Reliance 31406CRK User manual

TABLE OF CONTENTS
Page
Tools Needed for Installation 1
Parts List 1
Safety Symbols Used in this Manual 1
About Generators and Transfer Switches 2
Key Product Components 3
Pre-Planning the Load on Your Generator 4
Load Balancing Examples 5
Installation Instructions
Mounting the Transfer Switch 6
Connecting the Flexible Conduit 6
Grounding the Transfer Switch 7
Installing 120 Volt Circuits 7
Installing 240 Volt Circuits 8
Completing the Installation 8
Installing and Wiring the Power Inlet Box 9
Wiring the Power Inlet Box to the Transfer Switch 9
Installing an Optional Power Inlet 10
Finishing Up 10
Operating Instructions 10
Product Specifications 11
ELECTRICAL INNOVATION SINCE 1909™
TTRRAANNSSFFEERREEQQUUIIPPMMEENNTTFFOORRPPOORRTTAABBLLEEGGEENNEERRAATTOORRSS
IINNSSTTAALLLLAATTIIOONNAANNDD
OOPPEERRAATTIINNGG
IINNSSTTRRUUCCTTIIOONNSS
For Power Transfer Kit Model
31406CRK
http://waterheatertimer.org/Connect-electric-water-heater-to-generator.html
http://waterheatertimer.org/how-to-wire-transfer-switch.html

Page 1
Congratulations on your purchase of the Reliance Controls generator power transfer switch. Reliance has been
manufacturing transfer switches and equipment in Racine, Wisconsin since 1983 and has been producing high-quality
electrical equipment for nearly 100 years. Reliance is the Loadside® transfer switch used in nearly 90% of the installations
done by professional electricians.Your transfer switch is UL 1008 listed, C-UL listed, and meets all requirements of the 2002
National Electrical Code.
All Reliance Controls transfer switches are made to operate with any generator up to 7500 watts continuous output, having
20 or 30 Amp twist-lock power receptacles.
TOOLS NEEDED FOR INSTALLATION
1. Power Drill
2. Wire Stripper and Cutter (10 to 14 gauge)
3. Insulated Screwdrivers
(#2 Phillips, 1/4" Flat Tip or #2 Square Tip depending on
your load center)
4. Hammer
5. Marking Pencil
6. Tape Measure
7. Seven Wall Anchors with at Least a 3/8” Flange
8. Enough 10-3 with Ground Building Wire to reach from
where you install your Outdoor Power Inlet Box to where
you install your transfer switch
9. Battery Powered Lighting during Installation
10. A Non-Contact Voltage Detector (optional)
PARTS LIST for 31406CRK POWER TRANSFER KIT
30 Amp 6-Circuit Transfer switch
30 Amp Outdoor Power Inlet Box
30 Amp 10-foot long Generator Power Cord
20 Amp Interchangeable Power Cord Plug
4 red and 6 yellow wire connectors
Installation and Operating Instructions
SAFETY SYMBOLS USED IN THIS MANUAL
Danger indicates an imminently hazardous
situation that, if not avoided, could result in
death or serious injury.
Warning indicates a potentially hazardous
situation that, if not avoided, could result in
death or serious injury.
Caution indicates a potentially hazardous
situation that, if not avoided, may result in
minor or moderate injury.
Reliance Controls Corporation is not
responsible for damage or injury
caused by incorrect installation of this
transfer switch.
Reliance transfer switches covered
in this manual should not be used for
electric water heaters, clothes dryers, electric ranges,
central air conditioners or other appliances or systems
that may exceed the capacity of the product.
Improper installation of the transfer
switch could cause damage or
personal injury by electrocution or fire. Installation must be
performed by a qualified electrician, or others
knowledgeable of electrical systems, in compliance with
all applicable electrical codes.
DANGER
WARNING
CAUTION
WARNING
WARNING
Member of the National Electrical Manufacturers Association
Transfer switches are required for use with portable generators by Article
702 of the 2002 National Electrical Code
NOTE: The 30 Amp power cord plugs into this type of
generator power outlet:
If your generator only has a 20 Amp power outlet like this:
install the 20 Amp Power Cord Plug on your power cord
according to its included instructions.

