Premium EDT-150-5191 User manual

OPERATION MANUAL / QUICK GUIDE
MANUAL DE OPERACIÓN / GUÍA RÁPIDA
Specifications are subject to change without notice. These products are not intended for use as critical components in life support or nuclear
systems.
EDT-150-5191

EDT Series
Quick Guide
MA-5191C-1
21-10-2021
2/ 25
www.premiumpsu.com
Powering Your Challenge
1.- INSTALLATION
This is a wall-mounted unit that is cooled by natural convection, so it is necessary to install it in the position
shown in Figure 1. It is important not to cover the ventilation slots so that air can circulate freely.
Spillage and/or leakage of liquids into the equipment through the ventilation grids must be avoided. Care must
also be taken not to introduce objects through these grids that could cause the system to malfunction.
Figure 1. Charger mounting position
Figures 2a and 2b show the wiring of the input voltage, output voltage, temperature sensor and alarms and
Table 1 shows the cable required for the connections.
Figure 2a. Left lateral view Figure 2b. Right lateral view
Function Connection
Minimum
recommended
copper cross-
section
Maximum permissible
copper cross-section
Network input
Phase, Neutral, Earth
1 mm2
2.5 mm2
Battery
Battery +, 4-Battery -
4 mm
2
4 mm
2
Output 12V
Output 1+, Output 1-
4 mm
2
4 mm
2
Output 48V motor
Output 3+, Output 3-
1 mm
2
4 mm
2
Output 48V control
Output 2+, Output 2-
1 mm
2
4 mm
2
Alarms
1-URG, 2-FAU, 3-FAC, 4-NUR, 5-COM
0.25 mm
2
0.5 mm
2
Table. 1. Cable cross-sections for installation

EDT Series
Quick Guide
MA-5191C-1
21-10-2021
3/ 25
www.premiumpsu.com
Powering Your Challenge
2.- LOCAL CONNECTION
To connect locally to the equipment, you must be physically close to the equipment and be able to access it.
Beforehand, you must be able to determine if your device (PC, laptop, etc.) has the appropriate network
configuration to make the connection you want to make and, if so, be able to modify it conveniently. If not,
please ask authorised personnel for assistance. In order to access the charger, you need to know the IP
address of the specific unit. Each device connected to the same network (including the PC or device through
which you want to connect to the charger) must have its own IP address, different to the other devices. Two
circumstances may arise:
The procedure to connect locally without knowing the IP address of the charger would be as follows:
Step
no. 1
Press and hold the “Battery reconnection” button
for more than 10 seconds until all the LEDs start
flashing.
Button and LEDs
Step
no. 2
Connect the PC to the charger’s Ethernet socket.
If the Ethernet socket is connected to another
element (router, switch, etc.), it must be
disconnected and the device must be connected
directly to the charger.
Configure the device with:
IP address: 100.0.0.2
mask: 255.255.255.0
Ethernet socket
Step
no. 3
Optional.
Verify the connection to the charger by pinging
your device to the local IP address (100.0.0.1 by
default). If there is no connection to the charger,
double check all the above steps and ask
authorised personnel for assistance.
PING command successful
IMPORTANT!
BEFORE ANY MANIPULATION OF THE EQUIPMENT, YOU MUST HAVE READ THE USER'S MANUAL
COMPLETELY AND FULLY UNDERSTOOD THE FUNCTIONALITY OF THE EQUIPMENT.
DO NOT TAMPER WITH OR PERFORM ANY ACTION ON THE EQUIPMENT AND/OR ITS
CONFIGURATION WITHOUT BEING ABSOLUTELY CERTAIN THAT
YOU UNDERSTAND THE
IMPLICATIONS OF SAID ACTION.
PLEASE NOTE THAT INCORRECT HANDLING/CONFIGURATION MAY RENDER THE CHARGER
INOPERATIVE AND/OR DAMAGE THE BATTERIES AND EQUIPMENT CONNECTED TO THE
CHARGER.

EDT Series
Quick Guide
MA-5191C-1
21-10-2021
4/ 25
www.premiumpsu.com
Powering Your Challenge
Step
no. 4
Launch the Internet browser and enter the
default local address 100.0.0.1
For further details, see:
Operation manual - Communications
Compatible browsers (PC):
•
Mozilla Firefox (26.0 or higher)
•
Chrome (29.0 or higher)
•
Internet Explorer (11.0 or
higher)
IP address in browser
Step
no. 5
Select the corresponding user and enter the
username and password
To authenticate and access the website
Note: remember that the charger does not
have access to the LDAP server in local
mode, so the username and password are:
User: consulta
Password: consulta
Access screen
Step
no. 6
Perform the outlined operations
For more details, consult:
•Operation manual
•Operation manual - Communications
Web page
During the time that the local IP configuration is active, the unit will indicate this via flashing LEDs.
Before leaving the charger, return the charger to the normal (remote) IP configuration. To do this, press the
"Battery reconnection" button for more than 10 seconds until the LEDs stop flashing and light up as in normal
operation.
In any case, the maximum time in the local IP configuration is 20 minutes; once this time has elapsed since the
change from remote to local, the equipment will automatically reset to the remote IP configuration.

