QEED QA-TEMP User manual

01 2015
UNIVERSAL TEMPERATURE CONVERTER
I4 way isolated - RS485 MODBUS- Datalogger QA-TEMP
UNIVERSAL TEMPERATURE CONVERTER
4 way isolated - RS485 MODBUS- Datalogger QA-TEMP
Power
Fail
Rx
Tx
Dout
USB
OTG
QA-TEMP
QEED
Advanced UNIVERSAL TEMPERATURE CONVERTER,USB
configurable,DIN rail mounting, 4-way galvanically isolated,
universal power supply AC/DC, Programmable alarm contact,
RS485 Modbus.
DATALOGGING via USB with pen drive stick memory and
download storage data on excel importable files. RTC Real Time
Clock integrated. RTD,TC and POTENTIOMETER CONVERTER.
Temperature
Sensor
INPUT
TEMPERATURE:
RTD: Pt100, Pt500, Pt1000, Ni100. 2, 3 or 4 wire measure, automatic detection of
cable interruption.
TC Types: J, K, R, S, T, B, E, N; automatic detection of cable interruption.
POTENTIOMETER: from 1000 Ohm to 10 KOhm.
RESISTANCE: resistance measurement 400ohm or 4000 ohm to 2, 3, 4 wires.
OUTPUT
CURRENT: 0...20mA programmable, max load resistance 600 ohm.
VOLTAGE: 0...10V programmable, min load resistance 2 kohm.
CONTACT ALARM: 5A 230Vac SPDT relay fully programmable by FACILE QA-
TEMP.
RS485 MODBUS: Bus connection on the base of module by adapter (option) or
on terminals. Dip-switch for setting address and baudrate.
109 2015
Analog output
Contact Alarm
RS485 Modbus
DATALOGGER
POWER SUPPLY
RETRASMISSION OUTPUT
PROTECTION INDEX
10..40 Vdc, 20-28 Vac, 50-60 Hz
On isolated analog output,
ABSORPTION Maximum 2 VA
IP20
16 bit
50-60 Hz
< 100 ppm/°C
-15...+65°C
-40°C... +85°C
0,1% F.S.
Voltage and Current (impressed) programmable; Active
or Passive supply output 13 Vdc 30mA max
ACCURACY
RESOLUTION
REJECTION
THERMAL STABILITY AT 25°C
WORKING TEMPERATURE
STORAGE TEMPERATURE
ISOLATION Input, analog and digital output,
serial output RS485 and USB port, Power supply, are
4-way galvanically isolated at 1,5kV
OnTheGo port by Pen Drive stick memory. The software
FACILE QA-TEMP (free of charge) allow you to configure
Log, all conversion parameters, set contact alarm, set
Modbus address. RTC Real Time Clock integrated
By free software FACILE QA-TEMP to configure all of the
conversion parameters like span, zero, alarm contact and
log via USB port or via RS485. Dip-switch for setting
modbus address and baudrate
CONFIGURATION
EN61000-6-4/2006 + A1 2011;
EN64000-6-2/2005; EN61010-1/2010
17,5x 100 x 112 mm (terminals excluded)
Up to 2000 m s.l.m.
HUMIDITY 10...90% non condensing
ALTITUDE
MOUNTING
Removable terminals 5,08mm
CONNECTIONS
CE STANDARDS
DIMENSIONS
Non-volating memory. Log on USB
DATA LOGGER
DIN rail mounting with removable
terminals, RS485 bus and Supply connection ready on
the base of module (connector not included, on
request).
ENGLISH

