RectorSeal AquaGuard AG-1100+ User manual

Work Safe, READ THIS!
ATTENTION: FAILURE TO READ AND COMPLY WITH ALL WARNINGS, CAUTIONS AND INSTRUCTIONS PRIOR TO STARTING INSTALLATION MAY
CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE AND VOID WARRANTY.
STOP/READ: This device must be installed in accordance with manufacturer’s instructions. This unit must be in accordance with all applicable local plumbing, drainage and
electrical codes.
WARNING: Remove electrical shock hazard – DISCONNECT THE POWER BEFORE INSTALLING AQUAGUARD to avoid electrical shock and/or equipment damage.
Do not use on circuits exceeding 24 volts to avoid damage to switch, shock or fire hazard.
CAUTION: In some situations the switch may cause the unit to rapidly cycle on and off as water level rises slowly in pan. After a brief period the unit will turn off completely.
Condensation drain must be serviced if this occurs.
CAUTION: In any installation where property damage and/or personal injury might result from an inoperative switch due to power outages, a back-up system(s) and or alarm
should be installed.
NOTICE: The AquaGuard AG-1100+ must only be installed by a licensed contractor or under the direct supervision of same. Condensation pan must be properly maintained
after installation and be kept free from foreign objects, rust or other obstructions that might interfere with the proper operation of the AquaGuard float switch.
INSTALLATION OF FLOAT SWITCH ON DRAIN PAN:
(To ensure proper performance of product, instructions must be followed.)
1. Disconnect power to unit at main panel. Disconnect power to the low voltage thermostat circuit.
2. Slide the float switch onto the side of the pan.
3. Secure switch wires so they will not affect the operation of the float.
4. Secure the float switch by tightening thumb screws. (fig.1) Do not over tighten.
(fig.1)
WIRING THE AG-1100+ in a Conventional HVAC System:
(To ensure proper performance of product, instructions must be followed.)
1. Ensure the power is disconnected to the unit at the main panel prior to moving to step 2.
Refer to the appliance manufacturer’s installation and operating instructions and also review wire layout in their instructions.
2. Locate the red wire coming from the 24 volt thermostat “R” terminal.
3. Disconnect or cut red wire. Connect the non-ribbed wire of the switch, using a wire nut, to the thermostat side of the circuit. Connect the ribbed wire of the switch,
using a wire nut, to the air handler side of the circuit or to terminal in unit. Incorporating both switch wires in the red circuit will shut the unit completely off.
4. Test the switch. (At start-up check initial amperage load.)
A. With unit on, test switch by pulling the float pin up. (fig. 2) Unit should stop running if switch is correctly wired.
B. To test switch responsiveness fill pan with water to ensure that the switch stops the unit before the pan overflows. Remove water.
Thumb screws
"55&/5*0/$MFBOTVSGBDFXJUIJODMVEFEBMDPIPMQBECFGPSFNPVOUJOHXJUIBEIFTJWFUBQF
*OTUBMMBUJPO*OTUSVDUJPOT
8JSJOHUIF"RVB(VBSE¥"(.BHOFUJD'MPBU4XJUDI
"(

6. For wiring the normally open third wire (short wire) refer to the following diagrams:
Standard HVAC Installation Standard HVAC Installation w/ optional external alarm or accessory
WIRING the AG1100+ in a Communicating HVAC System:
1. See equipment manufacturers recommendations for specific wiring instructions.
5. Place the ATTENTION sticker on unit in a clearly visible location. (fig. 3)
(fig. 2) (fig. 3)
Pull pin up to test
switch
6SHQZLFN'ULYH+RXVWRQ7;
3)ZZZUHFWRUVHDOFRP