Page 2
ABOUT GENERATORS AND TRANSFER SWITCHES
Generators and transfer switches are dependent on one another as a system to power your home in a power out
situation. The Reliance Controls transfer switch system is needed because 1) your portable generator is very powerful and
the power it creates must be safely controlled to protect you and your electric utility provider, and 2) even with all of its power,
your generator probably cannot power all of the electrical circuits and devices in your home without help from a transfer
switch with load management capabilities.
The Reliance Controls transfer switch is designed to let you control and distribute your generator’s power. It correctly
distributes the power from your portable generator to your home circuitry through your electrical load center. It also
eliminates the need for messy cords running to your electrical appliances through open doors and windows. The Reliance
Controls transfer switch working with your generator takes the worry and inconvenience from power outage situations.
The Reliance Controls transfer switch distributes the power from your generator through its toggle switches to the
corresponding selected branch circuits that power the major appliances you choose to operate during a power outage (such
as your sump pump, refrigerator or furnace). However, because each of these branch circuits may power several other
electrical devices other than your major appliances, such as the items plugged into wall sockets and permanently installed
lighting, we recommend that you do a little pre-planning by:
1. Picking the key electrical appliances you want to power in an emergency
2. Finding the essential circuit breakers that control these devices
3. Creating a map of all of the other electrical devices plugged into or wired into these circuits
A tear-off Home Circuit Mapping Chart on the back of this manual should be completed and posted next to your transfer
switch to help you in managing the load on your generator. Make sure you note on the chart which electrical devices you will
not need during a power outage so that these can be turned off prior to starting your generator.
During a power outage, you can run your generator and transfer switch system in two ways:
• You can set up your transfer switch to run all of its circuits at the same time once you flip the toggles to the GEN position.
Setting your system up in this way will be discussed in the “Balancing the Load” section later.
• You can also use the load management function of the Reliance Controls transfer switch that allows you to alternate the
devices you choose to run at any given time. If your generator is running at or near its maximum output, selected circuits
can be switched off and others can be switched on for brief periods of time. For example, you can run a microwave oven
for a brief period from the transfer toggle switch that controls your microwave circuit, if you first turn off the transfer switch
toggle switch that controls your furnace—for that same brief period.
Typical Generator and Transfer Switch Installations
Generator Plugged into Outdoor Power Inlet
Box Wired to Transfer Switch Next to
Basement Load Center
(POSSIBLE KIT INSTALLATION)
Generator Plugged into Interchangeable
Power Inlet on Transfer Switch with
20-foot Cord
(POSSIBLE INSTALLATION WITH
AVAILABLE RELIANCE ACCESSORIES)
Generator Plugged into Outdoor Power Inlet
Box Wired to Transfer Switch Next to Garage
Load Center
(POSSIBLE KIT INSTALLATION)

Page 3
KEY COMPONENTS OF THE RELIANCE CONTROLS TRANSFER SWITCH AND
POWER TRANSFER KIT
Your Reliance Controls transfer switch is unique in two ways: 1) it has a patented internal wiring compartment which eliminates the need
for the installation of additional junction boxes, and 2) it has a removable front panel which allows a power inlet to be easily inserted to
allow a power cord to be plugged directly into the transfer switch with a longer power cord. Although this is not the installation addressed by
the 31406CRK Kit, such an installation may be desirable depending on your situation.
Circuit Selector Toggle Switches
These switches allow you to select either GEN
(generator) or LINE (utility) as the power source
for the branch circuits that have been wired
through the transfer switch. The OFF position
generally is not used, as a switch in the OFF
position removes that circuit both from generator
and utility power.
Wattmeters
Wattmeters indicate the total load on your
generator measured in watts resulting from the
appliances that are running using generator
power. They are calibrated to show how close
your generator is to its capacity.
Knockout Holes
Located on both sides, the bottom and the back of
your transfer switch, these knockouts are easily
removed with a screwdriver and a hammer and
allow the direct wiring of your transfer switch with
building wire.
