RectorSeal SS1 User manual

INSTALLATION INSTRUCTIONS
Technical Support Call 1-800-231-3345
PRODUCT CODE 97632
MODEL SS1 LOW VOLTAGE CONDENSATE OVERFLOW SHUTOFF SWITCH
Safe-T-Switch Model SS1
HORIZONTAL INSTALLATION (see Figs. 1 & 2):
1. Glue ¾” stub onto drain pan outlet adapter.
2. Press switch/cap assembly firmly into top 1” opening in Tee, until the rim is flush against the Tee opening. If more sensitivity is desired, the
switch can be threaded out of the cap. DO NOT GLUE THE SWITCH/CAP INTO THE TEE.
3. Glue 1”x ¾” bushing into remaining 1” Tee outlet.
4. Glue bushed inlet of Tee onto ¾” stub from pan outlet. Tee may be sloped up to 45°from pan outlet. If more slope is needed, see VERTICAL
INSTALLATION, below.
5. For plugged installation on auxiliary outlets, seat plug firmly into ¾” outlet of Tee, ensuring it is water tight. DO NOT GLUE. Pipe tape may
be required to ensure seal.
6. For inline installation, glue ¾” outlet of Tee onto drain line.
7. Wire the switch as per instructions under Wiring, below
8. Test the switch by liting the float while the unit is running. If wired correctly, the unit will stop.
9. Test all drain and fitting connections for plumbing leaks.
10. Test switch sensitivity: Plug drain downstream from installation point and run unit to fill pan. Float should rise and unit should stop before pan
overflows. If the pan overflows, reposition the float lower by either:
A. plumbing the entire assembly lower, or
B. loosening the jamb nut on the threaded stem and adjust the height of the float as necessary.
Test for proper sensitivity. Retighten jamb nut.
11. Ax warning sticker to air handler or condenser unit.
Connect to primary
drain pan outlet
Connect to auxiliary
drain pan outlet
Figure 1: Horizontal (plugged) installation for
auxiliary drain outlets.
Figure 2: Horizontal (Inline) installation.
VERTICAL INSTALLATION (see Figs. 3 & 4)
1. Glue ¾” stub onto drain pan outlet adapter.
2. Remove switch/cap assembly from top 1” Tee inlet and insert into remaining 1” Tee inlet so that rim is flush against the Tee opening. If more
sensitivity is desired, the switch can be threaded out of the cap. DO NOT GLUE THE SWITCH CAP INTO THE TEE.
3. Glue 1”x ¾” bushing into the open 1” Tee inlet.
4. Glue bushed inlet of Tee onto ¾” stub from pan outlet. Tee may be sloped up to 45°in either direction by rotating on stub.
5. For plugged installation on auxiliary outlets, seat plug firmly into ¾” outlet of Tee, ensuring it is water-
tight. DO NOT GLUE. Pipe tape may
be required to ensure the seal. Ensure Tee is level or sloped downward from the pan outlet. If upward slope is unavoidable, adjust float switch
downward out of cap by turning clockwise 1/8”.
Connect to auxiliary
drain pan outlet
Figure 3: Vertical (plugged) installation
for auxiliary outlets
Figure 4: Vertical (Inline) installation.
Connect to primary
drain pan outlet
INSTALLATION:
NOTICE: Failure to read and comply with all warnings, cautions and instructions prior to starting installation may
cause personal injury and/or property damage and void the warranty.

