Regency I31-3 Gas Fireplace Inbuilt
INSTALLATION
IMPORTANT:
SAVE THESE
INSTRUCTIONS
The Regency Gas Fireplace must be installed
inaccordancewith theseinstructions.Carefully
read all the instructions in this manual first.
Note: Failure to follow these instructions
could cause a malfunction of the
heater which could result in death,
serious bodily injury, and/or prop-
erty damage. Failure to follow these
instructions may also void your fire
insurance and/or warranty.
FOR YOUR SAFETY
This appliance requires air for proper combus-
tion. Alwaysprovideadequatecombustionand
ventilation air. Follow instructions and informa-
tion in the current AS5601-2004, NZS 5261
or local codes. Consult the "authority having
jurisdiction" to determine the need for a permit
prior to starting the installation.
GAS PIPE TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shutoff valve during any pressure
testing of the gas supply piping system at
test pressures equal to or less than 3.45 kPa.
Specifications:
Fuel: NG or LPG (see page 7)
Electrical:240 volt 50 hz system
Fan/Blower:2-speed, 127 CFM
Log Sets: Ceramic fibre
BEFORE YOU START
Installation is to be carried out ONLY by an
authorised person.
1) The appliance shall be installed in accord-
ance with the manufacturer'sinstallation
instructions,local gas fitting regulations,
municipal building codes, water supply
regulations,electricalwiringregulations,with
AS5601-2004.(AGA gas installation code)
NZS 5261(New Zealand)
2) Installation and repair should be done
ONLY by an authorised person.
3) The appliance should be inspected before
use and at least annually by an authorised
serviceperson.Morefrequentcleaningmay
berequiredduetoexcessivelintfromcarpet-
ing, bedding material, etc. It is imperative
that control compartments, burners and
circulatingairpassagewaysoftheappliance
be kept clean and free from excessive lint
from carpeting.
4) See general construction and assembly
instructions.This appliance mayonlybe in-
stalledinaflued,non-combustiblefireplace.
The appliance and flue should be enclosed
when installed or passing through a living
area, where children may come in contact
with it.
5) Alwaysconnectthisspaceheatertoachim-
ney and flue to the outside of the building
envelope.Neverfluetoanotherroom. Make
sure that the flue is properly sized and is of
adequateheighttoprovidetheproperdraft.
6) Inspect the flueing system annually for
blockage and any signs of deterioration.
7) Anysafetyglassremovedforservicingmust
bereplacedpriortooperatingtheappliance.
8) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fireplace.
9) Installer must mechanically attach the sup-
plied label to the inside of the firebox of the
fireplace into which the gas fireplace insert
is installed.
“WARNING:This fireplace hasbeenconverted
forusewithagasfireplaceinsertonlyandcannot
be used for burning wood or solid fuels unless
all original parts have been replaced, and the
fireplace re-approved by the authority having
jurisdiction.”.
INSTALLATION
CHECKLIST
The Regency Gas Insert is installed as listed
below.
1) Unit Location - check Clearances to Com-
bustibles on page 6.
2) Make the gas connections (see page 6).
3) Install the flue or liner to the sliding draft
diverter. See page 7.
4) InstallFlueing,page7.Slidetheunitintothe
fireplace. Attach draft diverter to the insert.
5) Test gas pressure, page 7. Check aeration,
page 7.
6) Test for flue spillage, page 7.
7) Install the optional brick panels. See page
8.
8) Install the log set. See page 8.
9) Assembleandinstallthefaceplateandtrim.
See page 10.
10) Installtheglassfront(page10)andoptional
Bay Front (page 11).
11) Install both louvres, flush (page 10) or Bay
(page 11).
12) InstallOptionalRemoteControlandOptional
Wall Thermostat, page 15.
13) Finalcheck:Beforeleavingthisunitwiththe
customer,theinstallermustensurethatthe
appliance is firing correctly. This includes:
a) Clocking the appliance to ensure the
correct firing rate.
b) Adjusting the primary air, if required, to
ensure that the flame does not carbon.
See page 7.
c) Ensuring that the appliance is flueing
correctly. See page 7.
MATERIALS REQUIRED
Noelectric power supplyis required forthe gas
control to operate.A240 VoltAC power cord is
hooked up to the fan switch and blower. Plug 3
wire cord into a suitable receptacle. Do not cut
thegroundterminaloffunderanycircumstances.
When connected with 240 volts, the appliance
must be electrically grounded in accordance
with local codes.
Note: Thisunitisequippedwithaheatsen-
sorthermodiscwhichwillpreventthe
blower from operating until the unit
reaches the correct temperature.