
Voltage Monitor – Instruction Manual
Model 520603-2V150
P/N 520603-2V150 • REV. D, 8/31/21 • © RAILWAY EQUIPMENT CO.
4.1 Digital Display
The idle screen displays the input voltage. If only channel 1 has input voltage, only channel
1 will be displayed. If both channels are monitoring voltage sources, both will be displayed.
If the optional current or temperature probes are being used, the lower screen will alternate
between displaying channel 2 voltage, temperature, and current. With only channel 1
powered, the following screens will be scrolled through when the MODE button is
depressed:
PASSWORD ___- The password to adjust parameters is 5. It is entered by pressing the
INCREASE button until 5 appears in the parameter field.
MAX VCH1
SET __._ - This displays the high voltage setpoint parameter for channel 1. It can be
adjusted from 0 to 50.0 VDC by use of the INCREASE or DECREASE push buttons. If the
input voltage rises above the setpoint, the channel 1 output relay will change state and the
channel 1 CHANNEL OK LED will go out. Factory default is 50.0 VDC.
LOW VCH1
SET __._ - Low voltage setpoint for channel 1, adjustable from 0 to 50.0 VDC.
If the input voltage falls below the setpoint, the output relay will change state and the
CHANNEL OK LED will go out. Factory default is 0 VDC.
DELAY CH1
SET ___ - Delay time in seconds before a voltage falling outside the parameters will
trigger a fault. This parameter is adjustable from 1 to 600 seconds. Factory default is 10
seconds.
If a voltage input is added on channel 2, in addition to the input on channel 1, the following
additional screens to appear as the MODE button is used:
MAX VCH2
SET __._ -High voltage setpoint for channel 2. Voltage range is 0 to 150.0 VDC
Factory default is 150.0 VDC.
LOW VCH2
SET __._ - Low voltage setpoint for channel 2. Voltage range is 0 to 150.0 VDC.
Factory default is 0 VDC.
DELAY CH2
SET ___ - Delay time in seconds for channel 2. Range is 0 to 600 seconds.
Factory default is 10 seconds.
There is an optional amp probe available which can be set up to trip the same relay as a
voltage fault will trip on Channel 2. The addition of the current probe will cause the
following additional screens to appear:
HIGH AMP
SET ___ - Parameter for amp setting above which channel 2 will change relay State.
Amp range is -120 to +120 amps. Factory default is +120 amps.