®Instructions for “Safe-T-Switch SS1 Directional Cleanout Tool”
1. Remove SS1 Cup/Float subassembly from SS1 body (i.e. the Tee).
2. Clear debris or any other obstacles inside SS1 body.
3. Route the Cleanout Tool into SS1 body. Either upstream or downstream depending on where
blockage is. Insert the rubber nozzle portion into the 3/4" pipe glued to SS1 body on the
blockage side.
4. Attach a pressurizing (or vacuuming) device (such as RectorSeal Might Pump) to Cleanout Tool’s
rigid plastic opening. Pump or vacuum until the blockage is cleared.
5. Disconnect the pressurizing (or vacuuming) device from Cleanout Tool.
6. Remove Cleanout Tool and hang it outside of the SS1 body.
7. Insert SS1 Cup/Float subassembly into SS1 body. Test SS1 function.®
®Instructions for “Safe-T-Switch SS1 Directional Cleanout Tool”
1. Remove SS1 Cup/Float subassembly from SS1 body (i.e. the Tee).
2. Clear debris or any other obstacles inside SS1 body.
3. Route the Cleanout Tool into SS1 body. Either upstream or downstream depending on where
blockage is. Insert the rubber nozzle portion into the 3/4" pipe glued to SS1 body on the
blockage side.
4. Attach a pressurizing (or vacuuming) device (such as RectorSeal Might Pump) to Cleanout Tool’s
rigid plastic opening. Pump or vacuum until the blockage is cleared.
5. Disconnect the pressurizing (or vacuuming) device from Cleanout Tool.
6. Remove Cleanout Tool and hang it outside of the SS1 body.
7. Insert SS1 Cup/Float subassembly into SS1 body. Test SS1 function.®
®Instructions for “Safe-T-Switch SS1 Directional Cleanout Tool”
1. Remove SS1 Cup/Float subassembly from SS1 body (i.e. the Tee).
2. Clear debris or any other obstacles inside SS1 body.
3. Route the Cleanout Tool into SS1 body. Either upstream or downstream depending on where
blockage is. Insert the rubber nozzle portion into the 3/4" pipe glued to SS1 body on the
blockage side.
4. Attach a pressurizing (or vacuuming) device (such as RectorSeal Might Pump) to Cleanout Tool’s
rigid plastic opening. Pump or vacuum until the blockage is cleared.
5. Disconnect the pressurizing (or vacuuming) device from Cleanout Tool.
6. Remove Cleanout Tool and hang it outside of the SS1 body.
7. Insert SS1 Cup/Float subassembly into SS1 body. Test SS1 function.®
6. For inline installation, glue ¾” outlet of Tee onto drain line.
7. Wire switch according to instructions under Wiring, below.
8. Test all drain and fitting connections for plumbing leaks.
9. Test switch sensitivity: plug drain downstream from installation point and run unit to fill pan. Float should
rise and unit should stop before pan
overflows. If pan overflows, reposition float lower by either:
A. plumbing entire assembly lower, or
B. turning switch assembly counter-clockwise /” away from cap/plug, so that it stops unit sooner in response to rising water.
10. Ax warning sticker to air handler or condenser unit.
Furnace / A.C.
Figure 5: Wiring Diagram for Unit Shutdown
Red
White
Green
Yellow
From Thermostat
To Switch
Wire Nut
WIRING (see g. 5)
1. WARNING: Disconnect power to unit at main panel prior to performing electrical work.
2. If not present, it is recommended that an inline fuse be installed to protect 24-volt circuit and time
delay to avoid rapid cycling of equipment.
3. Locate 24-volt thermostat cable entering the air handler unit.
4. Disconnect or cut the red wire and connect to switch lead using wire nut. Connect other switch lead
to air handler terminal. Incorporating switch in red circuit shuts down entire unit. If placed in the
yellow circuit, fan continues to run (inhibits mold during long absences.)
5. Test switch by liting float while unit is running. If wired correctly, unit will stop when float is lited.
INSTRUCTIONS
Safe-T-Switch SS1 Directional Cleanout Tool
1. Remove SS1 Cup/Float subassembly from SS1 body. (i.e. the Tee).
2. Clear debris or any other obstacles inside SS1 body.
3. Route the Cleanout Tool into SS1 body, either upstream or
downstream depending on where blockage is. Insert the rubber
nozzle portion into the 3/4” pipe glued to SS1 body on the blockage
side.
4. Attach a pressurizing (or vacuuming) device (such as RectorSeal
Mighty Pump™) to Cleanout Tool’s rigid plastic opening. Pump or
vacuum until the blockage is cleared.
5. Disconnect the pressurizing (or vacuuming) device from Cleanout
Tool.
6. Remove Cleanout Tool and hang it outside of the SS1 body.
7. Insert SS1 Cup/Float subassembly into SS1 body. Test SS1 function.
• For directional cleanout of condensate drain line
• Fits perfectly with Safe-T-Switch® SS1 & all 3/4” drain lines
• Can be let with Safe-T-Switch® or removed for future jobs
• Can be used with Mighty Pump™ or a shop vac
WARNING: This device must be installed strictly in accordance with manufacturer’s instructions (to ensure proper operation) and in
accordance with all applicable local plumbing, drainage and electrical codes.
WARNING: Electric shock hazard. Disconnect power supply before installing this product to avoid electrical shock and/or equipment
damage. Use in Class 2 (thermostat) circuit only, not to exceed 24-volts, 1.25 amps to avoid damage or fire hazard.
CAUTION: This device will not detect clogs occurring upstream from the installation point.
CAUTION: If not present, it is recommended that a fuse and time delay be installed, to protect the 24-volt circuit and avoid rapid cycling of
equipment, prior to installing this product.
CAUTION: When installing this device in plugged configuration on auxiliary drain outlets, it is essential that PVC plug is closed o and
water-tight.
CAUTION: This product is intended for use in water only. Not for use in the presence of flammable liquids or vapors.
CAUTION: Refer to the appropriate HVAC equipment operation manual prior to installing this product.
CAUTION: Do not use on dual compressor systems.
24 Volt AC, 1.25 Amp, GP, Use in Class 2 (Thermostat) Circuit Only 6 ft. 18 AWG Lead Wire
RectorSeal®• 2601 Spenwick Drive, Houston, TX 77055, USA • 713-263-8001 • rectorseal.com
A CSW Industrials Company. RectorSeal, the logos and other trademarks are property of RectorSeal, LLC, its aliates or its licensor’s and are protected by copyright, trademark and other intellectual
property laws, and may not be used without permission. RectorSeal reserves the right to change specifications without prior notice. ©2022 RectorSeal. All rights reserved. R50109 1022
Technical Support Call 1-800-231-3345
This manual suits for next models
1
Table of contents
Other RectorSeal Switch manuals
Popular Switch manuals by other brands

Omega
Omega PSW20 Series instruction sheet

HP
HP PROCURVE 2610-PWR Series Management and configuration guide

Siemens
Siemens 3NJ630 Series operating instructions

G&D
G&D DVIMUX4-DL-PS/2 Installation and operation guide

D-Link
D-Link DGS-3000-28SC/A1A Hardware installation guide

SMART Embedded Computing
SMART Embedded Computing ATCA-F140 Series Installation and use