Price Antec controls MVM Series User manual

MULTI-VARIABLE MONITOR
MVM Series
MANUAL v124

MULTI-VARIABLE MONITOR - MANUAL
2 | MVM – Manual | AntecControls.com
TABLE OF CONTENTS
TABLE OF CONTENTS .....................................................................................................................................................................2
INTRODUCTION ...............................................................................................................................................................................3
General..........................................................................................................................................................................................3
Product Overview..........................................................................................................................................................................3
Technical Specifications ................................................................................................................................................................3
GETTING STARTED WITH THE MVM ..............................................................................................................................................4
In the Box......................................................................................................................................................................................4
Standard Configurations................................................................................................................................................................5
Software Installation Instructions................................................................................................................................................14
Connecting to the MVM..............................................................................................................................................................15
ELECTRICAL INSTALLATION.........................................................................................................................................................20
Sample Wiring Diagram...............................................................................................................................................................20
BACnet MS/TP ............................................................................................................................................................................21
MECHANICAL INSTALLATION ......................................................................................................................................................22
Wall Cut-out and Bracket Installation ..........................................................................................................................................22
DISPLAY NAVIGATION...................................................................................................................................................................23
Functionality ................................................................................................................................................................................23
Home Screen ..............................................................................................................................................................................24
MVM Operation...........................................................................................................................................................................25
Settings .......................................................................................................................................................................................26
Login Screen ...............................................................................................................................................................................28
CONFIGURATION...........................................................................................................................................................................29
Before Arriving On-Site ...............................................................................................................................................................29
Accessing the LVIS Configurator File using the LVIS Configurator Software .............................................................................30
Accessing the LVIS Configurator File using a USB Memory Stick..............................................................................................31
BACnet Network Scanning .........................................................................................................................................................33
Adding Data Points to the Device ...............................................................................................................................................36
Adding Data Points to the Main Screen ......................................................................................................................................38
TROUBLESHOOTING.....................................................................................................................................................................40
Replacement Parts......................................................................................................................................................................40
Technical Support........................................................................................................................................................................40

MULTI-VARIABLE MONITOR - MANUAL
3 | MVM – Manual | AntecControls.com
INTRODUCTION
General
In this manual, you will find information regarding:
•Multi-Variable Monitor (MVM) Specifications
•How to install the MVM
•Detailed description of MVM display navigation and
configuration
•Troubleshooting information
Product Overview
The Multi-Variable Monitor (MVM) is a touchscreen monitor that
can be used to display and adjust settings from multiple devices
on a BACnet network. The MVM supports both BACnet MS/TP
and BACnet IP to connect with room level devices.
Some of its key features include:
•Easy-To-Use interface
•Displays any BACnet point including alarm status, room
temperature, humidity, room pressure, air change per hour,
and occupancy
•Connects with multiple devices in order to display critical
information for multiple rooms
•Audible alarms available locally and remotely
•Password protection to change room settings
Technical Specifications
MVM Size 7” 15”
Dimensions 8.8 in. (223 mm) ×6.4 in. (162 mm) ×2.6 in. (65 mm) 15.5 in. (394 mm) ×12.5 in. (318 mm) ×2.6 in. (65 mm)
Display Type Capacitive touch, 7.0 in. (178 mm), TFT, dimmable Capacitive touch, 15.0 in. (381 mm), TFT, dimmable
Resolution 800 px ×480 px, 262144 colors 1024 px ×768 px, 262144 colors
Input Power 24 VAC, 14 VA, Class 2 24 VAC, 25 VA, Class 2
Environmental (Operating) 50°F to 105°F (10°C to 40°C), 10% to 90% R.H. (non-condensing)
Communication Protocol BACnet MS/TP, BACnet IP
Face Glass, IP54
CAUTION
This mark indicates an important point for the proper
function of the MVM. Improper setup may cause unit
failure. Pay close attention to all caution points
throughout this manual.
For local area support, please
contact your local Antec Controls
Representative
For more information visit
www.AntecControls.com

