Plymovent Shield 5k1 User manual

www.plymovent.com
EN Fire safety solutions
EN Installation and user manual
shiEld 5k1

TABLE OF CONTENTS
0507347110/160114/B SHIELD fire safety solutions (5k1) 1
GENERAL Page
Preface 2
1. Introduction 2
2. Safety 4
3. Operation in case of fire 5
INSTALLATION Page
4. Installation (general) 6
5. ShieldControl 5k1 6
6. Heat detector set 9
7. Spark detector set 11
8. Smoke detector 13
9. Sliding valves 16
10. Solenoid valve 18
11. FlameShield 19
12. Functional test and commissioning 21
13. Commissioning checklist 22
14. Maintenance 23
15. Post-fire procedure 23
16. Electrical diagram 23
USER Page
17. Operation 24
18. Fire action procedure 25
19. Maintenance 26
20. Spare parts 26
21. Disposal 26
CE declaration 27
EN Original instruction
All rights reserved. The information given in this document has been collected for the general convenience of our clients. It has been based on general data pertaining to construction material properties and working methods known to us at
the time of issue of the document and is therefore subject at any time to change or amendment and the right to change or amend is hereby expressly reserved. The instructions in this publication only serve as a guideline for installation, use,
maintenanceandrepairof theproductmentionedonthe coverpage ofthis document.Thispublicationis to beusedfor thestandard modelof theproductof the typegiven on the coverpage.Thus themanufacturer cannotbeheld responsible
for any damage resulting from the application of this publication to the version actually delivered to you. This publication has been written with great care. However, the manufacturer cannot be held responsible, either for any errors occurring
in this publication or for their consequences.

0507347110/160114/B SHIELD fire safety solutions (5k1) | GENERAL | EN - 2
ENGLISH
Using this manual
This manual is intended to be used as a work of reference for
professional, well trained and authorised engineers to be able to
safely install, use, maintain and repair the components of
SHIELD fire safety solutions that are used for detection and
suppression of fire.
This document has been divided in an installation manual and a
user manual.
Pictograms and symbols
The following pictograms and symbols are used in this manual:
Text indicators
Listings indicated by "-" (hyphen) concern enumerations.
Listings indicated by "•" (bullet point) describe steps to perform.
This manual describes installation and maintenance of
components for fire detection and suppression. It contains
extensive commissioning instructions as well.
The user section describes the necessary maintenance activities
to secure the functionality of the overall system, as well as the
procedure in case a fire has occurred.
Abbreviations
In this manual, including electrical diagram, the following
abbreviations are used.
1.1 General description
This manual describes the following products.
1.1.1 Fire detection
Products developed to detect fire at an early stage in an reliable
manner. It concerns:
Detectors:
- heat detector set
- spark detector set
- smoke detector set
Fire detection panel:
- ShieldControl 5k1
1.1.2 Fire suppression
Products developed to suppress fire and constrain the risks with
minimum damage to the connected filter system, harmless to
environment and human. It concerns:
Valves:
- sliding valves
- solenoid valve
Aerosol fire extinguishing generators:
- FlameShield
1.2 Product combinations
The fire detection & suppression system is supposed to be
installed with:
- SparkShield (cyclone spark arrester)
- OilShield (limestone feeder)1
- central filter system type MDB, ranging from MDB-4 to MDB-
48 (other sizes on request)
- central fan type SIF
- system control panel SCP
- round ductwork of the appropriate diameter
1.3 Functional description of SHIELD fire safety
solutions
Fig. 1.1
The SparkShield2(A) spark arrester reduces the risk of sparks,
cigarette butts or other sources of ignition reaching the filter to
an absolute minimum. Inspection hatches1(E) are placed
around the SparkShield to monitor the system and determine
the need for preventive maintenance.
The OilShield2 (F) limestone feeder is placed between the spark
arrester and the filter. Limestone is applied in small quantities
and makes sticky welding fumes behave like dry welding fume,
enhancing filter cleaning and filter cartridge life. The limestone
reduces the risk of fire due to sparks and spontaneous
combustion to a minimum.
The ShieldControl (J) fire detection panel processes the
detection sensor signals, sets the alarm and activates the
PREFACE
TIP
Suggestions and recommendations to simplify
carrying out tasks and actions.
ATTENTION!
A remark with additional information for the user. A
remark brings possible problems to the user’s
attention.
CAUTION!
Procedures, if not carried out with the necessary
caution, could damage the product, the workshop or
the environment.
WARNING!
Procedures which, if not carried out with the necessary
caution, may damage the product or cause serious
personal injury.
WARNING!
Denotes risk of electric shock.
WARNING!
Fire hazard! Important warning to prevent fire.
Abbreviation Meaning
EOL
- EOL resistor
- EOL diode
end of line
- end of line resistor
- end of line diode
REOL end of line resistor
DEOL end of line diode
RAL alarm resistor
1 INTRODUCTION
Refer to the available product data sheets for detailed
product specifications.
1. Not required for dry welding and cutting fumes. Refer to the design
recommendations as stated in the available application data sheet.
Refer to the available application data sheet for design
recommendations and selection tables.
2. Refer to separate literature.