Branch-Rated Circuit Breakers
Each transfer switch circuit controlled by a toggle
switch has a built-in corresponding 15 or 20 Amp
push-to rest circuit breaker that protects the
branch circuit when the toggle switch is in the
GEN position. In the LINE position, each branch
circuit is protected by the breaker in the load
center.
Handle Ties
Used to link two 120 Volt circuits together to
create a 240 volt circuit to run larger appliances
such as a well pump.
Wiring Compartment Front Plate
Removing the two screws which attach this plate,
reveals the internal wiring compartment. Inside
are four pre-stripped wires which connect to the
incoming generator-powered wires.
Power Inlet Hole Cover Plate
This logo plate removes with one screw to allow
the insertion of an accessory power inlet on the
front of your transfer switch to allow direct
connection to the generator with a power cord.
Pre-Wired Flexible Conduit Whip
Contains all of the hot, neutral and ground wires
required to make connections between your
transfer switch and the circuit breakers in your
load center you choose to control. Each wire is
color-coded and marked with the switch letter for
easy identification.
30 Amp Outdoor Power Inlet Box
30 Amp NEMA 3-configured outdoor
generator Power inlet Box mounts to the
outside of your house near to where your
generator will be running. It allows direct
wiring to your transfer switch and load
center from a remote location.
30 Amp Twist-Lock Power Cord
30 Amp 10-foot long outdoor-rated
power cord has L14-30 connectors.
One end plugs into your generator
power outlet and the other into the
Reliance Power Inlet Box.
20 Amp Interchangeable
Power Cord Plug
Allows the use of the Reliance 30
Amp power cord on smaller
generators with only 20 Amp power
outlets, by replacing the 30 Amp plug
on the cord supplied.

Page 4
PRE-INSTALLATION PLANNING OF THE GENERATOR LOAD
Before you begin installing your Reliance Controls transfer switch system, you need to create a plan for the appliances you choose
to run during a power outage. To do this, it’s helpful to first know how your generator produces power. If your generator has four-prong
twist-lock 20 or 30 Amp output receptacles, and is set-up for home stand-by operation, it likely will produce 120/240 Volt power, or power
similar to your electrical utility. This type of power generation is useful as it: 1) allows common 120 Volt circuits, such as lights or small
appliances, to be operated, and 2) allows two 120 Volt circuits to be linked together to operate a 240 Volt device, such as a well pump.
Because of the way in which larger portable generators are designed, they generate power in two equal halves. A generator which
has output of 5000 continuous running watts, for example, generates power from two 2500 watt “sides”. In setting up a transfer switch
to get the most power from your generator, it is desirable to “balance the load” between the two halves of your transfer switch, or the left
side and the right side. Devices which will consume the most of the generator’s wattage should be divided between the two sides. Load
balancing is shown in Figure 1. For example, on the 6-circuit transfer switch shown in Figure 1, consider wiring the breaker controlling
the refrigerator to toggle switch A, the furnace breaker to toggle switch B, the sump pump breaker to switch E and the breaker controlling
your TV and VCR to toggle switch F. You may want to reserve switches C and D to be linked with a handle tie and wired to a double pole
breaker controlling, for example, a 240 Volt well pump.
The Residential Wattage Requirements Table below shows sample wattages used by typical household appliances and can help
you plan the set up of your transfer switch. Use the running watts of your appliances rather than starting watts when dividing them
between the two halves of the transfer switch. Check your appliances for actual wattage requirements if possible.
Your Reliance Controls transfer switch also allows you to manage the load on your generator manually by switching appliances
on and off as you need them, so the capacity of either half of your generator is not exceeded. However, if you prefer not to manage your
transfer switch loads manually, leave a buffer equal to the largest start-up wattage requirement of all of the appliances you are going to
run continually when doing your calculation. This buffer, along with the peak wattage of your generator, will allow for the periodic motor
start-up of any one large appliance, such as your refrigerator. If your transfer switch is equipped with watt meters, you can visually
monitor the amount of wattage being used by the appliances your generator is powering at any time.
Examples of load balancing calculations are shown on the worksheets on page 5. Use these to create your own plan.
