PUFF Alert-C User manual

‘No Smoking’ detector
● 3-level sensitivity photoelectric technology
● High intelligence with microprocessor
● Ultra life lithium battery
● Remote Indicator attached
Introduction
The Puff Alert-C No Smoking Detector is a high-sensitivity detector
based on photoelectric technology, which senses cigarette, cigar and
pip tobacco smoke at an early stage and warns by means of a buzzer
and a red light-emitting diode.
A remote indicator is also available for easy of centralized
identification.
Product characteristics
Smoke sensing
Every detector is separately calibrated in order to avoid false alarms.
The detector is electronically regulated internally, thereby maintaining
a constant sensitivity of the alarm.
The detector has 3 levels sensitivity.
1. High sensitivity
2. Normally sensitivity
3. Low sensitivity
Monitoring
A red light-emitting diode located (LED) on the top cover indicates
different function state of the detector.
The LED flashes once per 45 seconds signals that the device is in
monitoring state and is functioning correctly.
Battery-warning
The Puff Alert-C manages the battery automatically. When the battery
runs low, the detector turns into Low-battery state.
The detector emits a short beep warning sound, synchronous with the
LED blinking per 45 seconds, signalling the Low-battery state. The
detector will continue to function for up to 1 month under Low-battery
state.
Fully automatic test function
Advanced electronics ensure the best possible operating readiness by
means of an automatic self-test function.
In case of failure, the detector gives out a fault signal by means of 3
beeps every 35 seconds, synchronous with the LED blinking.
Smoke Alarm
When Puff Alert-C detects small amounts of cigarette, cigar or pipe
tobacco smoke, and the concentration of smoke reaches the alarm
threshold, the detector then turns into alarm state.
There are two styles of alarm signals, selected via the Button (see
below), one is quick, one is slow.
In quick style, the buzzer beeps once per second, synchronous with the
LED blinking.
In slow style, the buzzer beeps once every three seconds, synchronous
with the LED blinking.
Interconnection
The Puff Alert-C supplies an interconnection function, which allows
the alarm signal to be transferred from one to another.
When a detector is in Interconnection Alarm, the Buzzer emits 3 beeps,
then a obvious space, then 3 beeps, circularly. The LED keeps off.
Multi-function Button
A multi-function button is located on the top cover, which supplies
operations bellow.
1. Manual Test
When the detector is in monitoring state, press the button for
more than one second, the detector will turn into Test mode,
which is similar to the Smoke Alarm mode. And after a short
while, the detector turns back to monitoring mode again.
2. Hush
When the detector is in Smoke Alarm state and sounds an audible
voice, press the button for less than half a second, the detector
will stop the audible voice.
3. Sound Style Selection
When the detector is in monitoring state, press the button for less
than half a second, will change the sound style of the Smoke
Alarm from quick to slow or reversed.
Remote Indicator
A remote indicator is also available for easy of remote identification.
When Puff Alert-C is in Smoke Alarm state, The Remote Indicator
operates similar to that of the LED and the Buzzer which is located the
detector.
Placement Location
•Should be mounted on the ceiling in areas selected for No
Smoking.
•One device for every 65 cubic metres approximately. The
minimum requirement for large areas request advice from your
product supplier.
•For complicated or extensive properties please request qualified
advice from your product supplier.
The following locations shall be avoided:
•Next to doors, windows, ventilators etc. where draughts can
deviate smoke from the sensor.
•In small or poorly ventilated garages or kitchens where waste
gas or vapours may cause false alarms.
•In areas where dust and dirt can interfere with the operation or
cause false alarms.
•In areas where insects or vermin may effect the integrity of the
alarm.
•In damp or humid areas (e.g. in the bathrooms).
•In areas where the temperature may often fall below –5°C or
exceed +38°C.
Installation
•Drill two horizontal holes 5 diameter, 22mm deep, 58 mm apart,
where is intended to install the detector.
•Insert the enclosed plastic plugs into the holes.
•Separate the base plate and detector by rotating
counterclockwise.
•Place the base plate so that the two long slot-holes s are aligned
to the plastic plugs inside the ceiling. Fasten the base plate on
the respective surface using the enclosed screw.
•Open the battery lid of the detector, Clip the battery lead to the
9V lithium battery, ensuring the correct polarity, and insert the
battery in the space provided. Then close the battery lid.
•Push the detector onto the mounting bracket perfectly. and turn
it clockwise to align the side slot of the bracket and the detector.
Make sure the detector is firmly locked.
•Fig.1 Installation

