RAPIX Xi DALI Long Range Occupancy Sensor DGOZ-LRS-PRLLSW
Page 2 of 4
Specifications
Up to 12 metres, dependant on ceiling height.
See diagrams for typical cases.
16 V dc (nominal), with suitable operation from 9.5 V –22.5 V
DALI input and auxiliary input are mains voltage tolerant
4 Tunnel Terminal block
Each tunnel suitable for 1 x 2.5 mm2or 2 x 1.5 mm2
2 Tunnel Terminal block
Each tunnel suitable for 1 x 2.5 mm2or 2 x 1.5 mm2
Maximum auxiliary cable length
25 m –twin core mains cable ≥ 0.75 mm2
Momentary switch, toggle switch or motion sensor voltage-free contacts
DALI Operation: 1 x green, rear near terminal block
Identification: 1 x green, front through sensor lens
Ambient operating temperature
Ambient storage temperature
0% to 95% RH non-condensing
Enclosure –Flame retardant Polycarbonate, UL 94V-0
Number of DALI Short addresses used
None –this sensor does not use a DALI Short Address
DALI addressing types supported
Short Addresses, Group Addresses, Scenes, Broadcast
Number of Xi extended addresses used
Xi occupancy sensors per DALI line
Additional addressing types*
RAPIX Zones, RAPIX Flags, RAPIX Operating Properties
RAPIX features and additional addressing types work with other RAPIX products.
Commissioning
Use the free RAPIX Addressing or RAPIX Integrator software, available at ozuno.com.
A RAPIX USB Interface or Zone Controller is required to connect the commissioning software / PC to the DALI line.
Mounting
The recommended mounting height is in the range 6 to 10 metres.
Mount into a 61-72mm diameter hole in the ceiling. Sensor is retained by the
pre-fitted springs.
Optional Surface Mount Adaptor
(order separately)
Screw the Surface Mount adaptor over a conduit box , or break out the
conduit entry knockouts and screw the Surface Mount Adaptor directly to
the mounting surface.
Remove pre-fitted retaining springs and plastic posts from the Sensor using
side cutters. Wire as normal and clip Sensor into the Surface Mount Adaptor.