TYPICAL RESIDENTIAL WATTAGE REQUIREMENTS
Additional
Running Start-Up
Appliance Wattage Wattage
Furnace (1/3 HP) 700 1,400
Furnace (1/2 HP) 875 2,100
Window Air Conditioner
6000 BTU 1,200 2,100
12,000 BTU 1,700 2,900
Well Pump (1/3 HP) 750 1,400
Well Pump (1/2 HP) 1,000 2,350
Sump Pump (1/3 HP) 800 1,300
Sump Pump (1/2 HP) 1,050 2,150
Refrigerator 800 2,300
Garage Door Opener (1/4 HP) 550 1,100
Garage Door Opener (1/3 HP) 750 1,400
Home Security System 200 0
Lights On Bulb On Bulb
Stereo 200 0
TV/VCR 200 0
Computer 200 0
Microwave Check oven Check Oven
Coffee Maker 1,750 0
Toaster 1,300 0
Electric Fan 200 0
Clothes Washer 1,150 2,300
Clothes Dryer (Gas) 700 1,800
Dishwasher (Cool Dry) 700 1,400
Dishwasher (Hot Dry) 1,450 1,400
Vacuum Cleaner 1,000 0
Hair Dryer Check Dryer Check Dryer
Iron 1,200 0
Circular Saw 800 2,000
Figure 1
Refrigerator
(800 Watts)
Furnace
(875 Watts)
Well Pump
(1000 Watts)
Sump Pump
(1,050 Watts)
TV / VCR
(200 Watts)

Page 5
Load Balancing Example #1
Circuit Breaker Connections: Six (6) 120 Volt Single Pole Circuit Breakers
Generator: 5,500 Running Watts, 6,200 Peak Watts
Transfer Switch Model: 6-Circuits
Side One
Appliance Additional
Toggle Main Appliance Running Start-Up
Switch Hooked Up Watts Watts
ARefrigerator 800 2,300
BSump Pump 800 1,300
CIndoor Lighting 300 0
Total Running Watts Side One: 1,900
Side Two
Appliance Additional
Toggle Main Appliance Running Start-Up
Switch Hooked Up Watts Watts
FFurnace 700 1,400
ETV, VCR, Computer 600 0
DSecurity, Lighting 500 0
Total Running Watts Side Two: 1,800
Total Side One and Side Two Running Watts 3,700
Highest Additional Start-Up Wattage of all of the Appliances (Refrigerator) 2,300
Total Watts of Load 6,000
Peak Wattage Rating of Your Generator 6,200
You ’re OK!
Load Balancing Example #2
Circuit Breaker Connections: Four (4) 120 Volt Single Pole Circuit Breakers and One (1)
240 Volt Double-Pole Circuit Breaker (Toggles C & D Together)
Generator: 5,500 Running Watts, 6,200 Peak Watts
Transfer Switch Model: 6-Circuits
Side One
Appliance Additional
Toggle Main Appliance Running Start-Up
Switch Hooked Up Watts Watts
ARefrigerator 800 2,300
BTV, VCR, Computer 600 0
CWell Pump 500 1,175
Total Running Watts Side One: 1,900
Side Two
Appliance Additional
Toggle Main Appliance Running Start-Up
Switch Hooked Up Watts Watts
FFurnace 700 1,400
ESump Pump 800 1,300
DWellPump 500 1,175
Total Running Watts Side Two: 2,000
Total Side One and Side Two Running Watts 3,900
Highest Additional Start-Up Wattage of all of the Appliances (Refrigerator) 2,300
Total Watts of Load 6,200
Peak Wattage Rating of Your Generator 6,200
You're OK Again!

Page 6
INSTALLATION INSTRUCTIONS
A. Mounting the Transfer Switch
1. Position the transfer switch so that its bottom center is about
18 inches from the bottom center of your load center. The
end of the flexible conduit whip should be lined up with a 3/4"
knockout hole on the bottom of your load center (Figure 2).
2. Mark the position of the holes on the four external feet with a
pencil.
3. Anchor the transfer switch to the wall with four appropriate
anchors (with a flange of at least 3/8").
NOTE: Do not attempt to bend the flexible
conduit whip beyond its structural capabilities.