Remote Indicator and Interconnection Wiring
A connecter inside the bottom of the detector supplies wiring terminals
for the optional Remote Indicator and Interconnection function.
Figure 2 shows the wiring of the Remote Indicator and/or
interconnection.
Fig.2 Wiring of the Remote Indicator and/or interconnection
Testing
After installation, a test operation is a must to ensure that the detector
works properly.
Press the Multi-function Button continuously at least 1 second for a
Manual Test. The buzzer should beep and the LED should flash as
described in the Manual Test section.
If the horn does not beep or if the LED does not flash, please do check
the following points:
•Is the detector damaged?
•Is the detector clean?
•Are the batteries working properly? Are you using the required
battery types? Are the batteries connected properly? Replace the
batteries if necessary.
If the detector is still not working, do not attempt to repair it but
contact a professional.
False alarms
In case of false alarm, please check if the air around the detector is
clear. Fan the air around the smoke alarm if necessary, until the alarm
turns off. If the false alarm occurs frequently or continuously, Please
consider of maintenance.
Maintenance
Periodic maintenance contributes to a long service life of the Puff
Alert-C and ensures a failure-free operation.
•Clean the outside cover with a damp cloth at least every three
months (do not use any detergent!).
•Vacuum the outside cover and vents every three months. Never
let the vacuum cleaner come in contact with the interior parts of
the smoke alarm.
Please note!
The Puff Alert-C requires sufficient power to operate.
•Please use the appropriate type of branded batteries, used only
9-volt lithium battery for the smoke detector
•Please check the polarity of the battery carefully.
•Please verify that the smoke alarm is working properly
immediately after replacing the batteries.
•In case of the Battery Warning signal, replace the 9-volt battery
immediately. Otherwise please change it at least once per year.
•Puff Alert-C is designed for ceiling mount only.
General
Puff Alert-C will activate the sound warning when it detects cigarette,
cigar or pipe smoke. Everything preventing the smoke from reaching
the alarm obstructs an early alarm.
A single detector provides only limited coverage and you should
consult the supplier if a large area of detection is desired.
FIVE YEAR LIMITED WARRANTY
NOTE: In order to protect your right, please keep the original
purchase receipt for the proof of buying GLT Puff-Alert detector
from our authorized dealers. No warranty can be offered without the
original purchase receipt.
GLT warrants enclosed Smoke Detector - but not the battery – to be
free from defects in materials and workmanship under normal use and
service for a period of five years from date of purchase. GLT makes no
other express warranty for this smoke detector. No agent,
representative, dealer, or employee of the Company has the authority
to increase or alter the obligations or limitations of this Warranty. The
Company’s obligation of this Warranty shall be limited to the repair or
replacement of any part of the detector, which is found to be defective
in materials or workmanship under normal use and service during the
five year period commencing with the date of purchase. During the
initial one-year period commencing with the date of purchase, such
repair or replacement shall be made without charge. During the latter
four years of the Warranty period, such repair or replacement shall be
made at a charge to the Customer not to exceed the manufacturer’s
cost. Units in need of repair should be returned, shipping prepaid, to
Customer Service Department, GLT.
The Company shall not be obligated to repair or replace units, which
are found to be in need of repair because of damage, unreasonable use,
modifications, or alterations occurring after the date of purchase. The
duration of any implied Warranty, including that of merchantability or
fitness for any particular purpose, shall be limited to the period of five
years commencing with the date of purchase. In no case shall the
Company be liable for any consequential or incidental damages for
breach of this or any other warranty expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or
fault. Some states do not allow the exclusion or limitation of incidental
or consequential damages, so the above limitation or exclusion may
not apply to you. GLT makes no warranty, expressed or implied,
written or oral, including that of merchantability or fitness for any
particular purpose, with respect to the batteries. This warranty gives
you specific legal rights, and you may also have other rights which
vary from state to state
This manual suits for next models
1
Table of contents
Popular Security Sensor manuals by other brands

Trebs
Trebs 99707 manual

Velleman
Velleman PIR500 user manual

Optex
Optex HX-40/40AM Installation insrtuctions

Petzl
Petzl William Series TECHNICAL NOTICE

Endress+Hauser
Endress+Hauser Prosonic FDU83 Safety instructions for electrical apparatus certified for use in explosion-hazardous areas

schmersal
schmersal ZQ 700 operating instructions