RBH Sound UNC100 User manual

UNC100 Integra Manual
New Generation
Building Security
July 30, 2014 –V1.2

UNC100 Axiom Hardware Manual V1.2 RBH Access Technologies Inc.
Page 2of 20
Copyright Notice
Copyright©1995-2014 by RBH Access Technologies Inc.
All rights reserved Worldwide. Printed in Canada. This publication has been provided pursuant to an
agreement containing restrictions on its use. No part of this book may be copied or distributed,
transmitted, stored in a retrieval system, or translated into any human or computer language, in any
form or by any means, electronic, mechanical, magnetic, manual, or otherwise, or disclosed to third
parties without the express written consent of RBH Access Technologies Inc., Mississauga, Ontario,
Canada.
Trademark
Integra™is the trademark of RBH Access Technologies Inc. Windows is a trademark of Microsoft
Corporation. All other product names mentioned herein are the property of their respective owners.
Use of a term in this book should not be regarded as affecting the validity of any trademark or service
mark.
Disclaimer
This book is provided as is, without warranty of any kind, either express or implied, including but not
limited to performance, merchantability, or fitness for any particular purpose. Neither RBH Access
Technologies Inc. nor its dealers or distributors shall be liable to any person or entity with respect to any
liability, loss, or damage, caused, or alleged to have been caused directly or indirectly by this
information. Further RBH Access Technologies Inc. reserves the right to revise this publication, and to
make changes to the content hereof from time to time, without the obligation of RBH Access
Technologies Inc. to notify any person or organization of such revision or changes.
RBH ACCESS TECHNOLOGIES INC.
2 Automatic Road, Suite 108
Brampton, Ontario
CANADA
L6S 6K8

UNC100 Integra Hardware Manual V1.2 RBH Access Technologies Inc.
Page 3of 20
Revision History
Editor
Revision
Comment
Date mm/dd/yy
DM
1.0
First Release
08/13/13
RB
1.1
Removed reference to fire input
Removed partial firmware upgrade (formats)
Added dip-switch 5
Added Revision History
Updated copyright
Eliminated reference to rack mount type
Clarified the use of the Power Input/ Output
Moved all cable specs to one location.
Moved all input specs to one location.
Moved all output specs to one location.
Reduced the number of pages.
03/19/14
DM
1.1
Minor editing of text.
03/24/14
RB
1.2
Changing output voltage from
12V to 12v –14v
Changing battery charger spec
07/21/14
DM
1.2
Editing of text:
-Changed graphic
-Removed relevant information
-Confirmed correct specifications
07/30/14
DM
1.2
Added ULC text.
Reconfigured order of pages.
08/06/14

UNC100 Axiom Hardware Manual V1.2 RBH Access Technologies Inc.
Page 4of 20
New Generation............................................................................................................................................. 1
Building Security ............................................................................................................................................ 1
Copyright Notice ............................................................................................................................................ 2
Trademark...................................................................................................................................................... 2
Disclaimer....................................................................................................................................................... 2
Revision History ............................................................................................................................................. 3
Panel Graphics ............................................................................................................................................... 6
Introduction ................................................................................................................................................... 7
ULC-S319-05 III.............................................................................................................................................. 7
Battery Charger.............................................................................................................................................. 7
Reverse Battery Protection............................................................................................................................ 7
Battery Test.................................................................................................................................................... 7
Fuse Monitoring............................................................................................................................................. 7
Diagnostic LED’s ............................................................................................................................................. 7
Tamper Detection .......................................................................................................................................... 7
Power Input / Output..................................................................................................................................... 8
Communication.............................................................................................................................................. 8
Networks........................................................................................................................................................ 8
RS485 Applications......................................................................................................................................... 8
DIP Switch Settings ........................................................................................................................................ 8
Controller Addressing .................................................................................................................................... 9
RS485 (HOST) Port Baud Rate Selection ...................................................................................................... 10
Host Connection........................................................................................................................................... 11
PC to UNC100 Connection –RS485 Wiring.................................................................................................. 11
UNC100 TCP/IP Connection ......................................................................................................................... 12
Reader Interface .......................................................................................................................................... 14
Reader Connection ...................................................................................................................................... 14
Outputs ........................................................................................................................................................ 15
Switching Inductive Devices (Locks, Bells) ............................................................................................... 15
Output Operation .................................................................................................................................... 16
General Purpose Output ...................................................................................................................... 16
Lock Output.......................................................................................................................................... 16
Handicap Output.................................................................................................................................. 16
Forced / Tamper................................................................................................................................... 16
Modem Power Output......................................................................................................................... 16
Supervised Inputs......................................................................................................................................... 17