B. Connecting the Flexible Conduit Whip to
Your Load Center
1. Set up battery-powered lighting to clearly illuminate
your work area.
2. Tu rn off the main utility breaker (Figure 3).
3. Remove the cover of your load center. Keep in mind that the
wires on the utility side of the main breaker are still live and if
contacted could cause serious injury or death. If available,
use a non-contact voltage detector to insure that the power is
off on the non-utility side of the main breaker.
4. Remove the appropriate knockout hole in the bottom of your
load center with a screwdriver and hammer. (See step A-1
above.)
5. Insert all of the wires extending from the end of the flexible
conduit whip through the knockout hole. Snap the conduit
connector attached to the whip into the knockout hole.
Even with the main power
switch turned off, the wires
on the utility side of the main
breaker are still live and
contact with them can cause
serious injury or death.
Mount on wall
with anchors
Live Wires on
Utility Side of
Main Breaker
Typical Main Breaker
Location
Figure 2
Figure 3
To Transfer Switch Conduit Connector
DANGER

C. Connecting the Neutral and Ground Wire
1. Find the white wire (Neutral) and the green wire (ground)
among the wires from the transfer switch that you have
inserted into the load center.
2. Strip approximately 5/8” from the end of the white wire.
Locate the neutral bar and partially unscrew a terminal
screw on the bar. Insert the stripped end of the wire into
the side of the bar under the screw and retighten the screw.
(Figure 4)
3. Locate the ground bar. (It should be labeled.) Connect the
green wire to the ground bar in the same way as in step
#2. In service entrance load centers, the ground bar and
neutral bar are frequently the same; if so, the ground and
neutral wires can be connected to either.
D. Installing 120 Volt Circuits
This section provides instructions for connecting the wires
from your transfer switch to the circuit breakers in your load
center which control your appliances.
You should refer to the load planning you did previously to
insure that side #1 and side #2 of the transfer switch are
balanced. Wire the circuits, starting with toggle Switch A.
If you will not be installing any 240 Volt or multi-wire circuits,
remove the factory-installed handle tie(s) on the unit by
loosening the setscrews on the tie.
Lets assume that, according to your load balancing plan, you
will use Switch A to supply power to the refrigerator (Figure 5)
1. Tu rn off the refrigerator circuit breaker. Disconnect the wire
that is attached to the circuit breaker.
2. Find the black and red wires from the transfer switch
marked A.
3. Cut the red wire at a length convenient for it to reach to the
refrigerator circuit breaker. Strip 5/8” from the end of the
wire. Connect the red wire to the refrigerator circuit breaker
and retighten the screw on the breaker.
4. Cut the black wire from the transfer switch to a length
convenient for attaching it to the wire you removed from the
refrigerator circuit breaker in #1. Strip 5/8” from the end of
the wire.
5. Insert both wires—the one removed from the refrigerator
circuit breaker and the black wire for Switch A—into a
yellow wire connecter. Tighten the connection and push
the connected wires back into the wiring compartment of
the load center.
Page 7
Failure to properly install a multi-wire branch
circuit could result in overloading the neutral wire.
If a selected circuit is part of a multi-wire branch circuit, insure the
other branch circuit that shares the neutral is also connected to the
transfer switch. The two circuits must be connected to opposing legs
(phases) of the generator power and a handle tie must be installed on
the switch handles so that both legs are transferred at the same time.
When Installing 120 Volt Circuits
Figure 4
The transfer switch circuits with 20 Amp breakers must be connected only to
branch circuits with 20 Amp breakers in the load center. Do not connect transfer
switch circuits to any branch circuits greater than 20 Amps.
NOTE: The transfer switch circuits with 15 Amp breakers can be connected to
branch circuits with either 15 or 20 Amp breakers in the load center.
Figure 5
Wires from
Switch A
Ground Wire
(Green)
This completes the connection of Switch A for your refrigerator.
Label Switch A as “REFRIGERATOR” on the identification pad on
top of the transfer switch.