INSTRUCTION MANUAL QA-TEMP
INSTRUCTION MANUAL QA-TEMP
209 2015
ELECTRICAL CONNECTIONS:
DESCRIPTION:
The QA-TEMP is an Universal Temperature Converter, 4-ways isolated, with one analog input (temperature,
potentiometer, resistance) and three different outputs. The module has a programmable analog output (voltage or
current), one digital output (5A SPDT relay) and one serial RS485 slave output. Thanks to the presence of the RS485 serial
port, the device can perform advanced functions such as I / O Module with Modbus RTU protocol. The QA-TEMP behaves
as a slave device by placing n°1 RTD/ TC input , n°1 AO, n°1 DO.
POWER SUPPLY:
10...40 Vdc or 20...28 Vac - Connectors 16 and 17, or by T-BUS
connector (optional tool) on the base of the module (see the
picture placed on the bottom of this page).
ANALOG INPUT TEMPERATURE SENSORS CONNECTION:
Depending on the type of sensor or signal available, make the
connection as shown. For example, to connect a 3-wire RTD
sensor requires a connection to terminals 3, 4 and 6. The Thermo-
couple, whatever it is, it requires the connection between termi-
nals 3 and 4.
To connect a potentiometer use terminals 3, 4 and 6.
To make resistance measurements at 2, 3 and 4 wires to follow
the wiring diagram for the RTD.
ANALOG OUTPUT:
For the voltage analog output, connect terminals 31 and 29
(positive).
For the ACTIVE current analog output, connect terminals 29
(positive) and 30.
For the PASSIVE current analog output, connect terminals 30
(positive) and 31.
Analog output supply: 13 Vdc, max 30mA.
DIGITAL OUTPUT:
SPDT Relay Output. Connect the terminals 25 Normally Open and
27 Normally Closed. The default setting is Normally Open (NO).
SERIAL OUTPUT RS485 Modbus RTU:
Available on terminals 32 GND, 33 (B-), 34 (A+), or by using T-BUS
connector to be mounted on the base of the module. To configure
the device use the software FACILE QA-TEMP or by direct
connection via RS485 using the Modbus register map shown in
this manual.
T-BUS CONNECTION (T-BUS connector required):
It is possible to mount the accessory T-BUS to carry both power
and serial communication. The number of modules supported by
the function of the power supply bus is used (check the absorption
of the modules).
ENGLISH

PROGRAMMING THE DEVICE BY SOFTWARE FACILE QA-TEMP
It is possible to use the program without connecting
to the module, in this mode you can SAVE the
configuration on your PC, which can then be sent to
the QA-TEMP at a later time.
SERIAL PORTS AVAILABLE:
Check the available COM ports, press the UPDATE
button. Your PC will assign a virtual COM connection
with the QA-TEMP. Press START CONNECTION WITH
THE DEVICE. It will confirm you the connection was
successful with the module. If the connection does not
happen, please check the RS485 serial connection (A
+, B-), the position of the dip-switches (switching off
and on the device) and the COM generated
automatically by the device.
After connecting, you can proceed with the
configuration of the device.
ANALOG INPUT:
you will find the pull-down menu where you can select
the type of input signal: POTENTIOMETERS,
RESISTANCE at 400ohm or 4kohm at 2,3,4 wires, Ni100,
PT100, PT500, PT1000 at 2,3,4 wires, TC type J, K, R, S,
T, B, E, N.
The QA-TEMP sampling data every 100 msec, you can
choose to mediate the input value up to a maximum
of 32 samples.
PROGRAMMING THE DEVICE BY SOFTWARE FACILE QA-TEMP
309 2015
The programming of the module QA-TEMP may be performed in two different ways:
· via the interface program free FACILE QA-TEMP through the microUSB port on the module or via RS485
connection;
· via the RS485 serial connection (from terminal or T-Bus).
The QA-TEMP has two microprocessors, you can configure the module by connecting it to the USB port of your PC
without the power lead, this is possible because the microprocessor that manages the configuration is powered
directly from the USB port.
To use the program FACILE QA-TEMP, go on our website www.qeed.it in the PRODUCTS page, on the right menu,
click on DOWNLOAD SOFTWARE and then click FACILE QA-TEMP, you can install the program on your PC. Once
downloaded, install it in the desired directory and run the program.
ENGLISH