EDT Series
Quick Guide
MA-5191C-1
21-10-2021
5/ 25
www.premiumpsu.com
Powering Your Challenge
3.- REMOTE CONNECTION
Check if your device (PC, laptop, etc.) has the appropriate network configuration to make the connection and, if
necessary, modify it accordingly. If not, please ask authorised personnel for assistance.
In order to access the charger, you need to know the IP address of the specific unit. Each device connected to
the same network (including the PC or device through which you want to connect to the charger) must have its
own IP address, different to the other devices. You must know the IP address of the charger to which you want
to connect. (The following example figures show examples with IP 100.0.0.100 and 100.0.0.0.123, but in your
case you must enter the specific IP address of the charger to which you are connecting. By default, the charger
is configured with a remote IP address 200.0.0.1).
You should also know whether the charger is available from your location, i.e. whether the communications
infrastructure allows you to access the charger. The procedure would be as follows:
Step
no. 1 Connect the device with which it is going to communicate (PC etc.) to the same network as the charger is
connected. You may need to set up specific links on your computer (PPP, VPN, etc.)
Step
no. 2
Optional but recommended.
Verify the connection to the charger by pinging the IP address
of the charger on your device. If there is no connection to the
charger, double check all the above steps and ask authorised
personnel for assistance.
PING command successful
Step
no. 3
Launch the Internet browser and enter the remote address of
the charger.
•
Mozilla Firefox (26.0 or higher)
•
Chrome (29.0 or higher)
•
Internet Explorer (11.0 or higher)
For more details, please refer to the Communications Operation
Manual
IP address in browser
Step
no. 4
Select the user and enter your username and password to
authenticate and access the web page.
Note: if the charger does not have access to the LDAP server,
remember that the username and password would be:
User: consulta
Password: consulta
If you are denied access, verify that you have the required
permissions on the LDAP server and contact authorised
personnel.
Access screen
IMPORTANT!
PRIOR TO ANY MANIPULATION OF THE EQUIPMENT, YOU MUST HAVE READ THE USER'S MANUAL
COMPLETELY AND FULLY UNDERSTOOD THE FUNCTIONALITY OF THE EQUIPMENT.
DO NOT TAMPER WITH OR PERFORM ANY ACTION ON THE EQUIPMENT AND/OR ITS
CONFIGURATION WITHOUT BEING ABSOLUTELY CERTAIN THAT YOU UNDERSTAND THE
IMPLICATIONS OF SAID ACTION.
PLEASE NOTE THAT INCORRECT HANDLIN
G/CONFIGURATION MAY RENDER THE CHARGER
INOPERATIVE AND/OR DAMAGE THE BATTERIES AND EQUIPMENT CONNECTED TO THE CHARGER.

EDT Series
Quick Guide
MA-5191C-1
21-10-2021
7/ 25
www.premiumpsu.com
Powering Your Challenge
4.2.- Most common actions in the viewer profile
The following sections present the most common actions you may wish to perform in the user profile.
4.2.1 View active alarms:
Menu: MAINTENANCE -> Submenu: ALARMS

EDT Series
Quick Guide
MA-5191C-1
21-10-2021
11 / 25
www.premiumpsu.com
Powering Your Challenge
4.2.7 Consult configuration of electrical parameters:
Menu: CONFIGURE -> Submenu: PARAMETERS
4.2.8 Consult configuration of communications parameters:
Menu: CONFIGURE -> Submenu: NETWORK
For more details see the Operation Manual - Communications