MULTI-VARIABLE MONITOR - MANUAL
4 | MVM – Manual | AntecControls.com
GETTING STARTED WITH THE MVM
In the Box
For each of the available options, the order includes the following components outlined in this section.
Multi-Variable Monitor (MVM)
The following components will be included for both the 7” and 15”
MVM.
Component
Quantity
Description
Multi-Variable
Monitor
1
Single MVM
Mounting
Bracket
(optional)
1
Bracket used to mount the MVM
CAUTION
Please ensure you have all components before
proceeding. Inspect components for shipping damage. Do
not install any components that appear damaged, contact
your local Antec Controls Representative for
replacements.
For the latest information and videos please visit
www.AntecControls.com

MULTI-VARIABLE MONITOR - MANUAL
5 | MVM – Manual | AntecControls.com
Standard Configurations
The below standard configurations are available for the MVM from the factory. These configurations are also available for
download from AntecControls.com.
If a custom graphic is required, please contact your local Antec Controls rep for more information.
One-Room Configurations:
Configuration Type: (1)
Display Points: (RMP-RMT-RMRH)
The following points are included with this standard configuration.
Point
Description
Room Pressure
The current Room Pressure reading.
Room Temperature
The current Room Temperature reading.
Relative Humidity
The current Relative Humidity reading.
Status
Displays the operational state of the room, when
used with the PMT, status will include the following
text. This also displays the appropriate color for the
state, defined below:
1. Normal (GREEN): The room is in its required
pressure range.
2. Setback (BLUE): The room is currently not in use.
3. Caution (YELLOW): The status of the room
should be verified.
4. Alarm (RED): The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Pressure Mode
Indicates whether the room is configured for
Negative or Positive pressurization.
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.
Configuration Type: (2)
Display Points: (RMP-RMT-ACH)
The following points are included with this standard configuration.
Point
Description
Room Pressure
The current Room Pressure reading.
Room Temperature
The current Room Temperature reading.
Air Changes per Hour
The current air change rate in the room.
Status
Displays the operational state of the room, when
used with the PMT, status will include the following
text. This also displays the appropriate color for the
state, defined below:
1. Normal (GREEN): The room is in its required
pressure range.
2. Setback (BLUE): The room is currently not in use.
3. Caution (YELLOW): The status of the room
should be verified.
4. Alarm (RED): The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Pressure Mode
Indicates whether the room is configured for
Negative or Positive pressurization.
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.

MULTI-VARIABLE MONITOR - MANUAL
6 | MVM – Manual | AntecControls.com
Configuration Type: (3)
Display Points: (RMT-RMRH-CO2)
The following points are included with this standard configuration.
Point
Description
Room Temperature
The current Room Temperature reading.
Relative Humidity
The current Relative Humidity reading.
CO2
The current CO2 reading.
Status
Displays the operational state of the room, when
used with the PMT, status will include the following
text. This also displays the appropriate color for the
state, defined below:
1. Normal (GREEN): The room is in its required
pressure range.
2. Setback (BLUE): The room is currently not in use.
3. Caution (YELLOW): The status of the room
should be verified.
4. Alarm (RED): The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Pressure Mode
Indicates whether the room is configured for
Negative or Positive pressurization.
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.
Configuration Type: (4)
Display Points: (RMT-RMRH-ACH)
The following points are included with this standard configuration.
Point
Description
Room Temperature
The current Room Temperature reading.
Relative Humidity
The current Relative Humidity reading.
Air Changes per Hour
The current air change rate in the room.
Status
Displays the operational state of the room, when
used with the PMT, status will include the following
text. This also displays the appropriate color for the
state, defined below:
1. Normal (GREEN): The room is in its required
pressure range.
2. Setback (BLUE): The room is currently not in use.
3. Caution (YELLOW): The status of the room
should be verified.
4. Alarm (RED): The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Pressure Mode
Indicates whether the room is configured for
Negative or Positive pressurization.
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.