0507347110/160114/B SHIELD fire safety solutions (5k1) | GENERAL | EN - 3
suppression system. In case of alarm, a fire alarm sounder
(K) will go off. Operational reliability in the event of a power
failure is assured by a battery pack. To secure the overall
functionality, ShieldControl monitors open or short circuit of
wiring loops of detectors and the suppression system.
When a fire is detected, the system can be activated manually
at the manual call point (L).
Automatic detection is triggered by heat, sparks or smoke. The
filter is fitted with heat detectors (H) above the dustbin and at
the top of the filter. Spark detectors (C) are placed near the
filter outlet and in the duct after the filter. A smoke detector
(D), suitable for air ducts, is placed in the duct after the filter.
The inlet and outlet duct of the filter are fitted with pneumatic
sliding valves (B). If there is a fire, the valves close and cut off
the oxygen, thereby choking it. This constrains the risk of
escalation. When the extraction system is switched off, the
valves are closed as well to create a safe situation. The valves
have reed contacts to monitor the closing function; the filter
system software runs a periodic check.
The filter is fitted with one or more FlameShield (I) aerosol fire
extinguishing generators. The generators are placed directly in
the filter housing and do not require plumbing. FlameShield
requires no maintenance and has a service life of 10 years. If
there is a fire, FlameShield is activated by the fire detection
panel after the sliding valves have closed. FlameShield self
activates at 300°C (572°F). Fire suppression is rapidly achieved
through interference between the aerosol and the flames’ free
radicals, terminating propagation of the fire. The aerosol
remains active during 30 minutes after activation, thus
preventing re-ignition. The amount of aerosol is proportional to
the filter volume and can be easily adapted by adding
generators.
The system control panel SCP (M) controls the filter and fan
operation. If there is a fire, it will get a signal from the fire
detection panel and close the sliding valves, stop the fan and
shut off the supply of compressed air. The filter compressed air
connection is fitted with a solenoid valve (G) that will allow the
compressed air tanks to depressurize outside of the filter and
prevent any fresh oxygen from reaching the fire.
Fig. 1.1
1.4 System maintenance
The entire system including the ShieldControl panel must be
tested periodically in accordance with the national fire
protection association requirements or the authorities having
local jurisdiction.
The maintenance and testing procedure of the separate
components is described in the relevant chapter.
General instructions
If maintenance is required to any detector, the filter system or
peripheral equipment, proceed as follows.
• Isolate the FlameShield module(s).
After maintenance:
• Follow commissioning instructions.
• Make sure switch of ShieldControl panel is in RUN mode.
Refer to the available application data sheet about
SHIELD fire safety solutions for more detailed
information.
A
EF
D
H
C
B
J
GL
K
IM
ATTENTION!
Prior to performing any test:
- notify the local fire brigade that you will be testing
the fire safety system, especially when the
installation is connected to the brigade control room
- inform all other parties involved, e.g. staff, fire
safety coordinator, alarm monitoring department/
company
Testing the system may lead to acoustic fire alarm
without activating the fire suppression method.
WARNING!
Not isolating the FlameShield module(s) will cause
accidental activation of the fire suppression method.
WARNING!
Not having the ShieldControl panel in RUN mode will
disable automatic fire detection and extinguishing
when the system is in operation.

0507347110/160114/B SHIELD fire safety solutions (5k1) | GENERAL | EN - 4
General
The manufacturer does not accept any liability for damage to
the product or personal injury caused by ignoring of the safety
instructions in this manual, or by negligence during installation,
use, maintenance, and repair of the product mentioned on the
cover of this document and any corresponding accessories.
Specific working conditions or used accessories may require
additional safety instructions. Immediately contact your
supplier if you detect a potential danger when using the product.
The user of the product is always fully responsible for
observing the local safety instructions and
regulations. Observe all applicable safety instructions
and regulations.
User manual
- Everyone working on or with the system, must be familiar with
the contents of this manual and must strictly observe the
instructions therein. The management should instruct the
personnel in accordance with the manual and observe all
instructions and directions given.
- Never change the order of the steps to perform.
- Always keep the manual with the system.
Pictograms and instructions on the products (if
present)
- The pictograms, warning and instructions attached to the
products are part of the safety features. They must not be
covered or removed and must be present and legible during
the entire life of the products.
- Immediately replace or repair damaged or illegible
pictograms, warnings and instructions.
Users
- The use of this system is exclusively reserved to well
authorised, trained and qualified users. Temporary personnel
and personnel in training can only use the system under
supervision and responsibility of skilled engineers.
- The system is not to be used by children or persons with
reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given
supervision or instruction.
- Children must be supervised not to play with the system.
Intended use1
The system has been designed exclusively for reducing the risk
of filter fires. In the event of fire, it detects and suppresses fires
at an early stage, thus minimising consequential damage. Using
the system for other purposes is considered contrary to its
intended use. The manufacturer accepts no liability for any
damage or injury resulting from such use. The product has been
built in accordance with state-of-the-art standards and
recognised safety regulations. Only use this system when in
technically perfect condition in accordance with its intended use
and the instructions explained in the installation manual.
Intended use is limited to fire risk and does not involve
explosion risk.
Technical specifications
The specifications given in this installation manual must not be
altered.
Modifications
Modification of (parts of) the product is not allowed.
Product combinations
Since the products are used in combination with other products
and machines, the safety instructions in the documentation of
these products also apply.
Installation
- The installation of these products is exclusively reserved to
well authorised, trained and qualified engineers.
- Electric connection to be executed in accordance with local
requirements. Ensure compliance with the EMC regulatory
arrangements.
- During installation, always use Personal Protective Equipment
(PPE) to avoid injury. This also applies for persons who enter
the work area during installation.
- Use sufficient climbing gear and safety guards when working
on a higher level than 2 meters (local restrictions may apply).
- Never install any product in front of entrances and exits which
must be used for emergency services.
- Mind any gas and water pipes and electric cables.
- Make sure the wall, ceiling or support system is strong enough
to carry each of the products.
- Ensure the workspace is well illuminated.
- Use common sense. Stay alert and keep your attention to your
work. Do not install the product when you are under the
influence of drugs, alcohol or medicine.
- Make sure that the workshop, in the vicinity of the product,
contains sufficient approved fire extinguishers.
Service, maintenance and repairs
- Observe the maintenance intervals given in this manual.
Overdue maintenance can lead to high costs for repair, false
fire alarm and revisions and can render the guarantee null and
void.
- During service, maintenance and repair jobs, always use
Personal Protective Equipment (PPE) to avoid injury. This also
applies for persons who enter the work area.
- Always use tools, materials, lubricants and service techniques
which have been approved by the manufacturer. Never use
worn tools and do not leave any tools in or on the product.
- Safety features which have been removed for service,
maintenance or repairs, must be put back immediately after
finishing these jobs and it must be checked that they still
function properly.
- Use sufficient climbing gear and safety guards when working
on a higher level than 2 meters (local restrictions may apply).
- Ensure the workspace is well illuminated.
2 SAFETY
1. "Intended use" as explained in EN-ISO 12100-1 is the use for which
the technical product is suited as specified by the manufacturer,
inclusive of his directions in the sales brochure. In case of doubt it is
the use which can be deduced from the construction, the model and
the function of the technical product which is considered normal use.
Operating the machine within the limits of its intended use also
involves observing the instructions in the user manual.
WARNING
Observe the national fire protection association
requirements or the authorities having local
jurisdiction.

