Qoltec 53923 User manual

0
USER MANUAL
Uninterruptible power supply (UPS)
MODEL: 53923 | 53925
www.qoltec.com
EN

1
Content
1. Brief introduction ............................................................................................................................................................................................................ 2
1.1 System and model description .................................................................................................................................................................................... 2
1. Brief introduction ............................................................................................................................................................................................................ 2
1.2 Description of commonly used symbols..................................................................................................................................................................... 2
1.3 Appearance.................................................................................................................................................................................................................... 2
1.4 Product specification and performance...................................................................................................................................................................... 3
2. Safety Instruction............................................................................................................................................................................................................. 3
3. Installation........................................................................................................................................................................................................................ 4
3.1 Unpacking and inspection ............................................................................................................................................................................................ 4
3.2 Input and output power wiring and protective earth ground installation .............................................................................................................. 4
3.2.1 Notes for installation ................................................................................................................................................................................................. 4
3.2.2 Installation .................................................................................................................................................................................................................. 4
3.3 Operating procedure for connecting the long backup time model UPS with the external battery...................................................................... 5
3.3.1 Description external battery module ....................................................................................................................................................................... 5
3.3.2 The procedure for connecting the battery module models .................................................................................................................................. 5
4. Operation ......................................................................................................................................................................................................................... 5
4.1 Operation display panel ............................................................................................................................................................................................... 5
4.2 Operation mode ............................................................................................................................................................................................................ 6
4.2.1 Normal mode.............................................................................................................................................................................................................. 6
4.2.2 Battery mode .............................................................................................................................................................................................................. 6
4.2.3 Bypass mode .............................................................................................................................................................................................................. 7
4.2.4 LCD indication of UPS alarm status and faults........................................................................................................................................................ 7
4.3 Operating instructions.................................................................................................................................................................................................. 8
4.3.1 UPS ON/OFF operation .............................................................................................................................................................................................. 8
4.3.2 Conducting battery self-diagnosis............................................................................................................................................................................ 8
4.4 Checking UPS function.................................................................................................................................................................................................. 8
4.5 Setting the output voltage and frequency .................................................................................................................................................................. 9
4.6 Troubleshooting ............................................................................................................................................................................................................ 9
4.7 Backup time for the standard model ........................................................................................................................................................................ 10
4.8 Internet communication............................................................................................................................................................................................. 11
4.9 Description of communication interface .................................................................................................................................................................. 11
5. Battery maintenance..................................................................................................................................................................................................... 12
6. Notes for battery disposal and battery replacement ................................................................................................................................................ 12
7. Safety .............................................................................................................................................................................................................................. 12
nTec declares this device complies with the Directives as listed in this document: EMC 2004/108/WE, LVD 2006/95/WE. ............................. 12

2
1. Brief introduction
1.1 System and model description
The On-Line-Series is an uninterruptible power supply incorporating double-converter technology. It provides perfect protection specifically
for strict load. The double-converter principle eliminates all mains power disturbances. A rectifier converts the alternating current from the
socket outlet to direct current. This direct current charges the batteries and powers the inverter. In the event of power failure, the
maintenance-free batteries power the inverter. Thus the inverter generates a sine wave AC power, which permanently supplies the loads.
Designed with the proven on-line, double conversion architecture, this series of UPS offers the greatest degree of availability in power
protection and provides continuous high-quality AC power to connect strict load, especially for the basic equipments in some areas as:
finance, communication, government, traffic, manufacture, education and so on.
This manual is applicable to the following models:
Type
Model
Input
Battery
Long back up
time
6KVA
6KVA
Single phase + N
External battery
bank
10KVA
10KVA
Single phase + N
External battery
bank
1. Brief introduction
1.2 Description of commonly used symbols
The following symbols will be used in this manual and may appear during the course of your practical applications. Therefore, all users
should be familiar with them and understand their meanings.
1.3 Appearance
BACK VIEW OF 10KVA BACK VIEW OF 6KVA
Notation and Explanation
Notation
Explanation
Notation
Explanation
Alert you to pay special attention
Protective ground
Caution of high voltage
Alarm silence
Turn on the UPS
Overload indication
Turn off the UPS
Battery check
Idle or shut down the UPS
Recyclable
Alternating current source (AC)
Do not dispose with ordinary
trash
Direct current source (DC)
Battery

3
* The picture for back panel is just for reference, it subjects to change on customer’s requirement, please refer to the real subject.
1.4 Product specification and performance
●Electrical performance
Model
6KVA
10KVA
Rating
6kVA/4.8kW
10kVA/8kW
Input
Input system
Single phase & earth ground
Voltage range
(120±5)VAC~ (274±5)VAC
Power factor
≥0.99
Voltage range of bypass
(60±5)VAC~ (300±5)VAC (default: 80VAC~264VAC Could be
adjusted by software)
Output
Output system
Single phase & earth ground
Rated voltage
230VAC ①
Power factor
0.8
Voltage precision
±1%
Output frequency
Normal
mode
1.The output frequency synchronizes with the input frequency
when the input frequency is in the range of 46 Hz~ 54 Hz.
2.The output frequency is 50Hz when the input frequency is not in
the range of 46 Hz~ 54 Hz.
3.Can be set as 60Hz.
Battery
mode
Inverter overload capacity (Utility
power, 25℃)
105% ±5% < Load ≤125% ±5% 60s transfer to bypass
125% ±5% < Load < 135% ±5% 30s transfer to bypass
Load > 135% ±5%, 100ms transfer to bypass
Transfer time
0ms (Normal mode←→ Battery mode)
<4ms (Normal mode←→Bypass mode)
Crest factor
3:1
Battery
Batteries voltage
192VDC
Battery quantity
None
None
Battery Type
Sealed maintenance-free lead –acid battery of battery voltage
12V/7AH
Backup Time (25℃)
Full load ≥5min (Standard)
Charge current
5.5A
5.5A
Dimensions (L*W*H)mm
425x190x328
533x260x501
Weight (kg)
65
75
Note1: Output voltage can be set: 200V/208V/220V/230V/240V.
●Operating environment
Note: If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be decrease in use, please refer
to the following:
Altitude(M)
1000
1500
2000
2500
3000
3500
4000
4500
5000
Load
100%
95%
91%
86%
82%
78%
74%
70%
67%
2. Safety Instruction
●Even if the interruptible Power System (UPS) is not connected to utility power, the output socket of the UPS may still present 220V/230V
output voltage.
●If it is necessary to replace the external battery cord or power cord, please purchase the original material from the service center or
distributor of our company so as to avoid overheat or spark resulting in fire due to insufficient capacity.
●Do not let battery or batteries get close to any heating source and do not incinerate battery or batteries, they may explode.
●Do not open or mutilate the battery or batteries, released electrolyte is highly poisonous and harmful to the skin and eyes.
Temperature
Humidity
Altitude
Storage
temperature
0℃-40℃
<95%
<1000m
0℃-40℃