UNC100 Integra Hardware Manual V1.2 RBH Access Technologies Inc.
Page 5of 20
Input Circuit Types ....................................................................................................................................... 17
Input Applications ........................................................................................................................................ 18
Request to Exit (RTE)................................................................................................................................ 19
Door Contact (DC) .................................................................................................................................... 19
General Purpose ...................................................................................................................................... 19
Access Point Operating Modes .................................................................................................................... 19
High Security ........................................................................................................................................ 19
Unlocked .............................................................................................................................................. 19
Tamper................................................................................................................................................. 19
Lockout Alarm ...................................................................................................................................... 19
Door Held Open Warning..................................................................................................................... 19
Door Held Open Alarm......................................................................................................................... 19
Keypad / Reader Combination............................................................................................................. 19
Access Granted .................................................................................................................................... 19
Access Denied ...................................................................................................................................... 19
UNC100 Specification................................................................................................................................... 20
Cable Specification....................................................................................................................................... 20

UNC100 Axiom Hardware Manual V1.2 RBH Access Technologies Inc.
Page 6of 20
Panel Graphics

UNC100 Integra Hardware Manual V1.2 RBH Access Technologies Inc.
Page 7of 20
Introduction
The UNC100 has been designed as a two door access control panel with a built in local area network
interface, that can also provide a single door in/out access point.
The network interface also utilizes a POE (power over Ethernet) converter.
ULC-S319-05 III
For ULC-S319-05 III compliance, all wiring into the panel’s cabinet must enter through metal conduit.
Also be sure to mount the panel in a protected area.
Battery Charger
The battery charger routes input power from the 13.8v input source or POE module and constantly
monitors the battery voltage.
Reverse Battery Protection
A combination of a three ampere diode and a 1.6 amp thermal fuse protects against accidental
connection of a battery in the reverse direction.
Battery Test
A battery test cycle is operator initiated or scheduled. When initiated the charger is turned off and a
24Ω resistor provides a load to the battery for about ten seconds. If during this period the voltage drops
below 10 volts a battery alarm message is sent to the host, otherwise a battery normal message is sent.
Fuse Monitoring
Besides monitoring the battery voltage the UNC100 also monitors the input voltage (DC), auxiliary
voltage (aux) and the reader voltage (reader) and reports to the host whenever the state changes.
Diagnostic LED’s
The RS485 circuit has a red and green LED to indicate when a signal is received or transmitted.
Host Comms LED is a bicolour LED that turns red when receiving data from the host, and turns green
when transmitting of data.
The Run LED will flash slowly when connected to the host and quickly when not connected.
The Trouble LED will flash when there is a power problem such as a low battery or low auxiliary power is
detected.
Tamper Detection
A tamper wire may be connected to JP1 located close to the center of the board. A short to this input is
normal and an open is alarm.

UNC100 Axiom Hardware Manual V1.2 RBH Access Technologies Inc.
Page 8of 20
Power Input / Output
Located on the top right corner of the board is a jumper that selects if the power terminals are to be
used to supply power or provide power. Select “OUT” when using a POE supply and require 13.8V @
500ma for other equipment.
When not using POE, the jumper should be set to “IN”.
The UNC100 controller requires 13.8VDC to be supplied from an external source. (Note: Although the
unit can run on 12VDC, you will need 13.8VDC to be able to charge backup batteries.
Communication
The UNC100 has one RS485 port and an Ethernet 10/100 interface. Communications from the host
computer running Integra™software can be achieved in the following ways; either via the Ethernet
interface or via RS485 through a direct connection to a designated channel. The UNC100’s RS485
channel may be programmed as either NONE or INTEGRA. Use the DIP switch to select baud rate for
Host communications as 9600, 38400, 57600, or 115200.
Networks
There are two networks supported by the UNC100 these are:
1) Host Communications through the Ethernet or direct connection.
2) Integra Communications for devices such as additional IRC-2000s or URC-2000s starting at address
2, and PC100s.
RS485 Applications
Application name
Description
None
No connection to other devices.
Integra
The Integra selection connects the UNC100 controller to
other Integra units (e.g. IRC-2000s and URC-2000s) on a high-
speed RS485 network.
DIP Switch Settings
The UNC100 DIP switch controls the device’s address and serial port baud rate.
Note: To Clear Panel memory –All DIP switches must be off and the unit powered off and
on.
DIP Switch
DIP Switch
Function
1 - 4
Controller Address
5
Ethernet Secure Mode1
6,7
Controller Baud Rate
8
Not used
1DIP switch 5 up will enables Ethernet Secure Mode. This will prevent access to the panel’s programming through
the Ethernet.