MULTI-VARIABLE MONITOR - MANUAL
7 | MVM – Manual | AntecControls.com
Two-Room Configurations:
Configuration Type: (5)
Display Points: (RMP-RMRH)
The following points are included for each room in this standard
configuration.
Point
Description
Room Pressure
The current Room Pressure reading.
Relative Humidity
The current Relative Humidity reading.
Status
Displays the operational state of the room, when
used with the PMT, status will include the following
text. This also displays the appropriate color for the
state, defined below:
1. Normal (GREEN): The room is in its required
pressure range.
2. Setback (BLUE): The room is currently not in use.
3. Caution (YELLOW): The status of the room
should be verified.
4. Alarm (RED): The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.
Configuration Type: (6)
Display Points: (RMP-ACH)
The following points are included with this standard configuration.
Point
Description
Room Pressure
The current Room Pressure reading.
Air Changes per Hour
The current air change rate in the room.
Status
Displays the operational state of the room, when
used with the PMT, status will include the following
text. This also displays the appropriate color for the
state, defined below:
1. Normal (GREEN): The room is in its required
pressure range.
2. Setback (BLUE): The room is currently not in use.
3. Caution (YELLOW): The status of the room
should be verified.
4. Alarm (RED): The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.

MULTI-VARIABLE MONITOR - MANUAL
8 | MVM – Manual | AntecControls.com
Configuration Type: (7)
Display Points: (RMT-RMRH)
The following points are included with this standard configuration.
Point
Description
Room Temperature
The current Room Temperature reading.
Relative Humidity
The current Relative Humidity reading.
Status
Displays the operational state of the room, when
used with the PMT, status will include the following
text. This also displays the appropriate color for the
state, defined below:
1. Normal (GREEN): The room is in its required
pressure range.
2. Setback (BLUE): The room is currently not in use.
3. Caution (YELLOW): The status of the room
should be verified.
4. Alarm (RED): The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.
Configuration Type: (8)
Display Points: (RMT-ACH)
The following points are included with this standard configuration.
Point
Description
Room Temperature
The current Room Temperature reading.
Air Changes per Hour
The current air change rate in the room.
Status
Displays the operational state of the room, when
used with the PMT, status will include the following
text. This also displays the appropriate color for the
state, defined below:
1. Normal (GREEN): The room is in its required
pressure range.
2. Setback (BLUE): The room is currently not in use.
3. Caution (YELLOW): The status of the room
should be verified.
4. Alarm (RED): The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.

MULTI-VARIABLE MONITOR - MANUAL
9 | MVM – Manual | AntecControls.com
Three-Room Configurations:
Configuration Type: (9)
Display Points: (RMP-RMT)
The following points are included with this standard configuration.
Point
Description
Room Pressure
The current Room Pressure reading.
Room Temperature
The current Room Temperature reading.
Status
Displays the operational state of the room, when
used with the PMT, status will include the following
text. This also displays the appropriate color for the
state, defined below:
1. Normal (GREEN): The room is in its required
pressure range.
2. Setback (BLUE): The room is currently not in use.
3. Caution (YELLOW): The status of the room
should be verified.
4. Alarm (RED): The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.
Configuration Type: (10)
Display Points: (RMP-ACH)
The following points are included with this standard configuration.
Point
Description
Room Pressure
The current Room Pressure reading.
Air Changes per Hour
The current air change rate in the room.
Status
Displays the operational state of the room, when
used with the PMT, status will include the following
text. This also displays the appropriate color for the
state, defined below:
1. Normal (GREEN): The room is in its required
pressure range.
2. Setback (BLUE): The room is currently not in use.
3. Caution (YELLOW): The status of the room
should be verified.
4. Alarm (RED): The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.

MULTI-VARIABLE MONITOR - MANUAL
10 | MVM – Manual | AntecControls.com
Configuration Type: (11)
Display Points: (RMT-RMRH)
The following points are included with this standard configuration.
Point
Description
Room Temperature
The current Room Temperature reading.
Relative Humidity
The current Relative Humidity reading.
Status
Displays the operational state of the room, when
used with the PMT, status will include the following
text. This also displays the appropriate color for the
state, defined below:
1. Normal (GREEN): The room is in its required
pressure range.
2. Setback (BLUE): The room is currently not in use.
3. Caution (YELLOW): The status of the room
should be verified.
4. Alarm (RED): The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.
Configuration Type: (12)
Display Points: (RMT-ACH)
The following points are included with this standard configuration.
Point
Description
Room Temperature
The current Room Temperature reading.
Air Changes per Hour
The current air change rate in the room.
Status
Displays the operational state of the room, when
used with the PMT, status will include the following
text. This also displays the appropriate color for the
state, defined below:
1. Normal (GREEN): The room is in its required
pressure range.
2. Setback (BLUE): The room is currently not in use.
3. Caution (YELLOW): The status of the room
should be verified.
4. Alarm (RED): The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.