4
●Do not short the positive and negative of battery electrode. Otherwise, it may cause electric shock or fire.
●To avoid the risk of being shocked, please do not attempt to open the case of the UPS.
●A battery can present a risk of electric shock and high short circuit current.
●Do not plug household appliance such as hair dryers to UPS.
3. Installation
3.1 Unpacking and inspection
1) Unpack the packaging and check the package contents. The shipping package contains:
●A UPS
●A user manual
●A communication cable
2) Inspect the appearance of the UPS to see if there is any damage during transportation. Do not turn on the unit and notify the carrier and
dealer immediately if there is any damage or lacking of some parts.
3.2 Input and output power wiring and protective earth ground installation
3.2.1 Notes for installation
1) The UPS must be installed in a location with good ventilation, far away from water, inflammable gas and corrosive agents.
2) The UPS should not be tilted. The air inlet port at the lower part of the front panel and the fan outlet port on the rear panel should not be
blocked so as to ensure good ventilation (Allow at least 0.5m of space on each side).
3) In case if the UPS is unpacked, installed and used at very low temperatures, condensation of water drops may appear. It is necessary to
wait until the UPS is fully dried inside out before proceeding to installation and use. Otherwise, there may be a risk of electric shock.
3.2.2 Installation
Installation and wiring must be performed in accordance with the local electric code and the following instructions by professional personnel.
For safety, please cut off the mains power breaker before installation. The battery breaker also needs to be cut off if it is a long backup time
model.
1) Open the terminal block cover located on the rear panel of the UPS (please refer to the appearance diagram).
2) For 6KVA UPS, it is recommended to select the UL1015 10AWG (6mm2) wire or other insulated wire which complies with AWG Standard for
the UPS input and output wirings.
3) For 10KVA UPS, it is recommended to select the UL1015 8AWG (10 mm2) wire or other insulated wire which complies with AWG Standard
for the UPS input and output wirings.
Note: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the UPS’s maximum input current.
Otherwise the receptacle may be burned and destroyed. (Please refer to section 1.4)
4) Connect the input and output wires to the corresponding input and output terminals according to the following diagram.
Note: You must make sure that the input and output wires and the input and output terminals are connected tightly.
5) The protective earth ground wire refers to the wire connection between the equipment which consumes electro-equipment and the
ground wire. The wire diameter of protective earth ground wire should be at least as above mentioned for each model and green wire or
green wire with yellow ribbon wire is used.
6) After having completed the installation, make sure the wiring is correct.
7) Please install the leak current protective breaker at the output power distribution panel of the UPS if necessary.
8) To connect the load with the UPS, please turn off all the loads first, then perform the connection and finally turn on the loads one by one.
9) No matter the UPS is connected to the utility power or not, the output of the UPS may have electricity. The parts inside the unit may still
have hazardous voltage after turning off the UPS. To make the UPS have no output, power off the UPS, and then disconnect the utility
power supply.
10) Suggest charging the batteries for 8 hours before use. After connection, turn the input breaker in the “ON” position, the UPS will charge
the batteries automatically. You can also use the UPS immediately without charging the batteries first, but the backup time may be less
than the standard value.
11) If it is necessary to connect the inductance load such as a monitor or a laser printer to the UPS, the start-up power should be used for
calculating the capacity of the UPS, as its start-up power consumption is too big when it is started.

5
Input and Output Terminal Block wiring diagram of 6KVA/10KVA
3.3 Operating procedure for connecting the long backup time model UPS with the external battery
3.3.1 Description external battery module
The nominal DC voltage of external battery pack is 192VDC. Each battery pack consists of 16 pieces of 12V “maintenance-free” batteries in
series. To achieve longer backup time, it is possible to connect multi-battery packs, but the principle of “same voltage, same type” should be
strictly followed.
3.3.2 The procedure for connecting the battery module models
For 6KS/6KL/10KS/10KL, the procedure of installing battery bank should be complied with strictly. Otherwise you may encounter the
hazardous of electric shock.
1) A DC breaker must be connected between the battery pack and the UPS. The capacity of breaker must be not less than the data
specified in the general specification as follow.
Model
6KVA
10KVA
Battery voltage
192VDC
192VDC
Battery current
34A max.
56A max.
Note: 240VDC battery voltage can be choose.
2) Set the battery pack breaker in “OFF” position and connect the 16 pieces of batteries in series.
To complete the connection by plugging the connector of the external battery cable into the external battery socket of the UPS. Do not
attempt to connect any loads to the UPS now. You should connect the input power wire to the right position first. And then set the breaker of
the battery pack in the “ON” position. After that set the input breaker in the “ON” position. The UPS begins to charge the battery packs at the
time.
4. Operation
4.1 Operation display panel
1. ON button:
Pressing the ON button more than 1 second (buzzer beeps once), the UPS system is turned on.
2. OFF button:
By pressing this button more than 1 second (buzzer beeps once) turns off the UPS system whenever the UPS run under the normal
mode/battery mode.
3. Function button
The Function button provides the following functions:
a) Battery self- diagnosis: When the UPS ran in normal mode, pressing this button more than 5 seconds (buzzer beeps twice) can start the
battery self-diagnosis.
b) Silence function in battery/bypass mode
In battery/bypass mode, when the buzzer beeps, pressing and holding the function button for more than 5 seconds (buzzer beeps two