LIMITED WARRANTIES AND LIMITATION OF LIABILITY
REGISTER YOUR PRODUCT ONLINE: www.rectorseal.com
1 YEAR SWITCHAND SENSOR LIMITED WARRANTY AND LIMITATION OF LIABILITY
The limitations of liability set forth below include body and all component parts as well as the product itself as a whole.
Rectorseal warrants to the original consumer purchaser (“Purchaser) of its AquaGuard switch and sensor products, that they are free from
defects in material or workmanship for a period of one (1) year from the date of purchase. If this product shall prove to be defective within the
one (1) year period from the date of purchase, it shall be repaired or replaced, at Rectorseal ‘s option, subject to the GENERAL TERMS and
CONDITIONS set forth below.
EXCLUSIONS
This warranty does not cover damages resulting from use of components or accessories not approved by Rectorseal. 3, and 10 YEAR SEC-
ONDARY DRAIN PAN LIMITED WARRANTY AND LIMITATION OF LIABILITY
This warranty applies only to secondary drain pans installed in the United States and Canada.
Rectorseal warrants to the original consumer purchaser (“Purchaser”) of its AquaGuard secondary drain pan products, that they are free
from defects in material or workmanship for a period of three (3) years for Titan pan models, ten (10) years for Goliath and Goliath Furnace
PRGHOVIURPWKHGDWHRISXUFKDVH,IWKLVSURGXFWVKDOOSURYHWREHGHIHFWLYHZLWKLQWKHWKUHH¿YHRUWHQRU\HDUSHULRGIURPWKHGDWH
of purchase, it shall be repaired or replaced, at Rectorseal’s option, subject to the GENERALTERMS and CONDITIONS set forth below. This
warranty extends only to the original consumer purchaser and is nontransferable.
EXCLUSIONS
This warranty does not cover damages resulting from the use of corrosive material (including, but not limited to: Acetone, MEK and petro-
leum-based products); nor damages resulting from use of components or accessories not approved by Rectorseal.
GENERAL TERMS AND CONDITIONS
To be eligible for the warranty the purchaser must provide Rectorseal with the following:
1. Proof of Purchase (Original Receipt)
2. Installer’s Testimony
3. Original Product
4. Original Work Order
5. Photos of Installation
PURCHASER MUST PAY ALL LABORAND SHIPPING CHARGES NECESSARY TO REPLACE PRODUCT COVERED BY THIS WAR-
RANTY. This warranty shall not apply to acts of God, nor shall it apply to products which, in the sole judgment of Rectorseal have been subject
to negligence, abuse, accident, tampering, misapplication, alteration; nor due to improper installation, operation or maintenance or storage; nor
moved from its original place of installation; nor to other than normal application, use or service, including but not limited to, operational failures
caused by corrosion, rust or other foreign materials in the system. Requests for service under this warranty shall be made by returning the de-
fective product to the Retail outlet or to Rectorseal as soon as possible after the discovery of any alleged defect. Rectorseal will subsequently
take corrective action as promptly as reasonably possible. No requests for service under this warranty will be accepted if received more than
thirty-one (31) days after the term of the warranty.1hiswarranty sets forth Rectorseal’s sole obligation and purchaser’s exclusive remedy for de-
IHFWLYHSURGXFWV)RU\RXUEHQH¿WDQGSURWHFWLRQUHJLVWHU\RXUSURGXFWRQOLQHDWZZZUHFWRUVHDOFRPZLWKLQWKLUW\GD\VRILQVWDOODWLRQ7KLV
will initiate the Warranty period and will allow us to contact you, should it become necessary. In the absence of a recorded product registration,
the Warranty period will begin upon product shipment from Rectorseal. In the event that Rectorseal attempts to contact consumers regarding
a recall or other matter, and any damages occur, which could have been avoided by registration by the consumer, Rectorseal shall have no
liability. IN ALL CIRCUMSTANCES, RECTORSEAL’S MAXIMUM LIABILITY SHALL NOT EXCEED THEACTUAL PURCHASE PRICE
PAID FOR THE PRODUCTALONE. Warranty claims must be registered with Rectorseal within thirty (30) days of damage or malfunction.
Rectorseal reserves the right to visit the site of the installation or to require documentation of the claim before assuming any responsibility
under the provisions of this Warranty.Consumer agrees to inspect the product at the time of installation for any reasonable discernable defects
and, further, agrees to inspect the product annually. Any damages occurring, which could have been avoided by proper inspection will not be
the responsibility of Rectorseal. RECTORSEAL SHALL NOT BE LIABLE FOR ANY CONSEQUENTIAL, INCIDENTAL, OR CONTINGENT
DAMAGES WHATSOEVER TO THE PURCHASER OR ANY THIRD PARTY.THE FOREGOING WARRANTIES ARE EXCLUSIVE AND IN
LIEU OF ALL EXPRESSED WARRANTIES. IMPLIED WARRANTIES, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF
MERCHANTABILITYAND FITNESS FOR A PARTICULAR PURPOSE, SHALL NOT EXTEND BEYOND THE DURATION OF THE APPLICA-
BLE EXPRESSED WARRANTIES PROVIDED HEREIN.
Some states do not allow the exclusion of limitation of incidental and consequential damages or limitations on how long an implied
ZDUUDQW\ODVWVVRWKHDERYHOLPLWDWLRQVRUH[FOXVLRQVPD\QRWDSSO\WR\RX7KLVZDUUDQW\JLYHV\RXVSHFL¿FOHJDOULJKWVDQG\RXPD\DOVR
have other legal rights that vary from state to state.
VENUE: Any purchaser or third party actions brought for any reason hereunder shall be commenced in Houston, TX and no other jurisdiction,
and such action shall be governed by and construed in accordance with the laws of the State of Texas.Any notice herein shall be sent by
FHUWL¿HGRUUHJLVWHUHGPDLOWR6SHQZLFN'ULYH+RXVWRQ7;86$
24 VAC, 5 amps
RectorSeal® Houston, TX USA www.rectorseals.com US Patent Pending