EDT Series
Quick Guide
MA-5191C-1
21-10-2021
12 / 25
www.premiumpsu.com
Powering Your Challenge
5.- REPLACING BATTERIES
During the normal life of the charger, it will periodically test the battery to verify its condition. At some point in
the life of the battery, this test will determine that the result has been unsatisfactory and the battery must
therefore be replaced.
Step
no. 1
The “Battery test failure” alarm is
generated, the red “Battery” LED lights
up and the “Urgent failure" relay is
activated.
Step
no. 2
Batteries, even those to be replaced, may contain sufficient energy to pose a danger to the safety of persons and
equipment.
AVOID ANY ACCIDENTAL CONTACT OF THE BATTERY TERMINALS WITH ELECTRICALLY CONDUCTIVE
ELEMENTS.
Step
no. 3
For your safety and that of the equipment, PREMIUM recommends that this operation be carried out with the
equipment completely stopped.
Therefore, proceed to turn off ALL services and uses connected to the charger, disconnect the battery and remove
the AC power supply to the equipment. The charger will shut down completely.
Replace the battery as stipulated in the manual.
Step
no. 4
Make sure that you connect the
battery with the proper polarisation.
Use measuring equipment if required.
Step
no. 5
Proceed to start up the machine. Once
the start-up process has been completed,
all alarms will have disappeared. The
LEDs will indicate that the equipment is
charging the battery.
IMPORTANT!
PRIOR TO ANY MANIPULATION OF THE EQUIPMENT, YOU MUST HAVE READ THE USER'S
MANUAL COMPLETELY AND FULLY UNDERSTOOD THE FUNCTIONALITY OF THE EQUIPMENT.
DO NOT TAMPER WITH OR PERFORM ANY ACTION ON THE EQUIPMENT AND/OR ITS
CONFIGURATION WITHOUT BEING ABSOLUTELY CERTAIN THAT YOU UNDERSTAND THE
IMPLICATIONS OF SAID ACTION.
PLEASE NOTE THAT INCORRECT HANDLING/CONFIGURATION MAY RENDER THE CHARGER
INOPERATIVE AND/OR DAMAGE THE BATTERIES AND EQUIPMENT CONNECTED TO THE
CHARGER.
THE BATTERY TERMINALS PRESENT DANGEROUS VOLTAGES EVEN WHEN THE EQUIPMENT IS
NOT OPERATING. ACCESS TO BATTERIES SHOULD BE LIMITED TO TRAINED PERSONNEL. TO
AVOID POSSIBLE DAMAGE, PLEASE STRICTLY FOLLOW THE INSTRUCTIONS IN THIS MANUAL
AND IN THE USER'S MANUAL.

EDT Series
Quick Guide
MA-5191C-1
21-10-2021
13 / 25
www.premiumpsu.com
Powering Your Challenge
If you are unable to shut down the equipment, follow the steps below or contact the appropriate technical
personnel to guide you through the hot-swap process.
Step
no. 1
The “Battery test failure” alarm is
generated, the red “Battery” LED lights
up and the “Urgent failure" relay is
activated.
Step
no. 2
Batteries, even those to be replaced, may contain sufficient energy to pose a danger to the safety of persons and
equipment.
AVOID ANY ACCIDENTAL CONTACT OF THE BATTERY TERMINALS WITH ELECTRICALLY CONDUCTIVE
ELEMENTS.
Step
no. 3
Disconnect the battery, respecting the safety measures. Make sure that both the battery terminals and the
charger output do not make contact with each other or with any point of the equipment.
Step
no. 4 Force a no-battery test.
Keep the "Battery reconnection" button
pressed for more than 5 seconds and
less than 10 seconds. When the LEDs
are all lit up, release the button and the
test will be forced.
Once the test is completed, the charger
will indicate that there is no battery
connected and will reset the alarms
related to the battery test failure.
Step
no. 5
Connect the battery, making sure
you connect the battery with the
proper polarisation. Use measuring
equipment if required.
Step
no. 6
Once the battery is connected, the
equipment will detect it and once the
process is finished, all alarms will have
disappeared. The LEDs will indicate that
the equipment is charging the battery.

EDT Series
Quick Guide
MA-5191C-1
21-10-2021
14 / 25
www.premiumpsu.com
Powering Your Challenge
1.- INSTALACIÓN
Se trata de un equipo de montaje mural que se refrigera con convección natural, por lo que es necesario
instalarlo en la posición que muestra la figura 1. Es importante no cubrir las ranuras de ventilación para que el
aire pueda circular libremente.
Se ha de evitar el vertido y/o derrame de líquidos al interior del equipo a través de las rejillas de ventilación.
Igualmente se ha de tener la precaución de no introducir objetos por dichas rejillas que pudieran causar el mal
funcionamiento del sistema.
Figura 1. Posición montaje cargador
En las figuras 2a y 2b se observa el conexionado de la tensión de entrada, tensión de salida, sensor de
temperatura y alarmas y en la tabla 1 se indica el cable necesario para las conexiones.
Figura 2a. Vista lateral izquierda Figura 2b. Vista lateral derecha
Función Conexión
Sección de cobre
mínima
recomendada
Sección de cobre
máxima
admisible
Entrada de red
Fase, Neutro, Tierra
1 mm
2
2.5 mm
2
Batería Batería +, 4-Batería - 4 mm24 mm2
Salida 12V
Salida 1+, Salida 1-
4 mm
2
4 mm
2
Salida 48V motor
Salida 3+, Salida 3-
1 mm
2
4 mm
2
Salida 48V control
Salida 2+, Salida 2-
1 mm2
4 mm2
Alarmas 1-URG, 2-FAU, 3-FAC, 4-NUR 5-COM 0.25 mm20.5 mm2
Tabla. 1. Secciones de cable para la instalación