6
times) can silence the buzzer. Press the button for more than 5 seconds (buzzer beeps twice) again to resume the alarm function.
c) LCD display screen switch
Pressing the function button for more than 1 seconds (buzzer beeps once) to switch LCD display screen.
4. LED indicators
The LED indicators contains Fault indicator, Bypass indicator, utility power indicator, Inverter indicator, Battery indicator. The definition of
each indicator is the same as LED panel (refer to table Appendix 1).
4.2 Operation mode
UPS operation mode contains normal mode, battery mode and bypass mode. Under the three modes, the page showing output voltage and
output frequency is the main display page. If users need more information about UPS, Pressing the function button can initiate display
screen switch. If the current page is not the main page, UPS will auto switch back the main page after 30 seconds. In order to extend the LCD
usage life, the backlight will turn off after 1 minute without any switch operation. At this point, Users just need to touch any button briefly,
the backlight will be turn on.
4.2.1 Normal mode
When operating in the normal mode, the display of main page on the front panel is shown as the figure 4-2. The utility power indicator and
the Inverter indicator are turn on. Load information area shows load value, and the battery level area indicates dynamically when the battery
is not full charged (the battery level icons lit one after another circularly). When the battery is full charged, all the level icons are turn on.
1) If the utility power indicator blinks, it indicates that there are problems with reversed polarity (L, N) of site wiring or disconnect with
ground. UPS is still working in normal mode. If the battery indicator is turn on at the same time, it shows that the voltage or frequency of
the utility power is out of the normal input range of the UPS. The UPS works in battery mode.
Figure 4-2 Normal Mode
2) If load is more than 105 percent, the buzzer beeps twice every second, meanwhile, the warning icon blinks every second too, reminding
that you have been overloaded. You should get rid of some unnecessary loads one by one to decrease the loads until the alarm clear.
3) If the battery indicator blinks, it indicates that no battery is connected to the UPS or battery voltage is too low. You should check if battery
is properly connected to the UPS, and press function button more than 5 seconds to start the battery self-diagnosis. If the connection
between battery and UPS is confirmed without any problem, it may be due to the defect or aging of the battery, please refer to the
“troubleshooting” in chapter 7 to solve the problem accordingly.
4) The other four display pages are load percent page, actual load page, input information page and the maximum temperature page.
Note: Connection to the power generator should be made according to the following steps:
Activate the power generator and wait until the operation is stable before connecting the output of the power generator to the UPS (be sure that
the UPS is in idle mode). Then, turn on the UPS according to the startup procedure. After the UPS is turned on, the loads are connected one by
one.
It recommended that the capacity of the AC generator chosen should double that of the UPS.
4.2.2 Battery mode
When operating in the normal mode, the display of main page on the front panel is shown as the figure 4-3. The battery indicator and the
Inverter indicator are turn on. If the utility power indicator blinks at the same time, it shows that the utility power is abnormal. Load
information area shows load value, and bat level area shows current battery capacity.
1) When the UPS is running in battery mode, the alarm will beep every 4 seconds. If the “Function” key is pressed for more than 5 seconds,
the alarm will not beep (silence function). Press the “Function” key more than 5 seconds again to resume the alarm function.

7
Figure 4-3 Battery Mode
2) When the battery capacity decreases, the number of load/battery capacity indicators turned on will decrease. If the battery voltage drops
to the pre-alarm level (capable of maintaining the backup time for more than 2 minutes), the alarm will beep every second to remind the
user of insufficient battery capacity.
3) The other four display pages are load percent page, actual load page, battery information page and the maximum temperature page.
4.2.3 Bypass mode
When operating in bypass mode set up through UPSilon software, the display on the front panel is shown as the figure 4-4, the utility power
indicator and the bypass indicator are turn on. The load/battery capacity indicator will be turned on in accordance with the load capacity
connected. Load information area shows load value, and the battery level area indicates dynamically when the battery is not full charged (the
battery level icons lit one after another circularly). When the battery is full charged, all the level icons are turn on.
1) When operating in bypass mode, the UPS beeps every 2 minutes. If the “Function” key is pressed for more than 5 seconds, the alarm will
not beep (silence function). Press the “Function” key more than 5 seconds again to resume the alarm function.
2) If the utility power indicator blinks, it shows that the voltage or frequency of the utility power is out of the input range of the UPS or there
are problems with reversed polarity (L/N) of site wiring or disconnect to the ground for protection.
3) The other four display pages are load percent page, actual load page, input information page and the maximum temperature page.
Notes: When operating in bypass mode, the backup function of the UPS is not available and the power used by the load is directly from the utility
power via internal EMI filter.
Figure 4-4 Bypass Mode
4.2.4 LCD indication of UPS alarm status and faults
In the event of an UPS fault, UPS enters fault operation mode, at this point, the fault icon turn on consistently, the buzzer beeps continuously
and the data information area shows current fault code (refer to table 4-1), the display on the front panel is shown as the figure 4-5.
Figure 4-5 Fault display

