Operation SHZF2/SHZF3 SCR Power Controller
12 Ametek HDR Power Systems Rev 2
a. Set the ZERO and SPAN controls fully CCW (counterclockwise).
b. Connect a voltmeter across terminals X1 and X3 of the SHZF2/SHZF3. Set the voltmeter range to
measure full input voltage.
c. Close the fused disconnect or circuit breaker to apply power to the SHZF2/SHZF3. Turn the
Process controller on and set to demand zero power output.
Figure 4.2 Process Controller Input Connections
d. Adjust the ZERO control CW until the output just turns on, then turn the ZERO control CCW just to
the point where the output voltage reading is zero.
e. Set the Process controller to demand 100% output. Observing the voltmeter, adjust SPAN CW
just to the point where the reading is below the maximum output voltage. Then adjust SPAN CW
just to the point where the meter reading is at maximum.
Note: The output voltage measurement on Zero Fired Power Controllers with a digital voltmeter
will be erratic except at full output. This is due to the variable pulses to regulate the output.
f. Repeat steps 4.3d and 4.3e as necessary, to ensure proper control adjustments have been made.
g. Turn off the line power to the SHZF2/SHZF3 and disconnect the test equipment. The
SHZF2/SHZF3is now ready for automatic operation.
4.4 Remote Manual Control with a Potentiometer
Some applications only require a manual control input and not a closed loop input from a process
controller. This potentiometer may be located on a remote panel near other controls related to the
process being powered by the SHZF2/SHZF3. It may be calibrated to correspond to a percentage of
rated power output, process temperature, or some other parameter. The potentiometer may by 500
to 5 k, and should be rated at 1/2 watt, minimum.
a. With the power to the SHZF2/SHZF3 turned off, connect the potentiometer as shown in Figure 4.3.
The CW position is the full power output position. Terminal TB1-5 is internally connected to a
positive dc voltage source.
b. Connect a voltmeter across terminals X1 and X3 of the SHZF2/SHZF3. Set the voltmeter range to
measure the full output voltage.
c. Set the SPAN control and remote potentiometer fully CCW.
d. Close the fused disconnect or circuit breaker to apply power to the SHZF2/SHZF3. The unit
should be energized, with no output.
e. Adjust the ZERO control CW until the output just turns on, then turn the ZERO control CCW just to
the point where the output voltage reading is zero.
WARNING - ELECTRIC SHOCK CAN KILL
HAZARDOUS VOLTAGES exist at the output terminals and at the load when
the input voltage is connected. This condition exists even when the Controller is
set to deliver zero output. Always remove power and properly lock out power to
the unit before attempting any service, including the load.