0507347110/160114/B SHIELD fire safety solutions (5k1) | GENERAL | EN - 5
The fire suppression system can be
activated in two ways:
- automatically by heat, sparks and/
or smoke detectors
- manually at manual call point
If there is a fire, the automatic
sequence of events is as follows:
- acoustic fire alarm goes off
- fan motor is switched off
- release of compressed air through
solenoid valve
After a delay of ± 5 seconds:
- sliding valves close
- release of aerosol by FlameShield generators during 60
seconds
After activation, the FlameShield aerosol remains active for at
least 30 minutes to prevent re-ignition of the fire. In this way,
damage to the filter installation, as well as consequential loss is
kept to a minimum.
3 OPERATION IN CASE OF FIRE
WARNING!
All staff must be familiar with the fire procedures.

0507347110/160114/B SHIELD fire safety solutions (5k1) | INSTALLATION | EN - 6
ENGLISH
4.1 MDB filter system
Before installing the components of SHIELD fire safety
solutions, make sure the Cart-D filter cartridges of the
connected MDB filter system are properly installed. To check
this, refer to the corresponding manual.
• Securely check the installation of the Cart-D filter cartridges.
4.2 Tools and requirements
- connection wire: 5 x 20 AWG
- connection wire: 5 x 20 AWG shielded cable
- electric drill
- self-tapping screws
- mounting material ShieldControl 5k1
- metal cable glands
- duct support material (depending on weight of sliding valves)
- lifting and climbing gear
- existing duct: angle grinder or jigsaw
4.3 Installation and commissioning
To avoid accidental fire alarms and the activation of FlameShield
fire extinguishing generators, the following installation and
commissioning sequence should be followed. Deviation from
this sequence is allowed, provided the FlameShield module(s)
is/are always the last to be connected, even after having
performed the functional tests.
1. Filter/fan installation
2. System control panel SCP
3. ShieldControl panel (without power)
4. Detectors (heat, sparks, smoke)
5. Valves (sliding valves + solenoid valve)
6. FlameShield fire extinguishing generators (isolated)
• Refer to chapter 13 for extensive commissioning checklist.
4.4 Functional test
To perform any functional test, the following instructions should
be followed.
• Ensure that the FlameShield module(s) is/are isolated.
• Perform detector test. Sound alarm will go off.
• Check fire zone (FIRE IN ZONE).
• Press the SIGNAL SILENCE button on the ShieldControl panel to
suppress alarm.
• Press the SYSTEM RESET button.
To proceed with testing:
• Restart procedure.
If testing has been completed:
• Reconnect the FlameShield module(s).
• Make sure the panel is in RUN mode.
5.1 Product description and operation
ShieldControl 5k1 is a fire detection panel1with a separate
manual call point. It has three detection zones all of which are
capable of activating the FlameShield fire extinguishing
generators.
The fire detection panel makes it possible to connect additional
manual call points.
ShieldControl has two back-up batteries to allow for continuous
operation in the event of power failure.
5.2 Installation
To be sourced locally:
- connection wire: 5 x 20 AWG shielded cable
- mounting material
- metal cable glands
Location
- on the wall or at a convenient location close to the filter
installation
- at eye level
- indoors
Ambient conditions
- Min. temperature: –5°C (23°F)
- Max. temperature: +40°C (104°F)
- Relative humidity: max. 95%
The ShieldControl housing is NEMA 1 rated. It must be shielded
from excessive dust, welding sparks and grinding sparks, if any,
by e.g. an enclosure.
Installation
To install the ShieldControl panel, proceed as follows.
• Mount the ShieldControl panel at all four mounting points.
Use suitable fixtures so that the panel cannot move after it
has been installed.
5.3 Fire alarm sounder
Installation, tone selection and volume control of the fire alarm
sounder are described in the installation manual supplied with
the product.
• Mount the fire alarm sounder at an appropriate position.
• Select the desired tone.
• Adjust the noise to the desired level.
4 INSTALLATION (GENERAL)
WARNING!
Improper installation of the Cart-D filter cartridges will
cause internal leakage and a reduced filter efficiency.
In combination with SHIELD fire safety solutions it can
lead to a false fire alarm.
5 SHIELDCONTROL 5K1
Scope of supply:
- fire detection panel
- battery pack (2)
- fire alarm sounder
- manual call point
- EOL resistor-diode
- detonation simulator
- key (2)
1. UL Standard 862
WARNING
To prevent damage, do not mount the ShieldControl
panel close to sources of excessive heat.