8
When a warning occurred, the fault icon blinks every second, and users can switch to the alarm display page shown as the figure 4-6 to check
the warning code.
Figure 4-6 Alarm display
4.3 Operating instructions
4.3.1 UPS ON/OFF operation
Note: The battery is fully charged before delivery. However, storage and transportation will inevitably cause some charge loss. Therefore, it is
advisable to charge the battery for 10 hours before using it, so as to ensure adequate battery autonomy.
1. Turning on the UPS
The operation of turning on the UPS contains: turning on with utility power and turning on without utility power.
1) Turning on with utility power:
Connect the mains input to the UPS, press the ON button more than one second, UPS start to turn on. At this point, the LCD begins to
conduct self-diagnosis (all the LCD indicators are turn on about 4 seconds). Seconds later, the UPS will begin to operate in Normal mode;
meanwhile, the utility power indicator, inverter indicators will turn on. If the utility power is abnormal, the UPS will work in battery mode.
2) Turning on without utility power:
With no mains input feed to the UPS, press the ON button more than one
second, UPS start to turn on, At this point, the LCD begins to conduct
self-diagnosis (all the LCD indicators are turn on about 4 seconds). Seconds later, the battery indicator, inverter indicators will be turn on to
indicate that the UPS is working in battery mode.
2. Powering down the UPS
The operation of powering down the UPS contains: turning off UPS in normal mode, turning off UPS in battery mode.
1) Completely power down the UPS from Normal mode
Hold and press the OFF button persistently for more than 1 second to power off the UPS. If it bas been set up to work in bypass mode by
software, the bypass indicator will be turn on to indicate that the UPS is working in bypass mode. In order to cut off the output from the
UPS, simply cut off the utility power supply. LCD begins to conduct self-diagnosis (all the LCD indicators are turn on about 4 seconds),
seconds later, not any display is shown on the front panel and no output is available from the UPS outlets, system completely power
down.
2) Completely power down the UPS from Battery mode
Press the “OFF” button persistently for more than 1 second to power off the UPS. When being powered off, the LCD will start self-diagnosis
(all the LCD indicators are turn on about 4 seconds), seconds later, not any display is shown on the front panel and no voltage output is
available from the UPS outlets, system completely power down.
4.3.2 Conducting battery self-diagnosis
In UPS operation, users can manually initiate battery self-diagnosis to check the battery conditions. There are two methods to initiate the
battery self-diagnosis:
1. Through the function button
In normal mode, press and hold the function for more than 5 seconds until the buzzer beeps twice. At this point the indicators (LED7~10)
will blink cyclically, indicating the UPS has worked in battery mode and the battery self-diagnosis has started. The battery self-diagnosis
will last for 5 seconds default. In the event of a battery fault during battery self-diagnosis, the UPS will transfer to normal mode
automatically.
2. Through the monitor software
Users can also initiate battery self-diagnosis through the background monitoring software.
4.4 Checking UPS function
Every time when conducting field maintenance, please check the regular function of the UPS, including:

9
1. Check the operation status of the UPS
If the main voltage is within the specifications, the UPS should operate in normal mode; if the main voltage is abnormal, the UPS should
operate in battery mode. In both cases, there should be no fault indication.
2. Check the transfer between the UPS operation modes
Disconnect the main input to simulate a mains failure, the UPS should transfer to battery mode and operate normally; then recover the
mains input, the UPS should transfer to normal mode and operate normally.
3. Check the LED indicators of the UPS
During the check processes stated above, check that the LED indication of the UPS agrees with the UPS operation mode.
4.5 Setting the output voltage and frequency
1) Connect the mains input to the UPS, and make the UPS works in standby mode or bypass mode.
2) Press the ‘F’ and ‘OFF’ button more than one second, then release, the buzzer will beep once, the “OUTPUT” is flashing, which means all of
bottom are used for UPS setting, at this point, if the “VAC” is flashing, which means the output voltage is set to enable; if the “Hz” is flashing,
which means the frequency is set to enable, the LCD screen indicator represents current output voltage and frequency setting value.
3) If you need to set the voltage, check the voltage setting is enabled (“VAC” is flashing). If not, press the ‘F’ more than one second, then
release, the output setting is enabled, at this point you can start to set output voltage.
4) Release the ‘OFF’ key after you press it more than one second, LCD display the selected output voltage in turn.
5) Repeat the fourth step until the LCD indicator meets the required voltage.
6) Press ‘ON’ key about one second, the output voltage setting completed.
7) The frequency setting is the same as the voltage setting, but before the setting, please confirm the frequency setting is enabled, if not,
press ‘F’ key about one second in order to switch to the frequency setting screen (“Hz” is flashing).
8) When done, Press the ‘F’ and ‘OFF’ button more than one second, then release, the buzzer will beep once, exit the setting mode.
In the setting process, if no key is detected within twenty second, the UPS exits the setting screen automatically.
4.6 Troubleshooting
In the event of an UPS fault, shoot the trouble according to Table 4-1. If the fault still persists, please contact our customer service center.
Faults
Solution
Fault/
Warning
code
Fault icon
Alarm
F01
On constantly
Beep continuously
Please contact the distributor or Service center.
F02
On constantly
Beep continuously
Please contact the distributor or Service center.
F03
On constantly
Beep continuously
Please contact the distributor or Service center.
F05
On constantly
Beep continuously
Please contact the distributor or Service center.
F06
On constantly
Beep continuously
Please contact the distributor or Service center.
F07
On constantly
Beep continuously
Please contact the distributor or Service center.
F08
On constantly
Beep continuously
Please contact the distributor or Service center.
F10
On constantly
Beep continuously
Turn off the UPS. Remove all loads. Ensure that the loads are not
failed or the UPS has no internal short before turn on it again. If
failed, please contact the distributor or service center.
F11
On constantly
Beep continuously
After confirm the equipment safety, reset EPO.
F17
On constantly
Beep continuously
Please contact the distributor or Service center.
F21
On constantly
Beep continuously
Please contact the distributor or Service center.
F22
On constantly
Beep continuously
Please contact the distributor or Service center.
F23
On constantly
Beep continuously
Please contact the distributor or Service center.
F24
On constantly
Beep continuously
Please contact the distributor or Service center.
F25
On constantly
Beep continuously
Please contact the distributor or Service center.
F26
On constantly
Beep continuously
Please contact the distributor or Service center.
F32
On constantly
Beep continuously
Please check parallel line connect or not.
F34
On constantly
Beep continuously
Please contact the distributor or Service center.
F35
On constantly
Beep continuously
Please contact the distributor or Service center.
F36
On constantly
Beep continuously
Please contact the distributor or Service center.
F42
On constantly
Beep continuously
Please contact the distributor or Service center.
F55
On constantly
Beep continuously
Please contact the distributor or Service center.