FAIL MESSAGE/ ANOMALY:
FAIL HW: problems in the measurement chain (electrical
connections, microprocessor that manages the
measurement, sensor disconnected or faulty).
FAIL LOG: problem on recording data (without the
availability of stick usb memory stick usb not recognized).
FAIL RTC: problem on backup battery (dead or defective).
EEPROM FAIL: problem microprocessor configuration (not
calibrated module, takes no configuration).
MODBUS COMMUNICATION:
This is the last window of the device configuration. The left
column contains the parameters to be set for the
communication speed BAUDRATE (from 1200 to 115200),
the PARITY (None, Odd, Even), the STOP BIT (1 or 2), the
Modbus address to be assigned to the device . You do not
need to configure these parameters for the use of the
module with digital / analog output. It is possible to use the
module with RS485 serial output with Modbus output
analog and digital simultaneously.
LOGGING:
On the right side of the window you can enable the feature
LOG for the acquisition of data on usb pendrive. You can
assign a name to the log file by associating the extension.
Xls,. Xlsx,. Csv,. Txt,. Dat. Logs. The default file is in text
format. The minimum sampling time is 1 second, the
maximum is about 18 hours.
PROGRAMMING THE DEVICE BY SOFTWARE FACILE QA-TEMP
PROGRAMMING THE DEVICE BY SOFTWARE FACILE QA-TEMP
409 2015
ANALOG OUTPUT: You can associate the analog output to a single INPUT
(you have already performed the selection in the previous screen). The mode
of the analog output could be VOLTAGE or CURRENT. The QA-TEMP has the
ability to scale the inputs and outputs as required, then select the range of
measurement inputs (INPUT BEGIN SCALE and INPUT END SCALE) to assign
to the analog output signal (OUTPUT BEGIN SCALE and OUTPUT END SCALE).
Depending on the choices you make will change the units of the values in
the input and output. If you select MANUAL CONTROL VIA MODBUS, you can
manage the module as an AO (Analog Output) or a DO (Digital Output), thus
freeing the analog output and digital input selected.
The analog output will be handled via RS485 Modbus RTU (see register map).
DIGITAL OUTPUT: The digital output starting as OPEN CONTACT (that is if
there is an alarm already set or active). If you want to change the initial status
of the digital output select CONTACT CLOSED from the dropdown in the
upper right.
ALARM/ FAIL ANALOG OUTPUT: It is possible to use the analog output to
control any supervening anomaly Hardware HW FAIL, FAIL RTC Real Time
Clock anomaly that stores the date and time, FAIL EEPROM for the anomaly
on the microprocessor, FAIL LOG if an anomaly occurred during data
acquisition, UNDER RANGE scale of measurement set, OVER RANGE scale of
measurement set. It is possible to select multiple items in the menu. In case
of alarm the analog output will go to 21mA or 10.5 V depending on the
selection made in the previous window.
ALARM WINDOW: You can activate the ALARM functionality (in the gray
box), on the digital output or on the analog output, or both simultaneously.
In this window you can manage HOW and WHEN activate the alarm by
selecting the options from the dropdown menu : MORE THAN A THRESHOLD,
LESS THAN A THRESHOLD, NOT BETWEEN TWO THRESHOLDS, BETWEEN TWO
THRESHOLDS. We therefore have the possibility to insert the values of
THRESHOLD (Upper and Lower) and the value of HYSTERESIS. In the case
where it is selected the value of a Higher threshold when the signal falls
below, the alarm switched off at the threshold value minus the value of
hysteresis. In the event that you have chosen the value of a Minor threshold,
when the value exceeds the threshold plus the hysteresis value, the alarm
switch off. In the case where it is selected between two thresholds, the
hysteresis is external. In case you have selected Not included between two
thresholds, the hysteresis is internal.
ALARM/ FAIL DIGITAL OUTPUT: It is possible to use the digital output to
control any supervening anomaly Hardware HW FAIL, FAIL RTC Real Time
Clock anomaly that stores the date and time, FAIL EEPROM for the anomaly
on the microprocessor, FAIL LOG if an anomaly occurred during data
acquisition, UNDER RANGE scale of measurement set, OVER RANGE scale of
measurement set. It is possible to select multiple items in the menu. The
alarm can be associated with the state of the digital input (HIGH or LOW) for
up to 15 cycles per minute. STATE DIGITAL ALARM / FAIL allows you to define
the status of contact in case of alarm (CONTACT OPEN or CLOSED).
ENGLISH