6. Repeat Steps 1 through 5 for each of the remaining switches
on your transfer switch according to your load balancing plan,
taking into account the following:
•See the next section for installing 240-Volt Circuits
•Remember to “Balance the Load”, dividing appliances
with higher wattages between the left and right side of
the transfer switch
WARNING
WARNING

Page 8
E. Installing 240 Volt Circuits
Reliance Controls 6-Circuit Transfer switch (In Kit) is shipped from
the factory with one installed handle tie on two adjacent circuits.
Let’s assume that, according to your set-up plan, Switches C & D
on the 6-Circuit transfer switch will be used to supply power to your
well pump, a 240 Volt appliance. (Figure 6)
1. Find the two red and the two black wires marked C & D.
2. Tu rn off the double pole breaker for the well pump in the load
center.
3. Disconnect the two installed wires on the double pole breaker.
4. Cut the two red wires from Switches C & D at a length
convenient for them to reach to the double pole breaker. Strip
5/8” from the end of each red wire. Connect both red wires to
the double pole circuit breaker in place of the wires you just
removed from that breaker. It doesn’t matter in what order.
5. Cut the black wires marked C & D to a length convenient to
reach to the wires you removed from the double pole breaker in
#3. Strip 5/8” from the end of each wire.
6. Connect one of the wires you removed from the double pole
breaker in #3 with one of the black wires (either C or D) with a
yellow wire connector. Similarly, connect the other wire you
removed with the remaining black wire with a wire connector.
F. Completing the Installation of the
Transfer Switch
When you have wired all of the circuits from the transfer switch into
your load center and have properly installed the green and white
wires to ground the unit, you have finished the installation. (Figure
7) Just a few more steps to wrap things up.
1. Replace the cover of the load center.
2. If you have not already done so, fill in the chart on the top of the
transfer switch to identify your emergency circuits and the
toggle switches they correspond to.
3. Do not turn the main and individual circuit breakers in your load
center back on until you have installed all other transfer switch
components in Sections G, H and I which follow.
When Installing 240 Volt Circuits
The transfer switch circuits with 20 Amp breakers must be con-
nected only to branch circuits with 20 Amp breakers in the load
center. Do not connect transfer switch circuits to any branch cir-
cuits greater than 20 Amps.
NOTE: The transfer switch circuits with 15 Amp breakers can be
connected to branch circuits with either 15 or 20 Amp breakers
in the load center.
Figure 6
Figure 7
WARNING

Page 9
G. Installing and Wiring the Outdoor Power
Inlet Box (included in kit)
Since you will be operating your generator outdoors in a location
remote from your electrical load center, it is recommended that you
install an outdoor power inlet box on an exterior wall of your house.
Because it is hardwired directly to your transfer switch, the power
inlet box gives you the flexibility to locate your generator just about
anywhere.
Reliance Controls Power Inlet Boxes are UL listed and can be used
with the following generator and building wire sizes:
Generator Size Power Inlet BoxBuilding Wire (100' or less)
Up to 7500 Watts PB30 (In kit) 10 gauge
To install a Reliance Power Inlet Box (Figure 8):
1. Loosen the screw at the bottom front of the box and lift off the
cover.
2. Choose which knockout hole on the box is most convenient to
where you will be running the building wire into your house.
Remove the knockout with a screwdriver and hammer.
3. Plan to run enough building wire (check electrical codes for the
need for conduit) to reach your transfer switch, allowing extra
length for ease of wiring at the transfer switch end.
4. Using approved wiring methods, place a cable or conduit
connector (check codes) in the inlet box knockout hole and run
enough building wire into the box to allow easy wiring. Tighten
the connector.
5. Mount the back plate of the power inlet box where it will be
convenient. Use the three holes in the plate.
6. Strip 5/8” from each building wire lead. Loosen the green
grounding screw on the inside of the box and insert the stripped
end of the building wire ground under one side of the grounding
screw and retighten.
7. On the bottom of the inlet plug, insert the white wire into the
hole marked “W” and tighten the screw on the side of the plug.
Do the same with the red wire into the hole marked “X” and the
black wire into the hole marked “Y”.
8. Replace the cover of the power inlet box and tighten
the screw.