10
F57
On constantly
Beep continuously
Please contact the distributor or Service center.
F59
On constantly
Beep continuously
Please contact the distributor or Service center.
A04
Blink once every
second
4min beep one
sound
Please check line voltage.
A07
Blink once every
second
2min beep one
sound
Please check the polarity of the neutral wiring and the line wiring.
A08
Blink once every
second
1 sound /4s
Please check line voltage.
A10
Blink once every
second
Beep one sound
every second
Please check battery line connect or not.
A11
Blink once every
second
Beep one sound
every second
The UPS output will be cut off, please switch to the backup power.
A12
Blink once every
second
Beep continuously
Please contact the distributor or Service center.
A14
Blink once every
second
Beep two sounds
every second
Reduce the member of loads connected to the UPS.
A15
Blink once every
second
Beep two sounds
every second
Reduce the member of loads connected to the UPS.
A16
Blink once every
second
Beep one sound
every second
Ensure that the fan is not locked
A18
Blink once every
second
Beep one sound
every second
Please contact the distributor or Service center.
A20
Blink once every
second
Beep 3 sounds
Please check the battery cables connect or not.
A33
Blink once every
second
No beep
Please contact the distributor or Service center.
A34
Blink once every
second
1.5s beep 1sounds
total 3 sounds
Please contact the distributor or Service center.
A35
Blink once every
second
Beep continuously
Please contact the distributor or Service center.
A53
Blink once every
second
Beep continuously
Please contact the distributor or Service center.
A61
Blink once every
second
Beep continuously
Please contact the distributor or Service center.
Table 4-1 UPS troubleshooting of LCD panel indicator
When you contact the service center, please provide the following information:
●Model No and Serial No of the UPS.
●The date when the problem arose.
●Complete description of the problem, including the panel display, alarm warning, and power condition and the load capacity. If the UPS is a
long backup time model, you may also provide the battery information.
4.7 Backup time for the standard model
The backup time of the long backup time model is dependent on the external battery pack capacity and the load level as well as other
factors.
The backup time of standard model may vary from different models and load level.

11
Please refer to the following:
4.8 Internet communication
This series is equipped with an intelligent slot for Web power (optional accessory) or other optional card to achieve remote management of
the UPS. Please contact your local distributor for further information.
4.9 Description of communication interface
1) The standard RS232 port is applicable to communicate with computer.
Description and pin assignment of RS232
Baud rate: 2400bps DB-9 pin assignment:
Data bit: 8 bit
Ending bit: 1bit
Parity bit: None
RS232 Interface
2) USB introduction
Male Female
USB pin definition:
Note: When RS232 and USB are provided, only one of them will be
chosen and RS232 is preferred.
3) User enables to monitor and manage the UPS through installed the
AS400 card (optional).
PIN1: UPS failure (normally open, active close)
PIN2: Summary alarm
PIN3: Ground
PIN4: Remote shutdown
Pin
number
Function description
I/O
3
Rxd
Input
2
Txd
Output
5
GND
Ground
Pin
Function
Color
Note
1
V Bus
Red
5V
2
Data -
White
Data -
3
Data +
Green
Data +
4
GND
Black
Ground

12
PIN5: Common
PIN6: Bypass active (relay close)
PIN7: Low battery
PIN8: UPS on (relay close)
PIN9: Utility Power failure (normally open, active close)
5. Battery maintenance
●This series UPS only requires minimal maintenance. The battery used for standard models is valve regulated sealed lead-acid maintenance
free battery. These models require minimal repairs. The only requirement is to charge the UPS regularly in order to maximize the expected
life of the battery. When being connected to the utility power, whether the UPS is turned on or not, the UPS keeps charging the batteries
and also offers the protective function of overcharging and over discharging.
●The UPS should be charged once every 4 to 6 months if it has not been used for a long time. In the regions of hot climates, the battery
should be charged and discharged every 2 months. The standard charging time should be at least 12 hours.
●Under normal conditions, the battery life lasts 3 to 5 years. In case if the battery is found not in good condition, earlier replacement should
be made. Battery replace event should be performed by qualified personnel.
●Replace batteries with the same number and same type of batteries.
●Keep the ambient temperature between 15℃and 25℃.
●Do not replace the battery individually. All the batteries should be replaced at the same time following the instructions of the battery
supplier.
●Normally, the batteries should be charged and discharged once every 4 to 6 months. Charging should begin after the UPS shuts down
automatically in the course of discharging, the standard charging time for the standard UPS should be at least 12 hours. Discharge the
battery with the load more than 50%.
6. Notes for battery disposal and battery replacement
1) Before disposing batteries, remove conductive articles such as necklace, wrist watches and rings.
2) If it is necessary to replace any connection cables, please purchase the original materials from the authorized distributors or service
centers, so as to avoid overheat or spark resulting in fire due to insufficient capacity.
3) Do not dispose of batteries or battery packs in a fire, they may explode.
4) Do not open or mutilate batteries, released electrolyte is highly poisonous and harmful to the skin and eyes.
5) Do not short the positive and negative electrodes of the battery, otherwise, it may result in electric shock or fire.
6) Make sure that there is no voltage before touching the batteries. The battery circuit is not isolated from the input potential circuit. There
may be hazardous voltage between the battery terminals and the ground.
7) Even though the input breaker is disconnected, the components inside the UPS are still connected with the batteries, and there are
potential hazardous voltages. Therefore, before any maintenance and repairs work is carried out, switch off the breaker of the battery
pack or disconnect the jumper wire of connecting between the batteries.
8) Batteries contain hazardous voltage and current. Battery maintenance such as the battery replacement must be carried out by qualified
personnel who are knowledgeable about batteries. No other persons should handle the batteries.
7. Safety
nTec declares this device complies with the Directives as listed in this document: EMC 2004/108/WE, LVD 2006/95/WE.