UNC100 Integra Hardware Manual V1.2 RBH Access Technologies Inc.
Page 9of 20
Controller Addressing
Use DIP switches 1, 2, 3, and 4 to select the controller address. The address is binary coded and the
switch settings for all fifteen possible addresses are given below.
Controller Addressing
Switch 1
Switch 2
Switch 3
Switch 4
Address
Off
Off
Off
Off
Clear Memory
On
Off
Off
Off
1
Off
On
Off
Off
2
On
On
Off
Off
3
Off
Off
On
Off
4
On
Off
On
Off
5
Off
On
On
Off
6
On
On
On
Off
7
Off
Off
Off
On
8
On
Off
Off
On
9
Off
On
Off
On
10
On
On
Off
On
11
Off
Off
On
On
12
On
Off
On
On
13
Off
On
On
On
14
On
On
On
On
15

UNC100 Axiom Hardware Manual V1.1 RBH Access Technologies Inc.
Page 10 of 20
RS485 (HOST) Port Baud Rate Selection
The controller's serial port baud rate is set with controller DIP switches 6 and 7. This setting determines
the speed used to communicate with the PC; the controller baud rate must be the same as the baud rate
set for the port within the Integra™ software. The default baud rate is 9600.
Controller Baud Rate Selection
DIP Switch 6
DIP Switch 7
Baud Rate
OFF
OFF
9600
ON
OFF
38400
OFF
ON
57600
ON
ON
115200

UNC100 Axiom Hardware Manual V1.1 RBH Access Technologies Inc.
Page 11 of 20
Host Connection
The controller is connected to either a serial port on the PC or through the local Ethernet via a static IP
address. The means of communication is configured in the Integra™software under the network’s
properties under the Comms tab.
PC to UNC100 Connection –RS485 Wiring
Cable Specification
Twisted pair, shielded, 18 to 22 AWG
Maximum Cable Length
2000-4000 feet (600-1200 meters)
For ULC-S319-05 III compliance, all wiring into the panel’s cabinet must enter through metal conduit.
Also be sure to mount the panel in a protected area.

UNC100 Axiom Hardware Manual V1.1 RBH Access Technologies Inc.
Page 12 of 20
UNC100 TCP/IP Connection
The master controller in some installations may not be directly connected to the PC and may be linked by
the local Ethernet. The system supports a static IP address only [default address is 192.168.168.125]. To
change the IP address of the unit you can either use IP Locator [a utility program provided by RBH] or
Telnet.
PC to UNC100 Connection - LAN
For ULC-S319-05 III compliance, all wiring into the panel’s cabinet must enter through metal conduit.
Also be sure to mount the panel in a protected area.

UNC100 Axiom Hardware Manual V1.1 RBH Access Technologies Inc.
Page 13 of 20
Name
Defaults
Description and notes
IP ADDRESS
192.168.168.125
Local Ethernet address.
SUBNET MASK
255.255.255.0
Local Ethernet mask
IP GATEWAY
0.0.0.0
For future use when DNS option becomes available.
PORT NUMBER
3002
Primary port number.
ALT PORT NUMBER
3003
Alternate port number applies to “LAN” application.
RS485
INTEGRA
Set the RS485 to INTEGRA in order to connect via RS485 to the PC
and other Integra™ devices.
Telnet Password
password
This is a string of up to 10 characters that allows the user access
to this program.
Integra™ Network
URC2000 panels may also be used in place of IRC-2000 panels.
*** When UNC100 panels are used in conjunction with IRC2000 and URC2000 panels the last
panel in the line must be terminated.