EDT Series
Quick Guide
MA-5191C-1
21-10-2021
15 / 25
www.premiumpsu.com
Powering Your Challenge
2.- CONEXIÓN LOCAL
Para conectarse en local al equipo tiene que estar físicamente cercano al equipo y tener capacidad de acceso a
él. Como paso previo debe de ser capaz de determinar si su dispositivo (PC, portátil,…) tiene la configuración de
red adecuada para realizar la conexión que desea realizar, y en su caso, poder modificarla convenientemente.
Si no es así, por favor solicite ayuda al personal autorizado. Para poder acceder al cargador necesita saber la
dirección IP del equipo concreto. Cada dispositivo conectado a una misma red (incluido el PC o dispositivo a
través del cual desea conectarse al cargador) debe tener una dirección IP propia y diferente del resto de
dispositivos. Pueden darse dos circunstancias:
El procedimiento para conectarse localmente desconociendo la dirección IP del cargador sería el siguiente:
Paso
nº 1
Mantener pulsado durante un tiempo superior a
10 segundos el pulsador “Reconexión Batería”,
hasta que todos los LED empiecen a parpadear.
Pulsador y diodos led
Paso
nº 2
Conectar el PC a la toma Ethernet del cargador.
En caso de que la toma Ethernet esté conectada a
otro elemento (router, Switch…), ésta debe
desconectarse y conectarse directamente el
dispositivo al cargador.
Configurar el dispositivo con:
dirección IP: 100.0.0.2
máscara : 255.255.255.0
Toma Ethernet
Paso
nº 3
Opcional.
Verifique la conexión con el cargador por medio
del comando ping en su dispositivo, a la dirección
IP local (100.0.0.1 por defecto). En caso de no
tener conexión con el cargador, verifique de
nuevo todos los pasos anteriores y solicite ayuda
al personal autorizado.
Comando PING exitoso
¡IMPORTANTE!
ANTES A CUALQUIER MANIPULACIÓN SOBRE EL EQUIPO NECESITA HABER LEIDO
COMPLETAMENTE EL MANUAL DE USUARIO Y COMPRENDIDO EN SU TOTALIDAD LA
FUNCIONALIDAD DEL EQUIPO.
NO MANIPULE O REALICE NINGUNA ACCION SOBRE EL EQUIPO Y/O SU CONFIGURACIÓN SIN
ESTAR COMPLETAMENTE SEGURO DE QUE COMPRENDE LAS REPERCUSIONES QUE DICHA
ACCIÓN ENTRAÑA.
TENGA EN CUENTA QUE UNA MANIPULACIÓN / CONFIGURACIÓN INCORRECTA PUEDE DEJAR NO
OPERATIVO EL CARGADOR Y/O DETERIORAR LAS BATERIAS Y LOS EQUIPOS CONECTADOS AL
CARGADOR.

EDT Series
Quick Guide
MA-5191C-1
21-10-2021
16 / 25
www.premiumpsu.com
Powering Your Challenge
Paso
nº 4
Lance el navegador de Internet e introduzca
la dirección local por defecto 100.0.0.1
Para más detalles ver:
Manual de operación - Comunicaciones
Navegadores compatibles (PC):
•
Mozilla Firefox (26.0 o
superior)
•
Chrome (29.0 o superior)
•
IntenetExplorer (11.0 o
superior)
Dirección IP en navegador
Paso
nº 5
Seleccione el usuario correspondiente e
introduzca el nombre de usuario y
password
Para autenticarse y acceder a la página web
Nota: recuerde que en modo local el
cargador no tiene acceso al servidor LDAP,
por lo que el nombre de usuario y
contraseña son:
Usuario: consulta
Password: consulta
Pantalla de acceso
Paso
nº 6
Realice las operaciones previstas
Para más detalles consulte:
•Manual de operación
•Manual de operación - Comunicaciones
Página Web
Durante el tiempo que esté activa la configuración IP local, el equipo lo indicará con el parpadeo de los diodos
LED.
Antes de abandonar el cargador, vuelva a dejar el cargador en la configuración IP normal (remota). Para ello,
pulsar el pulsador “Reconexión Batería” durante más de 10 segundos, hasta que los leds dejen de parpadear y
se iluminen como en funcionamiento normal.
En cualquier caso, el tiempo máximo para estar en la configuración de IP local es de 20 minutos; una vez
pasado este tiempo desde el cambio, de remoto a local, el equipo se reseteará automáticamente a la
configuración IP remota.