H. Wiring the Power Inlet Box to the
Transfer Switch
All Reliance Controls transfer switches are designed to allow
hardwiring between the outdoor power inlet box and the transfer
switch’s internal wiring compartment. This installation is the most
efficient, eliminates the need for longer generator power cords
running through your home to your transfer switch and eliminates
the need for an additional junction box.
To hardwire your transfer switch to the building wire from the power
inlet box (Figure 9A and 9B):
1. Remove the front bottom wiring compartment cover plate of the
transfer switch by unscrewing the two screws securing the plate
and then pulling out on the bottom of the plate. Once the plate
is removed, the wire leads necessary to connect the incoming
building wire can be easily accessed.
2. Punch out the knockout hole on the side of the transfer switch
wiring compartment.
3. Using approved wiring methods, place a cable or conduit
connector (check electrical codes) in the knockout hole, and pull
enough building wire into the inside of the wiring compartment
to provide sufficient working length. Tighten the connector.
4. Connecting the Wattmeters: Thread the black building wire
through the transformer ring attached to the left wattmeter
before connecting it to the black transfer switch wire. Likewise
thread the red building wire through the transformer ring
attached to the right wattmeter before connecting it to the red
transfer switch wire. Connect the green to green and white to
white wires with a red connector. Do not thread these wires
through the transformer rings (Figure 9B).
5. Complete the wiring by pushing the wires back into the unit,
putting the wiring compartment cover back in place and
replacing the screws that hold the cover plate.
Connecting the Wattmeters
Black wire through left
ring transformer
Red wire through right ring
transformer
Figure 8 Figure 9A Figure 9B

Page 10
I. Installing an Optional Power Inlet on your
Transfer Switch (not necessary in kit
installation)
Although such an installation is not necessary with the Power
Transfer Kit, your Reliance Controls transfer switch is unique in that
it allows the installation of an accessory power inlet which allows
you to plug your generator directly into your transfer switch using a
longer power cord. This may be convenient under certain
circumstances and is explained here.
To install a power inlet on your transfer switch (Figures 10A-10C):
1.Purchase Reliance Flanged Power Inlet model number L1420F
for a 20 Amp inlet to accommodate 20 Amp power cords and
small generators up to 5000 watts, or L1430F for a 30 Amp inlet
to accommodate 30 Amp power cords and generators up to
7500 watts. If you choose to, you may also use the 30 Amp
power Inlet from the Reliance PB30 Power Inlet Box (supplied
with the kit).
2.Remove the plastic Reliance logo panel located on the right side
of the wiring compartment cover to reveal the hole for the power
inlet. One screw holds this plate on the bottom.
3.Remove the entire wiring compartment plate by removing the
other bottom screw and pulling out on the bottom of the plate.
4. If your transfer switch has wattmeters, make sure that the black
wire from the transfer switch is threaded through the transformer
ring connected to the left wattmeter, and the red wire from the
transfer switch is threaded through the transformer ring
connected to the right wattmeter.
5. Insert the power inlet into the hole in the wiring compartment
plate and fasten it with the two smaller screws included with the
inlet. Do not refasten the longer bottom screw at this time.
6. On the underside of the inlet, insert the white wire into the hole
marked “W” and tighten the screw on the side of the plug. Do
the same with the red wire into the hole marked “X”, the black
wire into the hole marked “Y” and the green wire into the hole
marked “G”.
7. Replace the wiring compartment panel with the two screws you
removed in steps #2 and #3, inserting the longer screw through
the bottom of the flanged inlet plug.
J. Finishing Up
According to your individual installation requirements, after you
have completed all the steps necessary in Sections G through I,
complete the system installation by doing the following:
1. Tu rn on all of the circuit breakers in your load center.
2. Tu rn on the main breaker.
3. Position all switches on the transfer switch to the LINE position.
4. IMPORTANT! In order to insure that all wiring connections
have been properly completed and that your system functions
properly under generator power, it is important to test each
circuit before turning on any devices or appliances connected to
that circuit. Correct voltage output can and should be checked
with a voltage meter at any convenient electrical outlet on each
branch circuit that is wired through the transfer switch. This
should be done under generator power with the appropriate
circuit breaker switch in the “GEN” position.