¡Trabaje seguro, LEA ESTO!
ATENCION: El fracaso de no leer toda las precauciones, advertencias e instrucciones antes de comenzar la instalación puede causar riesgo de lesiones personales y/o daño a su
propiedad y podrá perder su garantía.
ALTO/LEEA: Este dispositivo debe ser instalado en conformidad con las instrucciones del fabricante. Esta unidad debe estar conforme con todos los códigos de instalación de
cañería, desague y códicos eléctricos.
ADVERTENCIA: Desconecte la electricidad antes de instalar AquaGuard para evitar un posible corto circuito o daño al producto. No debe utilizarce en circuitos que excedan
24 voltios para evitar daño al interruptor, golpe eléctrico o riesgo de fuego.
CAUCION: En algunas circuntancias el interruptor puede causar que la unidad funcione rápidamente ocacionando que se prenda y apage mientras el nivel del agua sube
lentamente en la bandeja. Después de unos minutos el interuptor se apagará totalmente. Si esto occure, servicio al desague es recomendado.
CAUCION: En cualquier instalación donde haya riesgo de lesiones personales o a su propiedad debido a un interuptor inoperante, se debe correjir con un sistema de alarma.
NOTAS: El AquaGuard debe ser instalado por un contratista licenciado o bajo la supervisión directa de un persona adecuada. La bandeja de condensacion debe ser mantenerse
en buenas condiciones despues de la instalacion y mantenerla alejada de objetos extranos, oxido u otras circunstancias que puedan interferer con el buen funcionamiento del
dispositivo de AquaGuard.
INSTALACION DEL INTERRUPTOR DE FLOTA EN LA BANDEJA DE DESAGUE:
(para asegurar el buen funcionamiento del producto, se deben seguir correctamente las siguientes instrucciones):
1. Desconecte la electricidad del interruptor de la caja eléctrica principal. Desconecte el poder a bajo voltaje en el circuito del termostato.
2. Recorra el interruptor flotador en el lado de la bandeja.
3. Asegure los cables del interruptor para que no afecten la operacion del flotador.
4. Asegure el interruptor flotador ajustando el tornillo de dedo. (fig.1) No sobreajuste.
(fig. 1)
Tuerca de dedo
*OTUSVDDJPOFTEF*OTUBMBDJØO
$BCMFBEPEFM"RVB(VBSE¥"(*OUFSSVQUPSEFGMPUBEPSNBHOÏUJDP
"5&/$*0/-JNQMFMBTVQFSGJDJFDPOQB×PEFBMDPIPMJODMVJEPBOUFTEFNPOUBSDPODJOUBQFHBOUF
"(
CABLEADO DEL AG-1100+:
(para asegurar el buen funcionamiento del producto, se deben seguir correctamente las siguientes instrucciones):
1. Asegure que la electricidad esta desconectada antes de seguir las próximas instrucciones. Refiérase a las instrucciones de instalación de la unidad del aire
acondicionado o la refrigeración y también revise la disposición de alambre de revisión en su manual de instrucciones.
2. Localice el cable rojo que proviene de los terminales del termóstato ( circuito de enfriamiento) "R" de 24 voltios. Desconecte o corte el cables rojo. Conecte a uno de
los interruptor o suiche usando la tuerca de alambre. Conecte el otro interruptor a la terminal de la unidad usando una tuerca del alambre o perrito.
Incorporando los dos alambres del interruptores en el circuito rojo apagara la unidad completamente.
3. Desconecte o corte el alambre rojo. Conecte el cable no crucería del aparato, usando una tuerca de alambre, al lado del termostato del circuito. Conecte el cable del
interruptor de crucería, con una tuerca para cable, a un lado el ventilador de aire del circuito o terminal en la unidad. La incorporación de los cables del interruptor en
el circuito rojo se apagará completamente la unidad.
4. Pruebe el interruptor . (Al arrancar compruebe la carga del amperaje inicial)
A. Pruebe el interruptor levantando el flotador mientras la unidad este puesta y/o encendida. (fig.2) La unidad debe parar de funcionar si las conecciones de
alambres al interuptor estan correctamente instaladas.
B. Provar la receptividad del interuptor: Llene la bandeja de agua para asegurar que el interuptor apage la unidad antes que se desborde la bandeja.