1
INSTRUKCJA OBSŁUGI
Zasilacz awaryjny (UPS)
MODEL: 53923 | 53925
www.qoltec.com
PL

2
Spis treści
Wstęp.................................................................................................................................................................................................................................... 3
1.1 Opis modelu ...............................................................................................................................................................................3
1.2 Opis często używanych symboli ...............................................................................................................................................3
1.3 Schemat poglądowy tylnego panelu ........................................................................................................................................3
1.4 Specyfikacja techniczna.............................................................................................................................................................4
2 Środki ostrożności ............................................................................................................................................................................................................ 4
3 Montaż............................................................................................................................................................................................................................... 5
3.1 Rozpakowywanie........................................................................................................................................................................5
3.2 Procedura okablowania.............................................................................................................................................................5
3.2.1 Uwagi do instalacji .......................................................................................................................................................................................... 5
3.2.2 Instalacja .......................................................................................................................................................................................................... 5
3.3 Procedura podłączenia zewnętrznego modułu akumulatorowego......................................................................................6
3.3.1 Opis zewnętrznego modułu akumulatorowego........................................................................................................................................... 6
3.3.2 Procedura podłączania modułu akumulatorowego dla modeli 6KVA/10KVA........................................................................................... 6
4 Obsługa UPS...................................................................................................................................................................................................................... 6
4.1 Funkcje wyświetlacza.................................................................................................................................................................6
4.2 Wygląd wyświetlacza w poszczególnych trybach pracy .........................................................................................................6
4.2.1 Tryb normalny ................................................................................................................................................................................................. 7
4.2.2 Tryb akumulatora............................................................................................................................................................................................ 7
4.2.3 Tryb obejścia (bypass)..................................................................................................................................................................................... 8
4.2.4 Komunikaty wyświetlacza LCD podczas wykrycia błędu............................................................................................................................. 8
4.3 Eksploatacja................................................................................................................................................................................9
4.3.1 Procedura włączania i wyłączania UPS ......................................................................................................................................................... 9
4.3.2 Przeprowadzanie autodiagnozy akumulatora ............................................................................................................................................. 9
4.3.3 Ustawienia napięcia wyjściowego oraz częstotliwości ...................................................................................................................... 9
4.4 Okresowe sprawdzanie sprawności UPS................................................................................................................... …………10
4.5 Rozwiązywanie problemów.....................................................................................................................................................10
4.6 Czas podtrzymania –model standardowy ............................................................................................................................12
4.7 Monitorowanie UPS przez Internet ........................................................................................................................................13
4.8 Interfejs komunikacyjny –Port RS232....................................................................................................................................13
5 Konserwacja akumulatora.............................................................................................................................................................................................14
6 Wymiana oraz utylizacja akumulatorów ......................................................................................................................................................................14
7 Normy bezpieczeństwa.................................................................................................................................................................................................. 14

3
Wstęp
1.1 Opis modelu
UPS online dostarcza czyste i niezakłócone napięcie elektryczne. Wyposażony w technologię on-line o podwójnej konwersji. Zapewnia
najwyższa ochronę podłączonych urządzeń. Inwerter przekształca prąd zmienny na prąd stały. Prąd stały ładuje akumulator i zasila inwerter.
W przypadku gdy zasilanie sieciowe zawiedzie, akumulatory bezobsługowe zasilają inwerter. Inwerter generuje prąd przemienny
sinusoidalny, który zasila podłączone urządzenia. Podłączone obciążenie jest całkowicie odizolowane od niedoskonałości sieci zasilającej.
Niniejsza instrukcja dotyczy następujących modeli:
Typ
Model
Wejście
Akumulator
Długi czas
podtrzymywani
a
6KVA
6KVA
Pojedyncza faza + N
Zewnętrzny akumulator
10KVA
10KVA
Pojedyncza faza + N
Zewnętrzny akumulator
1.2 Opis często używanych symboli
Podczas użytkowania UPS, mogą pojawić się następujące symbole. Dlatego wszyscy użytkownicy powinni uważnie zapoznać się z tą instrukcją.
1.3 Schemat poglądowy tylnego panelu
Tylny panel modelu 10KVA Tylny panel modelu 6KVA
•Obrazek tylnego panelu jest obrazkiem poglądowym i może różnić się od posiadanego modelu
Symbol
Opis
Symbol
Opis
Ostrzeżenie
Uziemienie
Uwaga wysokie napięcie
Wyciszenie alarmu
Przycisk włącz
Przeciążenie
Przycisk wyłącz
Autodiagnoza akumulatora
Czuwanie
Recykling
Prąd zmienny (AC)
Utylizować zgodnie z lokalnymi
przepisami
Prąd stały (DC)
Akumulator

4
1.4 Specyfikacja techniczna
Model
6KVA
10KVA
Wartość znamionowa
6kVA/4.8kW
10kVA/8kW
Wejście
Układ wejściowy
Jednofazowy z uziemieniem
Zakres napięcia
(120±5)VAC~ (274±5)VAC
Współczynnik mocy
≥0.99
Zakres napięcia w trybie
obejścia (bypass)
(60±5)VAC~ (300±5)VAC (domyślnie: 80VAC~264VAC może być dostosowany przez
oprogramowanie)
Wyjście
Układ wyjściowy
Jednofazowy z uziemieniem
Napięcie znamionowe
230VAC
Współczynnik mocy
0.8
Regulacja napięcia
±1%
Częstotliwość
Tryb
normalny
Częstotliwość wyjściowa synchronizuje się z częstotliwością wejściową kiedy
częstotliwość wejściowa mieści się w przedziale: 46Hz~54Hz
Częstotliwość wyjściowa wynosi 50Hz jeżeli częstotliwość wejściowa nie mieści się w
przedziale 46Hz~54Hz
Możliwość ustawienia częstotliwości 60Hz
Tryb
akumulatora
Odporność inwertera na
przeciążenia
105% ±5% <obciążenia ≤ 125% ± 5% 60s przeniesienie na tryb obejścia (bypass)
125% ±5% <obciążenia < 135% ± 5% 30s przeniesienie na tryb obejścia (bypass)
obciążenie> 135% ± 5%, 100ms przeniesienie na tryb obejścia (bypass)
Czas przełączenia
0ms (Tryb normalny←→Tryb akumulatora)
<4ms (Tryb normalny←→Tryb obejścia - Bypass)
Współczynnik szczytu
3:1
Akumulator
Napięcie akumulatora
192VDC
Ilość akumulatorów
Brak
Brak
Typ akumulatora
akumulator bezobsługowy, szczelny kwasowo-ołowiowy o napięciu 12V/7AH
Czas autonomii (25℃)
100% obciążenia ≥ 5min (Standard)
Prąd ładowania
5.5A
5.5A
Wymiary (L*W*H)mm
425x190x328
533x260x501
Waga (kg)
65
75
2Środki ostrożności
1. Przed użyciem produktu uważnie przeczytaj instrukcję.
2. Używaj produkt zgodnie z instrukcją.
3. Nie przeciążaj UPS.
4. UPS jest wyposażony w akumulator o dużej pojemności. Pod żadnym pozorem nie otwieraj UPS. Otwarcie obudowy stanowi
zagrożenie dla życia na skutek porażenia prądem.
5. Nie zwieraj biegunów akumulatora ponieważ może to grozić porażeniem prądem lub/i pożarem.
6. Nie wkładaj żadnych przedmiotów do kratki wentylacyjnej urządzenia i innych otworów wlotowych.
7. Używaj w suchym i chłodnym miejscu.
8. Nie instaluj urządzenia w pobliżu źródła ciepła, np. ogrzewania elektrycznego lub pieca.
9. Nie umieszczaj UPS w miejscu, gdzie występują silne drgania.
10. W razie pożaru użyj gaśnicy proszkowej. Użycie gaśnicy wodnej może skutkować porażeniem prądem.
11. Gniazdo przyłączeniowe powinno być zamontowane blisko urządzenia i powinno być łatwo dostępne.
12. Nawet jeśli UPS nie jest podłączony do zasilania sieciowego, gniazdo UPS może nadal znajdować się pod napięciem 220V/230V.
13. Nie podłączają do UPS urządzeń użytku domowego (np. suszarka do włosów)
14. Nie wrzucaj akumulatorów do ognia, grozi to eksplozją.
Montaż UPS, wymiana akumulatorów oraz czynności
naprawcze powinny być wykonywane przez wykwalifikowany
serwis posiadający odpowiednie uprawnienia. Ingerencja
użytkownika jest zabroniona ponieważ grozi utratą zdrowia
lub życia.