UNC100 Axiom Hardware Manual V1.1 RBH Access Technologies Inc.
Page 14 of 20
Reader Interface
Two standard Wiegand interfaces provide the following connections for typical proximity readers.
Thermal fuse protected power (500ma @13vdc).
Reader Tamper Input(s): Initially, if open it will be ignored, but once a short is connected it will report a
reader tamper alarm whenever the input is opened.
LED and beeper outputs are open collector current limited to 100ma.
Reader Connection
RC-2 to 12-Volt Reader Connection Diagram1
For ULC-S319-05 III compliance, all wiring into the panel’s cabinet must enter through metal conduit.
Also be sure to mount the panel in a protected area.
1Reader wire colours may vary for different reader manufactures. Please verify your wiring.

UNC100 Axiom Hardware Manual V1.1 RBH Access Technologies Inc.
Page 15 of 20
Outputs
There are two form C relays and two open collector outputs that can be programmed as general purpose
or default applications. The contacts are rated for 2 amperes at 30vdc. The recommended use of the
relays is to provide isolated outputs for driving electric strikes or magnetic locks at a maximum voltage of
24v. The open collector outputs are current limited to 100 milli-amperes direct current only.
Number
Default Application
Type
1
Lock Reader 1
Relay form C
2
Forced Entry Alarm Reader 1
Open Collector (100ma)
3
Lock Reader 2
Relay form C
4
Forced Entry Alarm Reader 2
Open Collector (100ma)
Switching Inductive Devices (Locks, Bells)
Exercise caution when switching an inductive load. Inductive devices include external relay, solenoids,
bells, and door locks. All of these devices generate extremely high voltage spikes (several thousand volts)
when applied power is removed. Possible disruption of operation could occur if this interference gets on
to the electronic circuit board.
This interference can be suppressed by placing a diode (1N4001 or similar) across the lock or other
inductive device being switched. Connect the diode cathode (end with band) to the positive terminal
and the other end to the negative terminal. The diode must be placed at the device being switched and
not at the controller.

UNC100 Axiom Hardware Manual V1.1 RBH Access Technologies Inc.
Page 16 of 20
Output Operation
General Purpose Output
General Purpose Outputs are outputs that are user controlled. They are activated and de-activated by
user defined links and schedules.
Lock Output
For magnetic locks, the relay should be configured from the PC as On State de-energized for fail-safe
operation. If power fails (AC and battery) the power to the magnetic lock is removed and the door is
opened.
Handicap Output
This output is used to drive door operators. It turns on in less than one second after the Lock Output is
turned on, and stays on until the Lock Output is turned off. Only designated cardholders will activate this
output.
Forced / Tamper
The Forced/Tamper output turns on if the door is forced open or if a reader tamper is detected. This
output remains on for as long as the alarm condition exists.
Modem Power Output
The Modem Power Output is a normally activated output that is used to reset a modem by momentarily
removing the power from the modem.
For ULC-S319-05 III compliance, all wiring into the panel’s cabinet must enter through metal conduit.
Also be sure to mount the panel in a protected area.

UNC100 Axiom Hardware Manual V1.1 RBH Access Technologies Inc.
Page 17 of 20
Supervised Inputs
The UNC100 has 4 fully supervised inputs. Each input is individually programmable from the PC
Each input has four states: Restore, Alarm, Trouble, and Illegal. Trouble is reported if a short or break is
detected on a supervised circuit and illegal is reported if the measured loop resistance lies between valid
states. For example, if the circuit type is programmed as “2 resistors normally closed”, 1k represents a
restored state and 2k represents an alarm state. If the loop resistance changes by more than 15% but
not enough to enter the next state, an illegal state is reported.
Input Circuit Types
The UNC-100 supports seven different input circuit types ranging from no resistor for low security
applications to two resistor normally closed circuits where the highest security is required.
Normally Closed, No Resistor
Loop Resistance
State
Short
Restore
Open Circuit
Alarm
Normally Open, No Resistor
Loop Resistance
State
Short
Alarm
Open Circuit
Restore
Normally Closed, One Resistor
Loop Resistance
State
Short
Trouble
1k
Restore
Open Circuit
Alarm
Normally Closed, Two Resistor
Loop Resistance
State
Short
Trouble
1k
Restore
2k
Alarm
Open Circuit
Trouble