5. Ponga el stike de ATENCION en una locacion visible y clara. (fig. 3)
(fig.2) (fig. 3)
6. Para el tercer cable del cableado normalmente abierto (alambre corto) se refieren a los siguientes diagramas:
Norma de Instalación HVAC W estándar de instalación de HVAC / alarma externa opcional o accesorio
EL CABLEADO de AG-1100+ en un sistema de comunicación HVAC:
1. Ver las recomendaciones del fabricante para obtener instrucciones específicas del cableado.
Pruebe el interruptor jalando el
alfiler
6SHQZLFN'ULYH+RXVWRQ7;
3)ZZZUHFWRUVHDOFRP
Table of contents
Languages:
Other RectorSeal Switch manuals
Popular Switch manuals by other brands

SMC Networks
SMC Networks SMC6224M Technical specifications

Aeotec
Aeotec ZWA003-S operating manual

TRENDnet
TRENDnet TK-209i Quick installation guide

Planet
Planet FGSW-2022VHP user manual

Avocent
Avocent AutoView 2000 AV2000BC AV2000BC Installer/user guide

Moxa Technologies
Moxa Technologies PT-7728 Series user manual

Intos Electronic
Intos Electronic inLine 35392I operating instructions

Cisco
Cisco Catalyst 3560-X-24T Technical specifications

Asante
Asante IntraCore IC3648 Specifications

Siemens
Siemens SIRIUS 3SE7310-1AE Series Original operating instructions

Edge-Core
Edge-Core DCS520 quick start guide

RGBLE
RGBLE S00203 user manual