0507347110/160114/B SHIELD fire safety solutions (5k1) | INSTALLATION | EN - 7
5.4 Electrical connection
Fig. 5.3
ShieldControl (D) must be wired to:
- heat detector set(s) (J)
- spark detector set (H)
- smoke detector (I)
- fire alarm sounder (included in ShieldControl package) (C)
- manual call point (included in ShieldControl package) (B)
- system control panel SCP (E)
ShieldControl activates:
- FlameShield fire extinguishing generator(s) (A)
- fire alarm sounder (C)
- system control panel SCP (E)
System control panel SCP (E) activates:
- sliding valves (G)
- solenoid valve (F)
Fig. 5.3
All connections for field wiring are to the terminal strips along
the top and bottom of the PC board.
Cables to be used:
- 5 x 20 AWG shielded cable for detectors and manual call point
- 5 x 20 AWG normal cable for other wiring
The resistance of any core of any cable should not exceed 25
ohm(>1640 ft for 20 AWG).
To connect the cables to the ShieldControl panel, use suitable
metal cable glands fitted to the knock-outs provided.
• Connect all cables to the ShieldControl panel in accordance
with the electrical diagram on page 29.
The wiring of the detectors, manual call point, FlameShield and
fire alarm sounder is monitored for open circuit fault conditions.
5.4.1 Battery packs
The ShieldControl panel is fitted with battery leads wired to the
PC board to connect the two battery packs.
• Place both battery packs inside the ShieldControl panel.
• Connect them to the battery leads.
5.4.2 Mains supply
The mains supply of 115V/230V AC must be connected to a
clean group or to a group that is not connected to equipment
likely to cause frequent power failures.
• Connect the ShieldControl panel to the mains in accordance
with the electrical diagram on page 29.
5.5 Maintenance
The ShieldControl panel itself does not require specific
maintenance except for cleaning. Do not use solvents or
detergents and ensure that water cannot enter the enclosure.
Settings
ShieldControl is programmed for automatic activation of the
FlameShield generators five seconds after one of the detectors
or manual call point has been activated. The activation duration
time is 60 seconds.
5.6 Manual call point
5.6.1 Product description and operation
Manual pull station to activate the fire alarm and fire
suppression system.
Operated by pushing in the bar marked “PUSH” and pulling the
handle marked “PULL” on the front of the unit as far down as it
will go. At that point, the handle will lock in place and will be
easily visible up to 50 feet away.
5.6.2 Installation
Location
- where it will be easy for the operator to reach it
- indoors
5.6.3 Electrical connection
To be sourced locally:
- connection wire: 5 x 20 AWG shielded cable
Fig. 5.1
• Connect the manual call point to Zone 4 of the ShieldControl
panel in accordance with the electrical diagram on page 29.
• Take the EOL resistor 5k ohm mounted in the terminal strip
of Zone 4 and place it in the terminal strip of the manual call
point (A).
WARNING
It is extremely important for the polarity of the
batteries to be connected correctly. Incorrect
connections could damage the ShieldControl panel.
EF
ABC
D
F
JIH
Component Action Frequency:
when-
ever
dirty
every
year
every 4
years
ShieldControl
panel Clean the outside
using a barely damp
cloth.
X
Battery packs Test batteries; POWER
FAULT LED must be off. X
Replace batteries. X
Scope of supply:
- manual call point
-key
ATTENTION
Do not install the manual call point to the connected
filter system. It might not be accessible if there is a
fire.

0507347110/160114/B SHIELD fire safety solutions (5k1) | INSTALLATION | EN - 9
6.1 Product description and operation
Set of two temperature detectors to be installed in the filter
housing. When measuring a temperature of 88°C (190°F) or
more, they give a signal to the connected fire detection panel
ShieldControl to activate the fire suppression system.
6.2 Installation
Location:
Fig. 6.1
- 1st heat sensor: on top of filter housing (A)
- 2nd heat sensor: in hopper just above dustbin (B)
- 1 heat detector set per filter module (# hoppers = # heat
detector sets)
Fig. 6.1
Fig. 6.2
• Mount the heat sensors in the filter housing(s) + hopper(s);
A = housing
B = hopper.
Fig. 6.2
6.3 Electrical connection -Zone 2-
To be sourced locally:
- connection wire: 5 x 20 AWG shielded cable
Wiring
One or more sets of temperature detectors must be wired in
parallel. The detectors act as one sensor and are connected to
Zone 2 (ref. electrical diagram on page 29).
End of line resistor (REOL)
The last detector that is wired to the fire detection panel
ShieldControl must be fitted with an EOL resistor according to
Fig. 6.3. The EOL resistor of the heat detector is supplied with
the fire detection panel and can be found in Zone 2 of the
relevant terminal.
• Take the EOL resistor from Zone 2 of the ShieldControl panel
and place it in the last heat detector according to Fig. 6.3.
Fig. 6.4 shows the first heat sensor without EOL resistor.
Fig. 6.3: Heat sensor with EOL resistor (REOL)
6 HEAT DETECTOR SET
Scope of supply:
- heat detector (2) with
junction box (2)
- cable gland M25 (2)
- nut cable gland M25 (2)
- cable gland M16 (4)
Refer to the available application data sheet about
SHIELD fire safety solutions for the required number
of heat detector sets per filter type.
A
C
A
BB
A

0507347110/160114/B SHIELD fire safety solutions (5k1) | INSTALLATION | EN - 10
Fig. 6.4: Heat sensor no EOL resistor
The EOL resistor makes it possible for the fire detection panel to
monitor the wiring for open circuit.
Alarm resistor
The heat detectors are fitted with a 470 ohm alarm resistor
(RAL) placed in series with the switching contact circuit. The
alarm resistors have no active function but do not interfere with
the functionality of the ShieldControl 5k1 fire detection panel
either. In case of a short circuit it will activate the fire alarm.
• Connect the heat sensors in accordance with the electrical
diagram on page 29. Use shielded cables.
6.4 Functional test
The operation of the heat detectors can be checked in two ways;
by measuring the ohm resistance:
- Gently heat the detectors using a heat gun or heat lamp.
by connecting them to the fire detection panel:
- Gently heat the detectors using a heat gun or heat lamp.
- Check the system status. ShieldControl should indicate a fire
in Zone 2.
To perform the test, proceed as follows.
•Observe the functional testing instructions as
described in paragraph 4.4.
• Functionally test all heat detectors.
• Allow the detectors to cool down.
• Reconnect the heat detectors.
6.5 Maintenance
To be able to operate properly, the heat detectors must be kept
clean. They should be tested periodically in accordance with the
national fire protection association regulations or as directed by
the authorities having local jurisdiction.
• Clean the detectors regularly and gently.
• Test detectors for proper functioning; refer to paragraph 6.4.
• Place detectors back in the filter housing.
Any detector that has been involved in a fire, abused or
damaged must be tested and replaced if necessary.
WARNING
Not using shielded cables can lead to a false alarm by
external high voltage sources and might activate the
alarm.
ATTENTION!
Notify all parties involved that you will be testing the
fire safety system; refer to paragraph 1.4.
WARNING
Do not overheat the setpoint of the detector by more
than 55°C (131°F) because this can change the
default temperature setting.