MULTI-VARIABLE MONITOR - MANUAL
11 | MVM – Manual | AntecControls.com
Four-Room Configurations:
Configuration Type: (13)
Display Points: (RMP)
The following points are included with this standard configuration.
Point
Description
Room Pressure
The current Room Pressure reading.
Status
Displays the operational state of the room, when
used with the PMT, be indicated by the following
colors:
1. GREEN: The room is in its required pressure
range.
2. BLUE: The room is currently not in use.
3. YELLOW: The status of the room should be
verified.
4. RED: The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.
Configuration Type: (14)
Display Points: (RMT)
The following points are included with this standard configuration.
Point
Description
Room Temperature
The current Room Temperature reading.
Status
Displays the operational state of the room, when
used with the PMT, be indicated by the following
colors:
1. GREEN: The room is in its required pressure
range.
2. BLUE: The room is currently not in use.
3. YELLOW: The status of the room should be
verified.
4. RED: The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.
Configuration Type: (15)
Display Points: (ACH)
The following points are included with this standard configuration.
Point
Description
Air Changes per Hour
The current air change rate in the room.
Status
Displays the operational state of the room, when
used with the PMT, be indicated by the following
colors:
1. GREEN: The room is in its required pressure
range.
2. BLUE: The room is currently not in use.
3. YELLOW: The status of the room should be
verified.
4. RED: The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.

MULTI-VARIABLE MONITOR - MANUAL
12 | MVM – Manual | AntecControls.com
Six-Room Configurations:
Configuration Type: (16)
Display Points: (RMP)
The following points are included with this standard configuration.
Point
Description
Room Pressure
The current Room Pressure reading.
Status
Displays the operational state of the room, when
used with the PMT, be indicated by the following
colors:
1. GREEN: The room is in its required pressure
range.
2. BLUE: The room is currently not in use.
3. YELLOW: The status of the room should be
verified.
4. RED: The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.
Configuration Type: (17)
Display Points: (RMT)
The following points are included with this standard configuration.
Point
Description
Room Temperature
The current Room Temperature reading.
Status
Displays the operational state of the room, when
used with the PMT, be indicated by the following
colors:
1. GREEN: The room is in its required pressure
range.
2. BLUE: The room is currently not in use.
3. YELLOW: The status of the room should be
verified.
4. RED: The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.
Configuration Type: (18)
Display Points: (ACH)
The following points are included with this standard configuration.
Point
Description
Air Changes per Hour
The current air change rate in the room.
Status
Displays the operational state of the room, when
used with the PMT, be indicated by the following
colors:
1. GREEN: The room is in its required pressure
range.
2. BLUE: The room is currently not in use.
3. YELLOW: The status of the room should be
verified.
4. RED: The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.

MULTI-VARIABLE MONITOR - MANUAL
13 | MVM – Manual | AntecControls.com
Eight-Room Configurations:
Configuration Type: (19)
Display Points: (RMP)
The following points are included with this standard configuration.
Point
Description
Room Pressure
The current Room Pressure reading.
Status
Displays the operational state of the room, when
used with the PMT, be indicated by the following
colors:
1. GREEN: The room is in its required pressure
range.
2. BLUE: The room is currently not in use.
3. YELLOW: The status of the room should be
verified.
4. RED: The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.
Configuration Type: (20)
Display Points: (RMT)
The following points are included with this standard configuration.
Point
Description
Room Temperature
The current Room Temperature reading.
Status
Displays the operational state of the room, when
used with the PMT, be indicated by the following
colors:
1. GREEN: The room is in its required pressure
range.
2. BLUE: The room is currently not in use.
3. YELLOW: The status of the room should be
verified.
4. RED: The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.
Configuration Type: (21)
Display Points: (ACH)
The following points are included with this standard configuration.
Point
Description
Air Changes per Hour
The current air change rate in the room.
Status
Displays the operational state of the room, when
used with the PMT, be indicated by the following
colors:
1. GREEN: The room is in its required pressure
range.
2. BLUE: The room is currently not in use.
3. YELLOW: The status of the room should be
verified.
4. RED: The room is outside of it’s required
pressure range.
Alarm/Caution Reason
Indicates to the user the reason for the caution or
alarm status (if present).
Room Mode Override
Allows the user to change the room to Setback.
NOTE: The standard configuration does not include
password protection for this item.