5
3Montaż
3.1 Rozpakowywanie
1. Wyjmij UPS z pudełka. Upewnij się, że produkt nie został uszkodzony podczas transportu.
2. Upewnij się, że model UPS jest zgodny z zamówieniem.
3. Jeżeli UPS został uszkodzony w dostawie lub model UPS jest niezgodny z zamówieniem, natychmiast skontaktuj się z dostawcą.
3.2 Procedura okablowania
3.2.1 Uwagi do instalacji
1. Nie umieszczaj UPS w pobliżu: wody, łatwopalnych gazów, środków korozyjnych.
2. Postaw UPS tylko w pozycji pionowej. Aby zapewnić dobrą wentylację UPS nie blokuj kratki wentylacyjnej, portu wyjściowego i
bocznych paneli.
3. W przypadku gdy nierozpakowany UPS został umieszczony w niskiej temperaturze, wewnątrz obudowy może wystąpić zjawisko
skraplania pary wodnej. Należy poczekać aż UPS całkowicie wyschnie przed montażem i użyciem. W innym przypadku może to grozić
porażeniem prądem.
3.2.2 Instalacja
Instalacja UPS powinna być wykonana przez wykwalikowany serwis. Dla bezpieczeństwa odetnij zasilanie sieciowe przed instalacją UPS. Jeżeli
jest to model z funkcją długiego czasu podtrzymania, należy również przełączyć wyłącznik zasilania akumulatorowego na pozycję OFF/0.
1) Otwórz pokrywę listwy zaciskowej umieszczoną na tylnym panelu UPS.
2) Dla modelu 6KVA zalecane jest użycie przewodów UL1015 10AWG o przekroju 6mm2lub izolowanych przewodów spełniających
standardy AWG.
3) Dla modelu 10KVAzaleczane jest użycie przewodów UL1015 8AWG o przekroju 10mm2 lub izolowanych przewodów spełniających
standardy AWG.
4) Podłącz przewody wejściowe i wyjściowe do odpowiednich wejść i wyjść na listwie zaciskowej według poniższego schematu:
Uwaga: Upewnij się, że przewody wejścia i wyjścia są mocno dociśnięte
5) Przewodem uziemiającym należy połączyć wszystkie odbiorniki.
6) Upewnij się, że przewody fazowe, zera i uziemienia na wejściu i wyjściu są prawidłowo połączone.
7) Jeżeli rozdzielnia nie jest wyposażona w wyłącznik różnicowo-prądowy należy zainstalować go przy listwie zaciskowej.
8) Wyłącz wszystkie urządzenia obciążające przed podłączeniem ich do UPS. Po podłączeniu, kolejno włącz urządzenia obciążające.
9) Przewody lub gniazda UPS mogą nadal znajdować się pod napięciem, nawet jeśli UPS został wyłączony z zasilania sieciowego.
10) Ładuj akumulator przez 8 godzin przed pierwszym użyciem. Przed podłączeniem akumulatora, przełącz wyłącznik zasilania
akumulatorowego na pozycję OFF/0. UPS rozpocznie automatyczne ładowanie akumulatora.
11) Jeżeli istnieje potrzeba podłączenia do UPS obciążenia o charakterze indukcyjnym, takich jak monitor lub drukarka laserowa, należy
uwzględnić szczytowy prąd rozruchu do obliczenia obciążenia UPS, ponieważ w momencie rozruchu urządzenia te pobierają dużo
większy prąd.
Uwaga: Nie używaj gniazda ściennego jako źródła zasilania UPS, ponieważ prąd znamionowy gniazda jest mniejszy niż maksymalny prąd
pobierany przez UPS. Może to spowodować uszkodzenie lub spalenie gniazda.