0507347110/160114/B SHIELD fire safety solutions (5k1) | INSTALLATION | EN - 11
7.1 Product description and operation
Set of two infrared spark detectors. The spark detectors are
sensitive to the near IR light between 0.4 to 1.1 microns
wavelength.
When glowing particulate from the burning filter enters the field
of view of the detector, the detector responds by sending an
alarm to the ShieldControl fire detection panel.
7.2 Installation
Location:
- in filter outlet duct
- face to face (180° apart from each other) in the same vertical
plane
- min. 2,5x duct diameter from bend or branch
The spark detectors can be mounted without having access to
the inside of the duct. In this case you will need the supplied
insertion tool.
In case of a new or disconnected duct allowing access to the
inside, proceed as follows.
Fig. 7.1
• Make a hole Ø 38 mm (1.5 in.) in the duct using the supplied
hole saw.
• Mount the flange (D) in the duct using the split washer (C),
washer (B) and nut (A).
• Tighten washer and nut on the flange.
Fig. 7.1
In case of no access to the inside of the duct, proceed as
follows.
Fig. 7.2
• Make a hole Ø 38 mm (1.5 in.) in the duct using the supplied
hole saw.
• Slip nut (B), washer (C) and split washer (D) on the insertion
tool (A) until the tool fits tightly on the flange (E). The nut
and washer should be loose on the shaft of the tool.
• Push the flange completely through the hole in the duct and
insert the split washer by rotating it into the inside of the
duct.
• Gently pull the flange back through the hole with the
insertion tool so it rests against the split washer inside the
duct.
• Tighten washer and nut on the flange.
• Remove the insertion tool by loosening the wing nut and
pulling straight back and twisting if required.
Fig. 7.2
Fig. 7.3
• Insert the spark detector lens (A) into the flange (C).
• Fasten the detector using the supplied fixation screw (B).
• Follow the same procedure for the second spark detector.
Fig. 7.3
7.3 Electrical connection -Zone 1-
To be sourced locally:
- connection wire: 5 x 20 AWG shielded cable
Wiring
Fig. 7.4
The spark detectors (A) must be wired in parallel in the supplied
junction box (B). Each set consists of one spark detector with
EOL resistor (“EOL”) and one without (“no EOL”), which is
marked on the spark detector housing.
Fig. 7.4
7 SPARK DETECTOR SET
Scope of supply:
- spark detector*) +
fixation screw
- spark detector REOL*)
**) + fixation screw
- junction box
- installation set (hole saw
Ø 38 mm + insertion
tool)
*) with alarm resistor (RAL)
**) with end of line resistor
(REOL)
WARNING
To avoid dirtying the lens, never mount the spark
detectors on the bottom of the duct.
Installation is easier if the inside of the duct is
accessible.
WARNING
To prevent false alarms, ensure that no light can get
between the flange and the duct. Seal any holes with
metal foil. Do not use duct tape since this may let
through infrared light.

0507347110/160114/B SHIELD fire safety solutions (5k1) | INSTALLATION | EN - 12
• Mount the spark detector “EOL” in parallel after the one
without (“no EOL”) according to the electrical diagram on
page 29.
The spark detectors are provided with the following coloured
wires:
• Connect the red and black wire to the 24V auxiliary
connection of the ShieldControl fire detection panel.
• Connect the white and blue wire to Zone 1 of the
ShieldControl panel.
• Connect the green wire to earth/ground.
The EOL resistor over Zone 1 of the ShieldControl panel has
become obsolete and has to be removed because it is already
premounted in the spark detector.
• Remove the EOL resistor over Zone 1.
7.4 Functional test
The easiest way to test the spark detectors is to expose them to
daylight. Both detectors must be tested separately before the
system is put into operation.
To perform the test, proceed as follows.
•Observe the functional testing instructions as
described in paragraph 4.4.
• Loosen the fixation screw and remove one of the spark
detectors. That will expose the sensor to daylight.
• Check the system status. ShieldControl should indicate a fire
in Zone 1.
• Replace the spark detector and fasten it using the fixation
screw.
• Press the SYSTEM RESET button on the ShieldControl panel.
• Follow the same procedure for the other spark detector.
7.5 Maintenance
To be able to operate properly, the spark detectors must be kept
clean. Dirty lenses might influence their sensitivity. Both
detectors must be cleaned and tested periodically in accordance
with the national fire protection association regulations or the
authorities having local jurisdiction.
Cleaning intervals differ per situation and regular checks need
to be performed to set the cleaning interval for your specific
situation.
To clean and test the spark detectors, proceed as follows.
• Make sure the FlameShield module(s) is/are disconnected.
• Loosen the fixation screw and remove one of the spark
detectors.
• Clean the lens gently with a soft cloth or similar. In this way
it is exposed to daylight at the same time (ref. paragraph
7.4).
• Check the system status. ShieldControl should indicate a fire
in Zone 1.
• Replace the spark detector and fasten it using the fixation
screw.
• Press the SYSTEM RESET button on the ShieldControl panel.
• Follow the same procedure for the other spark detector.
If in both cases a fire is detected in Zone 1 of the ShieldControl
panel, the spark detectors are functioning properly. If no
detection takes place, the lens might still be polluted or the
spark detector is broken.
• Clean and test once more.
• If necessary: replace the broken spark detector.
• Reconnect the FlameShield module(s).
Any detector that has been involved in a fire, abused or
damaged must be tested and replaced if necessary.
Colour codes wiring
Red +24 VDC
Black 0 VDC
White 24 V SIGNAL or ZONE +
Blue ZONE –
Brown TEST
Green earth/ground
WARNING
To prevent a malfunction of the spark detector, ensure
that the green earth/ground wire is properly
connected.
WARNING
Failure to remove the EOL resistor over Zone 1 will
disable the monitoring function.
ATTENTION!
Notify all parties involved that you will be testing the
fire safety system; refer to paragraph 1.4.
ATTENTION
The spark detectors must be tested one by one to
make sure they both react to daylight.
WARNING
The FlameShield module(s) must be disconnected to
avoid unintentional activation of the fire suppression
system.