UNC100 Axiom Hardware Manual V1.1 RBH Access Technologies Inc.
Page 18 of 20
This circuit provides a high degree of supervision and detects both short and open circuit fault
conditions. Use this circuit in high security applications.
This circuit type is used where normally open and normally closed contacts are used in the same loop.
Input Applications
Number
Default Application
1
General Purpose
2
RTE (Request to Exit) Reader A
3
DC (Door Contact) Reader A
4
RTE (Request to Exit) Reader B
5
DC (Door Contact) Reader B
Normally Open, One Resistor
Loop Resistance
State
Short
Alarm
1k
Restore
Open Circuit
Trouble
Normally Open, Two Resistor
Loop Resistance
State
Short
Trouble
1k
Alarm
2k
Restore
Open Circuit
Trouble
Normally Open And Normally
Closed, One Resistor
Loop Resistance
State
Short
Alarm
1k
Restore
Open Circuit
Alarm

UNC100 Axiom Hardware Manual V1.1 RBH Access Technologies Inc.
Page 19 of 20
Request to Exit (RTE)
The Request to Exit [RTE] input is connected to a push button mounted on the door or to a motion
detector mounted near the door. A normally open or normally closed button can be used and the circuit
type can be programmed from the PC. Activating the RTE input will unlock the door. The RTE can be
disabled by time zone.
Door Contact (DC)
The Door Contact [DC] input monitors the state of the door. Forced entry, door held open alarm, and
door held open warning require monitoring of the door state.
General Purpose
The General Purpose selection is used for inputs that are not directly associated with the access point.
Access Point Operating Modes
High Security
The Red LED flashes quickly.
In High Security Mode, only cardholders with High Security Privilege are allowed access.
Unlocked
The green LED turns on to indicate the door is unlocked.
Tamper
The Buzzer sounds continuously.
Lockout Alarm
The Buzzer beeps rapidly.
A lockout alarm occurs when a user-defined number of “Access Denied‟ messages occur.
These messages can include “Invalid Card Number‟, “No Access at this Time‟, “No Access at this Reader‟,
or “Invalid PIN Code‟.
Door Held Open Warning
The Buzzer beeps slowly.
Door Held Open Alarm
The Buzzer sounds continuously.
Keypad / Reader Combination
The Buzzer emits a short beep every second after a card is presented, until a PIN is entered.
Access Granted
The Buzzer emits one long beep and the green LED turns on for the duration of the unlock time.
Access Denied
The Buzzer emits two short beeps and the red LED flashes twice.
For ULC-S319-05 III compliance, all wiring into the panel’s cabinet must enter through metal conduit.
Also be sure to mount the panel in a protected area.

UNC100 Axiom Hardware Manual V1.1 RBH Access Technologies Inc.
Page 20 of 20
UNC100 Specification
Controller Power Requirements
12 –14vdc
Current Consumption
250mA
Processor
32 bit micro controller
Memory
2MB
Panels per Network
16
HOST Ethernet speed
10/100 TCP/IP Ethernet, RS485 4 wire
HOST RS485 Speed
9600, 38400, 57600, 115200 baud
Clock/RAM backup battery
3v Lithium battery CR1632
Real Time Clock
Built-in as standard
Watch Dog Circuit
Built-in as standard
Board Dimensions
H 5½ in x W 5 in (14 x 12½ cm)
Operating Temperature
0 to 70C (35 - 150F)
Operating Humidity
20 to 85% RH (non-condensing)
Cable Specification
Circuit Function
Cable type
Length
PC To Controller (Ethernet)
CAT5 communications cable
323 feet (100 meters)
PC To Controller (RS485)
Twisted pair, shielded, stranded
18 to 22 AWG
2000-4000 feet
(600-1200 meters)
Reader
20 to 22 AWG, 6 or 8-conductor,
stranded, shielded (not twisted)
500 feet (150 meters)
Input / Output Port Circuit Loop
2-conductor, 20 to 22 AWG
1000 feet (300 meters)
Other manuals for UNC100
1
Table of contents
Other RBH Sound Controllers manuals
Popular Controllers manuals by other brands

Kitz
Kitz ESR Series Operation manual

Sunricher
Sunricher SR-2850C manual

Chromalox
Chromalox IntelliTrace ITC 1 Installation & operation manual

Weathermatic
Weathermatic SmartLink SmartLine owner's manual

Ametek
Ametek SHZF2 SCR Series Instruction, Operation and Maintenance Manual

BARTH Elektronik
BARTH Elektronik STG-65 manual