DATA LOGGING QA-TEMP
DATA LOGGING
Data (yyyy-mm-dd) & Time Status ID Analog
Input
Analog
Output
Input type Output type
12345678 2014/03/12-14-23-25 0 99.96 2499 3 0
12345678 2014/03/12-14-24-25 0 99.92 2498 3 0
12345678 2014/03/12-14-25-25 0 99.96 2499 3 0
12345678 2014/03/12-14-26-25 0 100 2500 3 0
QA-TEMP
509 2015
Serial
Number
The QA-TEMP provides, on a local memory type PEN DRIVE USB (USB KEY) connected to the module via the microUSB, a series of
information concerning the operation of the module, alarm status, type of input, the output type, the reading of the measured
data, the measure of the output value from the module.
For each row correspond to a precise time reference. The module is equipped with an RTC Real Time Clock powered by a backup
battery that lets you record data with YEAR / MONTH / DAY / HOUR - MIN - SEC.
EXAMPLE OF LOG FILE: for 400ohm 2-wire RESISTOR input, one sample per minute, 0-10V output.
The first number listed is the SERIAL NUMBER of the module, which allows it to be uniquely identified.
The second column give you information about: DATE (YEAR / MONTH / DAY / HOUR - MIN - SEC).
It is then reported the STATUS ID (Registry STATE) in binary mode to 16 bit. The binary number corresponds to the Modbus register
40005 that represents the state of the machine (Status: bit 1 = fail global, bit 2 = alarm, bit 3 = OVER RANGE, bit 4 = UNDER RANGE,
bit 5 = din status, bit 6 = dout status, bit 7 = fail hw, bit 8 = fail log, bit 9 = fail RTC, bit 10 = fail EEPROM, bit 11 = fail sensor).
The fourth column we find the information from ANALOG INPUT:temperature, potentiometer or resistor.
ANALOG OUTPUT: the value uA or in mV output of the module. This value follows the setting made via FACILE.
INPUT TYPE: refered to the Modbus Register 101 that indicate the type of the Input sensor (Analog Input type : 2=Potentiometer,
3=Resistor400-2W, 4=Resistor400-3W, 5=Resistor400-4W, 6=Resistor4000-2W, 7=Resistor4000-3W, 8=Resistor4000-4W, 9=NI100-2W,
10=NI100- 3W, 11=NI100-4W, 12=PT100-2W, 13=PT100-3W, 14=PT100-4W, 15=PT500-2W, 16=PT500-3W, 17=PT500-4W, 18=PT1000-
2W, 19=PT1000-3W, 20=PT1000-4W, 21=TC J, 22=TC K, 23=TC R, 24=TC S, 25=TC T, 26=TC B, 27=TC E, 28=TC N).
OUTPUT TYPE: refered to the Modbus Register 106 that indicate the output configuration (Output Analog mode: bit
0=Voltage/Current, bit 1-2=analog input,frequency, period, totalizer, bit 3 = fail UNDER RANGE, bit 4 = fail OVER RANGE, bit 5 = fail
hardware, bit 6 = fail log, bit 7 = fail RTC, bit 8 = fail EEPROM, bit 9 = fail alarm, bit 10-11 = 1 threshold high/1 threshold low/2
thresholds external/2 thresholds internal , bit 12 = Manual mode).
AVAILABLE ON THE WEBSITE www.qeed.it the MACRO for charge the .csv file logged directly on a Excel file
HOW TO IMPORT LOG DATA FROM EXCEL VERSION BEFORE 2003:
It‘s possible to import the data stored on the USB Memory Stick at any time (even if the log is not finished). Once you open the file
with Excel (or Open Office), you will have to act on the functionality of the program for wrapping the data as described above. To
do this, you can perform the following steps: Select the first column, go to the option data, click on TEXT COLUMN, then choose
the option that provides for the separation of the data by tabs or commas, the next step endorse the option POINT and COMMA.
Following the procedure as soon as you get the data displayed in columns.
ENGLISH