0507347110/160114/B SHIELD fire safety solutions (5k1) | INSTALLATION | EN - 13
8.1 Product description and operation
Detector for smoke detection, based on light scattering by air
sampling tube. The sampling tube transports the air to the
smoke detector. When smoke is detected for more than 30
seconds1, it triggers an alarm. The smoke detector is fitted with
the following features:
Fig. 8.1
A Opening for test spray
B Sensor LED (2);
-LED is off: sensor is OK
- LED is on: sensor must be replaced
C Service indicator: status LEDs that indicate the sensor
contamination;
-green LED is on: sensor is OK
- yellow LED is flashing: sensor is 75% contaminated
- red LED is on: sensor is 100% contaminated
Fig. 8.1
8.2 Installation
The smoke detector is available with two different air sampling
tube lengths, that are suitable for different duct diameters;
Location:
- on filter outlet duct (airflow >1 m/s)
- min. 3x duct diameter before a change in duct direction or
damper; min. 5x duct diameter after these devices
- before or after the sliding valve, whatever is practical
- any position on the duct (top/bottom/front/back)
- in line with the airflow direction; refer to Fig. 8.4.
It is recommended to mount the smoke detector on the front
side of the duct in view of the visibility of the status LEDs. In
case the LEDs are not (clearly) visible, an external light tower
must be installed as additional warning device to indicate the
sensor contamination.
To mount the smoke detector, proceed as follows.
• Drill a hole Ø 51 mm (2 in.) in the duct at the intended
mounting position.
• Determine the correct tube length according to the table
below.
Fig. 8.2
• Remove the end cap (A).
• Shorten the length of the air sampling tube at the side of the
removed end cap;
- do not cut the other side of the tube.
• Reinsert the end cap.
Fig. 8.2
Fig. 8.3
• Put the air sampling tube (C) in the connection tube (B).
• Insert the connection tube in the housing of the smoke
detector.
• Secure the tubes with the locking screw (A).
8 SMOKE DETECTOR
Scope of supply:
- smoke detector
- air sampling tube
- connection tube
- rubber bushing (T600: 1
pc, T1500: 2 pcs)
- mounting bracket
- test spray 250 ml
- cable gland
- locknut
- self-tapping screws
1. Alarm delay time of 30 seconds
The smoke detector enters into alarm when it has detected smoke for
more than 30 seconds continuously. This feature prevents the smoke
detector to be activated unintentionally by fluctuations in filter
efficiency, which makes it pre-eminently suitable for use in filter
systems.
A
B
C
ATTENTION
Particularly in case of a new installation, the inside of
the duct can be polluted, e.g. by remainders of duct
mounting material. Before installation of the smoke
sensor, the duct must be flushed to avoid unnecessary
pollution of the smoke sensor.
Penetration of air sampling
tube through duct ± 90% 100%
Ø 250 mm Ø 10 in. ± 325 mm ± 13 in.
Ø 315 mm Ø 12 in. ± 385 mm ± 15 in.
Ø 400 mm Ø 16 in. ± 460 mm ± 18 in.
Ø 500 mm Ø 20 in. ± 550 mm ± 22 in.
Ø 630 mm Ø 25 in. ± 750 mm ± 29.5 in.
Ø 700 mm Ø 28 in. ± 820 mm ± 32.5 in.
ATTENTION
To prevent the smoke detector from malfunctioning,
the end cap must always be installed.
A
x

0507347110/160114/B SHIELD fire safety solutions (5k1) | INSTALLATION | EN - 14
Fig. 8.3
Fig. 8.4
• Bend the mounting bracket (C) to fit the duct diameter in
question.
• Install the smoke detector housing (A) on the mounting
bracket.
• Put the rubber bushing (D) in the hole of the duct.
Duct diameter < 630 mm (25 in.)
• Insert the air sampling tube (B) through the rubber bushing.
• Install the mounting bracket on the duct with the supplied
self tapping screws. The arrow on the mounting bracket
must correspond with the airflow direction through the duct.
Duct diameter ≥630 mm (25 in.)
• Drill another hole Ø 51 mm (2 in.) in the opposite of the
duct.
• Put the other rubber bushing (E) in the hole of the duct.
• Insert the air sampling tube (B) through both rubber
bushings.
• Install the mounting bracket on the duct with the supplied
self-tapping screws. The arrow on the mounting bracket
must correspond with the airflow direction through the duct.
Fig. 8.4
Post installation checks
• Check that all screws are tightened.
• Check that the airflow direction corresponds with the arrow
on the mounting bracket.
• Check that the test opening is closed by the cap.
8.3 Electrical connection -Zone 3-
To be sourced locally:
- connection wire: 5 x 20 AWG shielded cable
Fig. 8.5
Wiring
The smoke detector must be connected in accordance with the
electrical diagram on page 29. Use shielded cables.
• Connect terminals 14 and 15 of the smoke detector to 24V.
Option:
• Connect terminals 1 and 4 of the smoke detector to the
LightTower.
• Connect terminals COM and NO to Zone 3 of the
ShieldControl panel.
Fig. 8.5
ATTENTION
Protruding of air sampling tube: max. 30 mm (1.2 in.)
(F).
A
C
B
WARNING!
The airflow direction of the smoke detector must be
correct to the ensure proper functioning.
A
B
C
E
F
D
COM
24 V
Zone 3
24 V
AC/DC
NO