MULTI-VARIABLE MONITOR - MANUAL
14 | MVM – Manual | AntecControls.com
Software Installation Instructions
System Requirements
System requirements to program the MVM:
•Operating System: Windows 7 or higher
•CPU: 2 Gigahertz or faster
•RAM: 4 Gigabytes or more
•Hardware: Ethernet port or USB port and USB to Ethernet
adapter
LVIS Configurator Install Instructions
Use the following instructions to download the LVIS Configurator
from the Antec Controls website.
•Ensure an internet connection is present.
•Go to https://anteccontrols.com and enter the login section.
oIf you do not have login access, please request an
account.
•Enter the
Resources
tab.
•Go to
Software
MVM Configurator
•Select the web icon beside
Software
to navigate to the
LOYTEC website
•Run through the InstallShield Wizard for LOYTEC LVIS
Configurator.

MULTI-VARIABLE MONITOR - MANUAL
15 | MVM – Manual | AntecControls.com
Connecting to the MVM
Tools required
•Laptop
•Ethernet Cable (RJ-45 to RJ-45)
•LVIS Software
•Power wired into the MVM
Physical Connection
Connect one end of the RJ-45 cable into the bottom of the MVM
and the other end into the Ethernet port of your computer

MULTI-VARIABLE MONITOR - MANUAL
16 | MVM – Manual | AntecControls.com
Connection Instructions
The following steps will allow the user to connect to a Multi Variable Monitor (MVM)
STEP 1
Open the Ethernet settings on your computer and select
Change
adapter options.
STEP 2
Select the Ethernet port to which the MVM is connected.
NOTE: In this case Ethernet 2 is selected. The Ethernet port may
be different on the user’s computer. Ensure to configure the
settings for the Ethernet port to which the MVM is physically
connected.
STEP 3
In the Ethernet status menu select
Properties
.

MULTI-VARIABLE MONITOR - MANUAL
17 | MVM – Manual | AntecControls.com
STEP 4
Enter the
Internet Protocol Version 4 (TCP/IPv4)
menu.
STEP 5
Select
Use the following IP address
.

MULTI-VARIABLE MONITOR - MANUAL
18 | MVM – Manual | AntecControls.com
STEP 6
Go to the TCP/IP menu in the MVM. Ensure that DCHP is turned
off.
Record the address and netmask from the top of the menu. In
this case:
Address: 010 000 042 013
Netmask: 255 255 255 000
Gateway: 010 000 042 001
User Recording Table:
Address
Netmask
Gateway
NOTE: Ensure that the first three numbers of the gateway
(010 000 042 ***) match the address on the MVM.
STEP 7
Enter the IP address but with the final three digits one number
greater or lower than the MVM address.
In this case:
IP Address: 010 000 042 014
NOTE: The final three digits of the IP Address MUST be different
from the MVM’s IP Address.
STEP 8
Open the LVIS Configurator software.

MULTI-VARIABLE MONITOR - MANUAL
19 | MVM – Manual | AntecControls.com
STEP 9
Select the
Connection
drop down at the top of the screen and
select
Connect to Device
.
STEP 10
Ensure that
Use HTTP connection
is selected.
Enter the IP address that was recorded from the TCP/IP menu of
the MVM in STEP 6.
Enter the Admin Password: loytec4u
NOTE: This password will be saved and only needs to be
entered the first time you connect to an MVM.
STEP 11
The status bar will display “Loading Dynamic Points List” and
then display “DP Connection, 10.0.42.13” once you have
successfully connected.
NOTE: The user’s IP address will be different than what is used
here.

MULTI-VARIABLE MONITOR - MANUAL
20 | MVM – Manual | AntecControls.com
ELECTRICAL INSTALLATION
Sample Wiring Diagram
NOTES:
1. For further information, please see the BACnet MS/TP section of the manual.
2. All wire connections to the monitor screw connection terminals must be between 12-26 AWG wire.
3. Current and voltage drop should be taken into consideration when selecting wire gauge.
4. Wiring above may not reflect those required for your project. Refer to your Antec Controls Project Submittals for project
specific wiring diagrams.