MODBUS REGISTER MAP QA-TEMP
MODBUS REGISTER MAP QA-TEMP
609 2015
DIPSW status : bit 0-7=dip switch status, pos
1=bit 8,..., pos 8=bit 1
UNIT16 R
Third wire Resistence Ohm FLOAT (MSW) R/W
Analog Input type : 2=Potentiometer,
3=Resistor400-2W, 4=Resistor400-3W,
5=Resistor400-4W, 6=Resistor4000-2W,
7=Resistor4000-3W, 8=Resistor4000-4W,
9=NI100-2W, 10=NI100-3W, 11=NI100-4W,
12=PT100-2W, 13=PT100-3W, 14=PT100-4W,
15=PT500-2W, 16=PT500-3W, 17=PT500-4W,
18=PT1000-2W, 19=PT1000-3W, 20=PT1000-4W,
21=TC J, 22=TC K, 23=TC R, 24=TC S, 25=TC T,
26=TC B, 27=TC E, 28=TC N
UNIT16 R/W 2 2...28
NOT USED 40102
Temperature mode : bit 0-1 = unit measure
°C/°F, bit 7-15analogfiltervalue
UNIT16 R/W 1 MSB: 1...32 40103
NOT USED 40104
NOT USED 40105
Output Analog mode : bit 0=Voltage/Current, bit
1-2=analog input, frequency, period,totalizer, bit
3= fail ur, bit 4 = fail or, bit 5 = fail hw,bit 6 =
fail log, bit 7 = fail rtc, bit 8 = fail eeprom, bit 9
= fail alarm, bit 10-11 = 1threshold
greater/1threshold less/2thresholds
external/2thresholds inside, bit 12=Manual mode
UNIT16 R/W 0 40106
REMARKS:
●Modbus connections: A+ and B-;
●Modbus Register reference: with reference to the logical address, for ex. 40010, corresponds to physical address n°9 as per
Modbus RTU standard;
●Modbus functions supported: 3 (Read multiple registers), 6 (Write single), 16 (Write multiple);
●Any changes made by dip-switch required to switch off the power supply.
40005
Comment Register Type R/W Default
Value Range Modbus
Address
UNIT16
UNIT16
UNIT16
R
R
0
0...65535
40001
40002
40003 (MSW)
40004 (LSW)
UNIT16 R
UNIT16 R
UNIT32 (MSW) R/W
UNIT16 R/W
Float (MSW) R
0…10000
0...4294967295
0...65535
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
Register Name
Machine ID
Firmware ID
ID
Status
Machine ID
Serial Number
Firmware ID
Status Register: bit 0 = fail global, bit 1 =
alarm, bit 2 = over range, bit 3 = under range,
bit 4= din status, bit 5=dout status, bit 6 =
fail hw, bit 7=fail log, bit 8=fail rtc, bit 9=fail
eeprom, bit 10=fail sensor
Input Value
Totalizer
Output Value
Input Value
Input Value Normalized
Totalizer
Output Value (mV or uA)
Input Value
NOT USED
Third wire
resistance
Analog input
type
Temperature
mode
Cold Junction
Temp
TC read
Digital Output
Dip-switch
status
NOT USED
Cold Junction Temperature Float (MSW) R
TC uV readed Float (MSW) R
40016
40017
40018
40019
40020
40021
40022
40023
UNIT16 R/W
Digital Output: bit 0= disabled/enabled
10R
Output Analog
mode
40101
ENGLISH

MODBUS REGISTER MAP QA-TEMP
QA-TEMP
09 2015
Register Name Comment
Output Analog
Input Begin scale
Output Analog Input Begin Scale FLOAT (MSW) R/W 0.0
Output Analog
Input End scale
Output Analog Input End Scale FLOAT (MSW) R/W 10000.0
Output Analog
Begin scale
Output Analog Begin Scale UNIT16 R/W 0
Output Analog
End scale
Output Analog End Scale UNIT16 R/W 10000 0...65535 40112
Digital Output UNIT16 R/W 0 40113
Alarm Low Trip
value
Alarm Low trip value FLOAT (MSW) R/W 0.0
Alarm High Trip
value
Alarm High trip value FLOAT (MSW) R/W 0.0
Alarm Hysteresis
value
Alarm Hysteresys value FLOAT (MSW) R/W 0.0 40118
40119
Modbus Address Modbus address +parity +stopbits : MSB Modbus
address, bit 0-1 =parity none/odd/even,
bit 2=stop bits 1/2
UNIT16 R/W 256 40120
Modbus Baudrate Modbus Baudrate : value 0=1200, 1=2400,
2=4800, 3=9600, 4=19200, 5=38400, 6=57600,
7=115200
UNIT16 R/W 3 0...7 40121
Log mode Log mode : bit 0=disabled/enabled UNIT16 R/W 0 40122
Log sample time Log sample time (sec) UNIT16 R/W 1 1...65535 40123
Log name Log name 15 letters max UNIT16 R/W 0 40124
Log name Log name 15 letters max UNIT16 R/W 0 40125
Log name Log name 15 letters max UNIT16 R/W 0 40126
Log name Log name 15 letters max UNIT16 R/W 0 40127
Log name Log name 15 letters max UNIT16 R/W 0 40128
Log name Log name 15 letters max UNIT16 R/W 0 40129
Log name Log name 15 letters max UNIT16 R/W 0 40130
Log name Log name 15 letters max UNIT16 R/W 0 40131
RTC Year RTC Year UNIT16 R/W 2000...2099 41001
RTC Month RTC Month UNIT16 R/W 1...12 41002
RTC Day RTC Day UNIT16 R/W 1...31 41003
RTC Hour RTC Hour UNIT16 R/W 1...23 41004
RTC Minute RTC Minute UNIT16 R/W 0...59 41005
RTC Second RTC Second UNIT16 R/W 0...59 41006
Command Command : value 1=Reset, 2=Save Cfg to
EEPROM, 3=Set Factory CFG,
UNIT16 R/W
Command 1 Command parameter 1 UNIT16 R/W
Command 2 Command parameter 2 UNIT16 R/W
Register Type
Digital Output : bit 0=default value, bit 1
=fail ur,
bit 2 = fail or, bit 3 = fail hw, bit 4 =
fail log,
bit 5 = fail rtc, bit 6 = fail eeprom, bit 7
R/W Default
Value
Range Modbus
Address
40107
40108
40109
40110
0...65535 40111
40114
40115
40116
40117
Upgrade FIRMWARE:
The QA-TEMP is designed to upgrade the firmware via the USB port using a standard pen drive where the file will be placed.
The firmware will allow you to implement the functionality of the card and correct any anomalies that may occur.
In order to upgrade the firmware simply, remove power from the module, insert the pen drive with the file, restore power, at this point
the card will automatically discharge the file and update the firmware without altering the configuration loaded during programming.
During the update phase the LED light will be intermittent FAIL.
7
42001
42002
42003
MODBUS REGISTER MAP
ENGLISH