0507347110/160114/B SHIELD fire safety solutions (5k1) | INSTALLATION | EN - 15
8.4 Functional test
To verify its functioning, the smoke detector is fitted with an
opening for test spray. To perform the test, proceed as follows.
Fig. 8.6
•Observe the functional testing instructions as
described in paragraph 4.4.
• Turn off the extraction fan.
• Remove the cap of the test opening (A).
• Insert the test spray’s tube into the test opening.
• Release as much test gas as needed to activate the smoke
sensor. In this case, the sensor LEDs (B) light up and the
ShieldControl panel indicates a fire in Zone 3.
Fig. 8.6
The detector resets automatically once the test gas chamber is
free from smoke. The sensor LEDsextinguishes at the same
time.
• Place the cap back on the test opening.
8.5 Maintenance
The sensor wil become polluted over time. When the sensor is
75% contaminated, it must be replaced. This is indicated by the
yellow status LED on the smoke detector and on the LightTower
(option).
• During use, check the sensor LEDs and the status LEDs
regularly.
• Replace the sensor when the yellow LED flashes.
ATTENTION!
Notify all parties involved that you will be testing the
fire safety system; refer to paragraph 1.4.
Smoke detector Sensor
LEDs
Status LEDs / LightTower Action
green yellow red
Standby / OK off on off off -
Trouble:
- sensor 75%
contaminated off on flash off replace
sensor
- sensor 100%
contaminated on off flash on replace
sensor
- removed sensor - flash flash flash place
sensor
ALARM on off off on
A
B
WARNING
Poor maintenance will lead to inadequate sensitivity of
the smoke detector.

0507347110/160114/B SHIELD fire safety solutions (5k1) | INSTALLATION | EN - 16
9.1 Product description and operation
Double activated pneumatic sliding valve with 5/2 solenoid, to
be installed by two pieces (before and after filter system).
When the filter system is in operation the valves are open. In
case of an alarm or power failure or when the fan is switched off
the valves are closed. Correct closing of the valves is monitored
by the reed contact.
In case of fire, the sliding valves close automatically, operated
by pneumatic cylinders. In sequence to a lack of oxygen the fire
is supposed to choke. This will also minimize risk of escalation
or spreading of smoke.
9.2 Installation
Location:
- 1st sliding valve: in filter inlet duct
- 2nd sliding valve: before or after spark and smoke sensors in
filter outlet duct
- to be mounted in vertical position
It is strongly recommended that the sliding valves be installed
indoors. If they are installed outside, however, ensure that they
are protected from rain and snow. Avoid installation where
compressed air can cool down below its dew point to prevent
damage to the pneumatics.
The sliding valves can be mounted:
- during installation of a new ductwork
- in an existing duct
To mount the sliding valves, proceed as follows.
Fig. 9.1
• In case of installation in an existing duct: cut away a piece
of the existing duct as indicated in the table below.
• Slide a connection flange (B) into both duct ends (A).
• Place the sliding valve (D) in between and fasten it using the
quick release clamps (C).
• Fasten the connection flanges using self-tapping screws.
Fig. 9.1
9.3 Electrical connection
To be sourced locally:
- connection wire: 5 x 20 AWG cable
Wiring
• Connect the sliding valves to the system control panel SCP
in accordance with the electrical diagram on page 29.
• Connect the reed contacts to the system control panel SCP
in accordance with the electrical diagram on page 29.
9.4 Compressed air connection
• Connect the sliding valves to a compressed air source.
9 SLIDING VALVES
Scope of supply:
- sliding valve incl. 5/2
solenoid valve, reed
contact, junction box and
cable gland (3)
- connection flange (2)
- quick release clamp (2)
WARNING
Do not mount the sliding valves in horizontal position
to avoid malfunction of the valves.
ATTENTION
Allow sufficient space above the duct for the sliding
valves to fully open;
- SV-10: + 14 in.
- SV-12: + 16 in.
- SV-16: + 20 in.
- SV-20: + 26 in.
- SV-24: + 32 in.
WARNING
Ensure that the ductwork can carry the weight of the
sliding valves. It is recommended to use duct
supports, especially for sliding valves type SV-16/20/
24.
ATTENTION
The sliding valves are equipped with eye bolts for
lifting purposes during installation. The eye bolts
cannot be used to mount the sliding valves
permanently.
Type of sliding valve Duct length to be removed
SV-10 11.6 in. +/- 0.4 in.
SV-12 11.6 in. +/- 0.4 in.
SV-16 11.6 in. +/- 0.4 in.
SV-20 15.0 in. +/- 0.4 in.
SV-24 15.0 in. +/- 0.4 in.
WARNING
The valves must be mounted straight and without
tension on the shell/housing to guarantee airtightness
and to avoid noise by airflow.
WARNING
If applicable, take precautions to ensure that people
are not able to get into the blade's arc of movement.
WARNING
Keep wiring away from places that can become hot
due to fire. Do not use filter or duct as support for
electrical wires.
Compressed air specifications
Compressed air connection 6 mm
Recommended operational pressure 5 bar (max. 9 bar)
Quality dry and oil-free according to
ISO 8573-3 class 6
B
A
B
A
C
D
C