6
3.3 Procedura podłączenia zewnętrznego modułu akumulatorowego
3.3.1 Opis zewnętrznego modułu akumulatorowego.
Znamionowe napięcie DC zewnętrznego modułu akumulatorowego wynosi 192VDC. Każdy moduł zawiera 16 bezobsługowych
akumulatorów o napięciu 12V. Istnieje możliwość podpięcia kilku modułów akumulatorowych, aby osiągnąć dłuższy czas podtrzymania.
Wszystkie akumulatory muszą być tego samego typu oraz o tym samym napięciu i pojemności. Nie wolno używać jednocześnie
akumulatorów nowych i starych.
3.3.2 Procedura podłączania modułu akumulatorowego dla modeli 6KVA/10KVA
1) Przed rozpoczęciem podłączania modułu należy wyłączyć UPS i odciąć źródło zasilania.
2) Konieczne jest zainstalowanie odpowiedniego rozłącznika bezpiecznikowego prądu stałego (DC). Obciążenie bezpiecznika nie może
wynosić mniej niż w podanej specyfikacji:
Model
6KVA
10KVA
Napięcie akumulatora
192VDC
192VDC
Prąd akumulatora
34A max.
56A max.
Uwaga: Istnieje możliwość podłączenia akumulatora o pojemności 240VDC
3) Przełącz główny wyłącznik zasilania na pozycję „OFF/0”. Następnie podłącz (po kolei) 16-elementowy moduł akumulatorowy.
4) Podłącz wejściowy kabel zasilający.
5) Przełącz główny wyłącznik zasilania na pozycję „ON/I”. UPS rozpocznie ładowanie modułu akumulatorowego.
6) Podłącz urządzenia obciążające.
4Obsługa UPS
4.1 Funkcje wyświetlacza
1. Przycisk „ON”: Przycisk „ON”: przytrzymaj przez około jedną sekundę, żeby włączyć UPS (jeden sygnał dźwiękowy).
2. Przycisk „OFF”: przytrzymaj przez około jedną sekundę, żeby wyłączyć UPS. Wyłącza urządzenie zarówno w trybie normalnym, jak i
w trybie akumulatora.
3. Przycisk „F”:
a) Autodiagnoza akumulatora: kiedy UPS działa w trybie normalnym, przytrzymanie przycisku „F” przez około pięć sekund (dwukrotny
sygnał dźwiękowy) uruchamia autodiagnozę akumulatora.
b) Funkcja wyciszania w trybie akumulatora /obejścia (bypass): przytrzymaj przycisk „F” przez około pięć sekund, żeby wyciszyć alarm.
Przytrzymaj przycisk „F” ponownie, żeby wznowić alarm.
c) Przełączanie między ekranami wyświetlacza LCD: Przytrzymaj przycisk „F” dłużej niż przez jedną sekundę, ale krócej niż przez dwie
(jeden sygnał dźwiękowy), żeby przełączyć ekran wyświetlacza LCD
4. W skład diod LED wchodzą diody: trybu obejścia (bypass), zasilania sieciowego, inwertera oraz akumulatora.
4.2 Wygląd wyświetlacza w poszczególnych trybach pracy
UPS działa w trzech trybach: normalnym, akumulatora i obejścia (bypass).
W każdym z wyżej wymienionych trybów, na stronie głównej wyświetlacza wyświetla się napięcie wyjściowe oraz częstotliwość wyjściowa.
Jeżeli istnieje potrzeba uzyskania większej ilości danych o UPS, należy przytrzymać przycisk „F”, aby przełączyć ekran wyświetlacza. Jeżeli obecna
strona nie jest stroną główną, UPS powróci do strony głównej po 30 sekundach. Wyświetlacz LCD wyłącza się samoczynnie po jednej minucie
bezczynności, w celu wydłużenia jego żywotności. Naciśnij jakikolwiek przycisk, żeby przywrócić podświetlenie ekranu.

7
4.2.1 Tryb normalny
Wygląd strony głównej na wyświetlaczu w trybie normalnym, ukazuje poniższy obrazek:
Figura 5-2 Tryb normalny
Wyświetlone są ikony zasilania sieciowego oraz inwertera. Widoczna jest również wartość obciążenia oraz poziom naładowania akumulatora.
W trybie ładowania obszar poziomu naładowania akumulatora zmienia się dynamicznie, po zakończonym ładowaniu świeci jednolicie.
1) Jeżeli ikona zasilania sieciowego miga, oznacza to, że wystąpił problem z odwróconą biegunowością (L, N). Może być to
spowodowane niewłaściwym podłączeniem przewodów lub odłączeniem od uziemienia. UPS nadal działa w trybie normalnym. Jeżeli
ikona akumulatora jest zapalona w tym samym czasie, oznacza to, że napięcie lub częstotliwość zasilania sieciowego jest po za
normalnym zakresem wejściowym UPS. UPS działa w trybie akumulatora.
2) Jeżeli obciążenie wynosi powyżej 105%, dwukrotny sygnał dźwiękowy powtarza się co sekundę, w międzyczasie miga ikona
ostrzegawcza, również co sekundę. Odłącz niepotrzebne obciążenie.
3) Jeżeli miga ikona akumulatora, oznacza to, że akumulator nie jest podłączony do UPS lub napięcie akumulatora jest za niskie.
Sprawdź czy akumulator jest poprawnie podłączony do UPS i włącz autodiagnozę akumulatora (przytrzymaj przycisk „F” przez około
pięć sekund). Jeżeli połączenie akumulatora z UPS jest prawidłowe, problem może być spowodowany defektem akumulatora lub
jego zużyciem. Odnieś się do rozdziału 7 „Rozwiązywanie problemów”.
4) Kolejne cztery strony wyświetlacza to:
a) Strona 1 –procent obciążenia
b) Strona 2 –wartość obciążenia
c) Strona 3 –informacje o wejściu
d) Strona 4 - maksymalna temperatura
Uwaga: Podłączenie zasilacza do UPS powinno być przeprowadzone według następujących kroków:
•Podłącz zasilacz do prądu, poczekaj aż jego praca będzie stabilna przed podłączeniem go do UPS. Upewnij się, że do UPS nie jest podłączone
urządzenie obciążające. Następnie włącz UPS zgodnie z procedurą uruchamiania. Po uruchomieniu UPS, podłącz urządzenie obciążające.
•Zalecane jest, aby wybrany zasilacz posiadał dwa razy większą moc niż UPS.
4.2.2 Tryb akumulatora
Wygląd strony głównej na wyświetlaczu w trybie akumulatora, ukazuje poniższy obrazek:
Figura 5-3 Tryb akumulatora
Wyświetlone są ikony zasilania sieciowego oraz inwertera. Widoczna jest również wartość obciążenia oraz poziom naładowania akumulatora.
Jeżeli w tym samym czasie miga ikona zasilania sieciowego, oznacza to, że zasilanie sieciowe nie zachowuje prawidłowych parametrów.
1) Kiedy UPS działa w trybie akumulatora, urządzenie wydaje sygnał dźwiękowy co 4 sekundy. Przytrzymaj przycisk „F” przez około pięć
sekund, aby wyciszyć alarm, przytrzymaj ponownie około pięć sekund, aby przywrócić alarm.
This manual suits for next models
1
Table of contents
Languages:
Other Qoltec UPS manuals