MODBUS ADDRESS CONFIGURATION AND BAUD
RATE BY DIP-SWITCH
Through the dip-switch on the front panel of the module,
you can change the Modbus address and baud rate.
In the case in which all the dip switches are set to zero,
the module will take the calibration from EEPROM,
otherwise it will take parameters from a dip-switch.
In order to assign addresses more than 62 assignments
you need to take advantage of the interface software
FACILE QA-TEMP. In order to assign values of baud rates
different from those selectable dip you should take
advantage of the interface software FACILE QA-TEMP.
For changing the addresses and the baud rate it can also
be done by writing directly on the related registers.
POWER SUPPLY:
10...40 Vdc or 20...28 Vac - Connectors 16 and 17, or by
T-BUS connector (optional tool) on the base of the
module (see the picture placed on the bottom of this
page).
POWER SUPPLY by T-BUS CONNECTION (T-BUS
connector required):
it is possible to mount the accessory T-BUS to carry both
power and serial communication. The number of
modules supported by the function of the power supply
bus is used (check the absorption of the modules).
INTERFACE PROGRAM FACILE QA-TEMP
FACILE QA-TEMP is the configuration software for QA-
TEMP module.
The software is free and downloadable from the website:
www.qeed.it/category/software/facile-qa-temp/ .
To communicate with the module you have to connect
via USB port directly on your PC.
It is possible to configure the module via RS485 through
the register map contained on this manual.
QA-TEMP
QA-TEMP
QUICK GUIDE
809 2015
This document is the property of DEM S.p.A. Duplication or
reproduction is prohibited. The contents of this document
correspond to the products and technologies described. This
information may be amended or supplemented by technical
and commercial requirements.
Disposal of Electrical & Electronic Equipment (Applicable throughout the European Union and other European countries with separate
collection programs) This symbol, found on your product or on its packaging, indicates that this product should not be treated as household
waste when you wish to dispose of it. Instead, it should be handed over to an applicable collection point for the recycling of electrical and
electronic equipment. By ensuring this product is disposed of correctly, you will help prevent potential negative consequences to the
environment and human health, which could otherwise be caused by inappropriate disposal of this product. The recycling of materials will
help to conserve natural resources. For more detailed information about the recycling of this product, please contact your local city office,
waste disposal service or the retail store where you purchased this product.
QUICK GUIDE
LEDS - FRONT SIGNALS:
POWER: power presence on the device.
FAIL: presence of a failure / error on the device. It is
activated in the case have been activated by FAIL
messages on FACILE QA-TEMP. One or more events
FAIL are active.
RX, TX: the module is communicating via RS485 (LED
blinking).
Dout: digital output active.
MOUNTING INSTRUCTIONS:
To mount the card on DIN rail, we recommend to
place the top of the form on the edge of the bar
omega, then pushing the bottom until it clicks. The
module is equipped with a slider fastening that will
be pushed forward in order to ensure the perfect
fastening of the module on the bar.
NOTE: through the hole on the case of QA - TEMP
(shown in the figure ) , you can access an internal DIP
SWITCH . Turning up the " DIP 1”you can activate the
dynamic terminating of the Modbus .
ENGLISH
Table of contents
Popular Data Logger manuals by other brands

ThermoFisher Scientific
ThermoFisher Scientific DataTaker DT90 Series user manual

Kilowatt Labs
Kilowatt Labs SIRIUS 7100-48-B-3C-M-SD-A-X-X-FL user manual

ALTUS
ALTUS Nexto Series manual

Dataq Instruments
Dataq Instruments DI-2160 user manual

Kaye
Kaye Log NFC Temperature Logger instructions

Huawei
Huawei FusionModule1000A20 Maintenance Guide