0507347110/160114/B SHIELD fire safety solutions (5k1) | INSTALLATION | EN - 17
Setting closing speed of the sliding valves
The closing speed of the valves can be set by the air pressure.
• Set the closing speed of the valves to 4-5 seconds arranged
by the air pressure.
Do not set the valves to faster than 4 seconds. If there is a fire
alarm, the fan is switched off and the sliding valves are closed.
The 4 seconds give the fan enough time to reduce speed and
prevents damage to the duct by negative pressure. Do not
select speeds slower than 5 seconds either, since the
FlameShield modules are activated 5 seconds after the fire
alarm.
Post installation checks
• Check electrical connections.
• Check pneumatic connections.
• Check bolts and nuts for correct tightening.
9.5 Functional test
The sliding valves can be tested manually by pushing the test
button (A) on the 5/2 solenoid valve.
• Functionally test both sliding valves.
Fig. 9.2
9.6 Maintenance
In order to function properly the sliding valves must be
inspected regularly.
WARNING
Keep the compressed air feed line away from places
that can become hot by fire. Do not use the
compressed air supply from the filter because this will
be shut off in case of fire. Do not use filter or duct as
support for compressed air hoses.
Component Action Frequency:
every 6
months
Pneumatics Check connections. X
Electrical wiring Check connections. X
Bolts and nuts Check for correct tightening. X

0507347110/160114/B SHIELD fire safety solutions (5k1) | INSTALLATION | EN - 18
10.1 Product description and operation
Fig. 10.1
Normally closed 3-way 2-position solenoid valve.
When the connected filter system is in operation, the solenoid is
activated and compressed air is supplied to the cleaning system
of the filter (port P and A are open). If there is a fire alarm or
power failure, the solenoid will return to its normally closed (NC)
position, closing port P and opening port R. In this position
compressed air escapes from the filter and it is unable to
execute a filter cleaning procedure. This prevents fresh oxygen
from reaching the filter in case of fire.
Fig. 10.1
10.2 Installation
Location
The solenoid valve is placed in the main compressed air line
between pressure reducer and filter unit. It is recommended to
mount the valve on the filter housing.
• Mount the solenoid valve at an appropriate position.
10.3 Electrical connection
To be sourced locally:
- connection wire: 5 x 20 AWG
Wiring
• Connect the solenoid valve to the system control panel SCP
in accordance with the electrical diagram on page 29.
10.4 Compressed air connection
The solenoid valve is fitted with a 12 mm compressed air tube
connection.
• Connect the solenoid valve to compressed air.
• Check compressed air connection of filter system.
10.5 Functional test
The solenoid valve is provided with a button for testing
purposes.
• Press button (A) and check that the compressed air escapes
from outlet R (B).
Fig. 10.2
10 SOLENOID VALVE
Scope of supply:
- 3/2 solenoid valve, incl.
electrical entry terminal,
2 swivel elbow adapters
and silencer
- screw M4x35 (2)
- washer M4 (2)
- locknut M4 (2)
A
P
R
A
PR
A
P
R
A
B

0507347110/160114/B SHIELD fire safety solutions (5k1) | INSTALLATION | EN - 19
11.1 Product description and operation
FlameShield1is a fire suppression generator designed to be
installed directly into the filter system. FlameShield is activated
by the ShieldControl fire detection panel 5 seconds after a fire
alarm.
The FlameShield is designed to suppress or extinguish filter fires
of EN 2 Class A and NFPA 10 Class A (normal or solid
combustible material in Plymovent filters).
In 5 to 10 seconds, the filter volume closed by the sliding valves
is filled with a potassium aerosol. This material reacts with the
free radicals in the flame. The free radicals react with the
aerosol instead of the fuel and the chain reaction is stopped
immediately. The residue is a negligible amount of harmless and
stable potassium hydroxide salt (KOH). This reaction also uses
energy from the fire.
After activation the aerosol remains active for at least 30
minutes, which also prevents the fire from starting up again.
11.1.1 Transport and storage
To avoid damage, the following conditions for transport and
storage should be adhered to.
- Do not drop.
- Store between -50 and +100°C (-58 and +212°F).
- Relative humidity during transport and storage: max. 98%.
If FlameShield is stored in accordance with the above-
mentioned conditions, shelf life of the aerosol generator is 15
years.
11.2 Installation
• Refer to Fig. I on page 28 for the required number, type2and
position of FlameShield aerosol generator in MDB filter
system.
Final installation position of FlameShield must be as follows.
Fig. 11.1
A Filter cartridge
B Junction box
C Framework MDB
D Mounting bracket FlameShield
E FlameShield module
Fig. 11.1
To install the FlameShield module(s), proceed as follows.
Fig. 11.2
• Assemble the mounting bracket (part A + B).
• Drill 2 x 2 holes in the framework of the MDB housing in
accordance with the supplied drilling template.
• Mount the junction box (C) along with the mounting bracket
using the supplied bolts, washers and nuts.
• Place a cable gland (F) in the junction box using one of the
knock-out cable entries.
• Guide the cable through the cable gland into the junction
box.
• Place the FlameShield module (E) in the bracket. Make sure
to push the generator to the middle stop (D) to ensure the
correct flow direction of 10°.
• Fasten tightly.
11 FLAMESHIELD
Scope of supply:
- aerosol generator (200
or 500 g)
- mounting bracket (two-
piece)
- junction box
- metal cable gland
- plastic cable gland (2)
- mounting material
1. FlameShield is the name used by Plymovent for the use of FirePro
aerosol generators in Plymovent filter systems. FirePro is a product
of Celanova Ltd. Listing and certifications are registered under the
name FirePro.
2. Number and type of FlameShield aerosol fire extinguishing
generators has been calculated by certified personnel in conformity
with BRL-KZ 3003 and NFPA 2010, based on filter class A, E, safety
factor 1.3 and min. concentration of 55.29 g/m² effective
component.
WARNING
Failure to use the correct number, type and position of
the FlameShield generators will prejudice the effective
fire response.
Use one of the predrilled holes in the junction box
housing to mount it. The box can be mounted using
only one mounting point.
C
AB
MDB
A
D
E
Table of contents
Popular Fire Alarm manuals by other brands

SILENT KNIGHT
SILENT KNIGHT SK-4224 Installation and operation manual

Honeywell
Honeywell SILENT KNIGHT 5860 Product installation document

GST
GST DC-9204E quick start guide

Cranford Controls
Cranford Controls IS-CP4B-PB instruction manual

Cooper Notification
Cooper Notification RSS-241575W instruction manual

Eaton
Eaton CF1100 Installation and operation manual