is reading
incorrectly
• There is no span adjustment on the pressure sensor. If a duct traverse indicates
there is an error, the only option is to use the Configuration Plug-in to adjust the
scaling of the input voltage range. For example, if 0" W.C. is at 0.45 Vdc and 5"
W.C. is at 4.75 Vdc, the Configuration Plug-in scaling needs to indicate 0.45
Vdc = 0" W.C. and 4.75 Vdc = 5" W.C.

©2010 Phoenix Controls Specifications subject to change without notice. Rev. 5/10 MKT-0266 MPC-1480 FAN STATIC RESET KIT—11 OF 12
PHOENIX RECOMMENDED CABLES
A 3-conductor will typically be used with the FSR100.
Cable
Type
Plenum
Rated Function Wire
Gauge
Primary
Vendor/Part #
Alternate
Vendor/Part # Color Code Notes
2C
Round
No 24 Vac power to
LOSEA or
Pneumatic (110’
max at load 1, 2)
18 Belden 9409 1: Red
2: Black
Must be
stranded
24 Vac power to
HiSea (288’ max
at load 1, 2)
14 Belden 9411
2C
Round
Ye s 2 4 Va c p o w e r t o
LOSEA or
Pneumatic (110’
max at load 1, 2)
18 Belden 82740 Windy City
NP002360
1: Red
2: Black
Must be
stranded
24 Vac power to
HiSea (288’ max
at load 1, 2)
14 Windy City
NP007960
TP No FTT-10 (4500’)
TP1250 (425’)
22 Windy City 107500 Connect Air
W221P-1002
1: White/Blue stripe
2: Blue/White stripe
For more
alternatives
visit:
echalon.com
FTT-10 (8800’) 16 Windy City 109600
TP Yes FTT-10 (4500’)
TP1250 (425’)
22 Windy City 105500 Connect Air
W221P-2001
1: White/Blue stripe
2: Blue/White stripe
For more
alternatives
visit:
echalon.com
FTT-10 (8800’) 16 Windy City 109500
3C
Round
No Signal 22 Belden 8443 1: Red
2: Black
3: Green
Must be
stranded
3C or
4C
Round
Yes Signal 22 Belden 88444 Windy City
004380
1: Red
2: Black
3: Green
4: White (not used as 3C)
Must be
stranded
4C
Round
No Signal 22 Belden 8444 Manhatten
M13304
1: White
2: Green
3: Black
4: Red
Must be
stranded
5C
Round
No Signal 22 Belden 8445 Manhatten
M13305
1: White
2: Brown
3: Black
4: Red
5: Green
Must be
stranded
8C No Signal 22 Belden 9421 Manhatten
M13308
1: White
2: Orange
3: Black
4: Red
5: Green
6: Yellow
7: Blue
8: Brown
No
substitutes
8C Yes Signal 22 Comtran 4956 1: White
2: Orange
3: Black
4: Red
5: Green
6: Yellow
7: Blue
8: Brown
No
substitutes
3C
MS/TP
No Shielded 22 Belden 3106A
(120 ohm)
See specifications
below for alternate
cable solutions
1: White with Orange stripe
2: Orange with White stripe
3: Blue with White stripe
Shielded with
drain

12 OF 12—FAN STATIC RESET KIT MKT-0266 MPC-1480 ©2010 Phoenix Controls Specifications subject to change without notice. Rev. 5/10
1Load is 96 VA when power is provided by a 100 VA transformer with external 4 amp slow blow fuse.
2Load is 100 VA when power is provided by a 100 VA transformer with internal circuit breaker.
MS/TP Specifications for Alternate Cable Solutions
1. An MS/TP EIA-485 network shall use shielded, twisted-pair cable with characteristic impedance between 100 and 130Ω.
2. Distributed capacitance between conductors shall be less that 100 pF per meter (30 pf per foot).
3. Distributed capacitance between conductors and shield shall be less that 200 pF per meter (60 pF per foot).
4. Foil or braided shields are acceptable. The maximum recommended length of an MS/TP segment is 1200 meters (4000 feet)
with AWG 18 (0.82 mm2conductor area) cable.
5. The use of greater distances and/or different wire gauges shall comply with the electrical specifications of EIA-485 for MS/TP
cable requirements.
4C
MS/TP
Ye s A r m o r e d
Shielded
22 Belden 1269A
(100 ohm)
See specifications
below for alternate
cable solutions
1: Red
2: Blue
3: Black
4: Yellow
Foil and
braided
shield with
drain
4C
MS/TP
Ye s A r m o r e d
Shielded
22 Belden 123107A
(100 ohm)
See specifications
below for alternate
cable solutions
1: White with Blue stripe
2: Blue with White stripe
3: White with Orange stripe
4: Orange with White stripe
Foil and
braided
shield with
drain
4C
MS/TP
Ye s A r m o r e d
Shielded
24 Belden 82842
(100 ohm)
See specifications
below for alternate
cable solutions
1: White with Blue stripe
2: Blue with White stripe
3: White with Orange stripe
4: Orange with White stripe
Foil and
braided
shield with
drain
Low smoke
4C
MS/TP
Yes Shielded 24 Belden 82729
(100 ohm)
See specifications
below for alternate
cable solutions
1: White with Blue stripe
2: Blue with White stripe
3: White with Orange stripe
4: Orange with White stripe
Shield with
drain
4C
MS/TP
Yes Shielded 24 Belden 88102
(100 ohm)
See specifications
below for alternate
cable solutions
1: White with Blue stripe
2: Blue with White stripe
3: White with Orange stripe
4: Orange with White stripe
Shield with
drain
Cable
Type
Plenum
Rated Function Wire
Gauge
Primary
Vendor/Part #
Alternate
Vendor/Part # Color Code Notes
Table of contents