EDT Series
Quick Guide
MA-5191C-1
21-10-2021
17 / 25
www.premiumpsu.com
Powering Your Challenge
3.- CONEXIÓN REMOTA
Compruebe si su dispositivo (PC, portátil,…) tiene la configuración de red adecuada para realizar la conexión, y
en su caso, poder modificarla convenientemente. Si no es así, por favor solicite ayuda al personal autorizado.
Para poder acceder al cargador necesita saber la dirección IP del equipo concreto. Cada dispositivo conectado a
una misma red (incluido el PC o dispositivo a través del cual desea conectarse al cargador) debe tener una
dirección IP propia y diferente del resto de dispositivos. Debe conocer la dirección IP del cargador al que quiere
conectarse. (En las figuras siguientes de ejemplo se muestran ejemplos con las IP 100.0.0.100 y 100.0.0.123,
pero en su caso debe poner la dirección IP concreta del cargador al que se conecta. Por defecto el cargador sale
configurado con una dirección IP remota 200.0.0.1).
Debe conocer igualmente si el cargador está disponible desde su ubicación, es decir, si la infraestructura de
comunicaciones le permite acceder a dicho cargador. El procedimiento sería el siguiente:
Paso
nº 1 Conectar el dispositivo con el que se va a comunicar (PC,…) a la misma red que está conectado el cargador. Puede
ser que necesite establecer enlaces específicos en su ordenador (PPP, VPN, etc….)
Paso
nº 2
Opcional pero recomendado.
Verifique la conexión con el cargador por medio del comando
ping en su dispositivo, a la dirección IP del cargador. En caso de
no tener conexión con el cargador, verifique de nuevo todos los
pasos anteriores y solicite ayuda al personal autorizado.
Comando PING exitoso
Paso
nº 3
Lance el navegador de Internet e introduzca la dirección remota
del cargador.
•
Mozilla Firefox (26.0 o superior)
•
Chrome (29.0 o superior)
•
IntenetExplorer (11.0 o superior)
Para más detalles el Manual de operación de Comunicaciones
Dirección IP en navegador
Paso
nº 4
Seleccione el usuario e introduzca su nombre de usuario y
password, para autenticarse y acceder a la página web.
Nota: si el cargador no tiene acceso al servidor LDAP, recuerde
que el nombre de usuario y contraseña serían:
Usuario: consulta
Password: consulta
En caso de serle denegado el acceso verifique que dispone de
los permisos en el servidor LDAP acuda al personal autorizado.
Pantalla de acceso
Paso
nº 5
Realice las operaciones previstas
Para más detalles consulte:
•Manual de operación
•Manual de operación - Comunicaciones
¡IMPORTANTE!
PREVIO A CUALQUIER MANIPULACIÓN SOBRE EL EQUIPO NECESITA HABER LEIDO
COMPLETAMENTE EL MANUAL DE USUARIO Y
COMPRENDIDO EN SU TOTALIDAD LA
FUNCIONALIDAD DEL EQUIPO.
NO MANIPULE O REALICE NINGUNA ACCION SOBRE EL EQUIPO Y/O SU CONFIGURACIÓN SIN
ESTAR COMPLETAMENTE SEGURO DE QUE COMPRENDE LAS REPERCUSIONES QUE DICHA
ACCIÓN ENTRAÑA.
TENGA EN CUENTA QUE UNA MANIPULACIÓN / CONFIGURACIÓN INCORRECTA PUEDE DEJAR NO
OPERATIVO EL CARGADOR Y/O DETERIORAR LAS BATERIAS Y LOS EQUIPOS CONECTADOS AL
CARGADOR.

EDT Series
Quick Guide
MA-5191C-1
21-10-2021
19 / 25
www.premiumpsu.com
Powering Your Challenge
4.2.- Acciones más comunes en el perfil visualizador
En los siguientes apartados se presentan las acciones más comunes que puede desear realizar en el perfil de
usuario.
4.2.1 Ver alarmas activas:
Menú: MANTENIMIENTO -> Submenú: ALARMAS
Other manuals for EDT-150-5191
1
Table of contents
Languages:
Other Premium Fan manuals