OPERATING INSTRUCTIONS
Do not operate your generator in an
enclosed area.
Figure 10
AB
C
WARNING
You want your generator to be ready when you need it – so, it is
important to perform the following steps once a month:
•Start and run generator power through your transfer switch circuits.
•Keep your fuel tank filled with fresh fuel.
With your Reliance Controls transfer switch installed, it is not necessary
to turn off any of your load center breakers when starting your generator,
even when utility power is fully functional. This is because the double
throw break-before-make action of the transfer switch prevents feeding
generator power to the utility and, conversely, prevents feeding utility
power back to your generator.
A. Transferring from Utility Power to Generator
Power in an Emergency
1. Make sure that all switches on the Reliance Controls transfer switch
are in the LINE position.
2. Plug the male end of your power cord into the generator. NOTE: If
your generator has only 20 Amp 125/250 V output receptacles,
replace the 30 Amp male end of the power cord with the 20 Amp
male plug end supplied in the kit. See installation instructions with the
20 Amp plug.
3. Plug the female end of your power cord into either the outdoor power
inlet box or directly into the transfer switch, depending on how you
installed your system.
4. Start your generator outdoors and let it warm to a point where it is
running evenly.
5. Tu rn the toggle switches on your Reliance transfer switch to the GEN
position one at a time.
If you have a Reliance transfer switch with wattmeters, you can monitor
the wattage load on your generator.
B. Transferring back to Utility Power When the
Power Is Restored
1. Move all switches on the Reliance Controls transfer switch back to
the LINE position.
2. Tu rn off your generator.
3. Unplug your power cord and store it.

Page 11
TRANSFER SWITCH PRODUCT SPECIFICATIONS
Maximum Watts 7500
Possible Single Pole/Double Pole Combinations 0-1 DP / 4-6 SP
Maximum Combined Load @ 125 Volts AC (Amps) 60 Amps
Maximum Combined Load @ 250 Volts AC (Amps) 30 Amps
Maximum Load per Circuit from Generator (Amps) (2) 20, (4) 15
Maximum Load per circuit from Load Center (Amps) 20
Recommended Building Wire Size (runs less than 100’) 10 Gauge with ground
Wattmeters Yes
Number of Knockouts Available 1/2" or 3/4" 6
Power Inlet Box Match PB30
Cabinet Dimensions H x W x D (inches) 7 1/2" x 7" x 4 1/2"
Cabinet Type (NEMA) 1
TRANSFER SWITCH ACCESSORIES AVAILABLE
FROM RELIANCE CONTROLS
These additional products are available through your local distributor.
Call Reliance Controls at (800) 634-6155 to locate the distributor nearest you.
Power Cords
Connect generator power outlets with outdoor power inlet boxes or accessory power inlets
PC2010 10-foot cord with L14-20P and 14-20R twist lock ends
PC2020 20-foot cord with L14-20P and 14-20R twist lock ends
PC3010 10-foot cord with L14-30P and 14-30R twist lock ends
PC3020 20-foot cord with L14-30P and 14-30R twist lock ends
Transfer Switch Accessory Power Inlets
Insert into faceplate of transfer switch wiring compartment to allow plug-in of power cords
directly to transfer switches
L1420F 20 Amp power inlet
L1430F 30 Amp power inlet
Flush-Mount Kit
Use with Reliance surface-mount transfer switch (supplied in kit) to convert to a
flush-mount installation
KF6 For 6-Circuit Transfer Switch
Power Cords
Accessory
Power Inlets
Flush Mount Kit

Attach Your Purchase
Receipt Here for Your
Records
Warranty Registration
Return within 30 days of purchase. Please answer these few questions for our records, cut on dotted line above, fold with
Reliance Controls address on the outside of the mailer and staple. Thank you.
First Name:
Last Name:
Address:
City, State,Zip:
Phone:
Email:
Purchase Date: Purchase Price: Name of Store:
Are you: a professional installer a do-it-yourself installer
Please call us anytime at (800) 439-5745 with your comments or questions. Thank you.
Cut Here and Fold to Create Self Mailer for Warranty Registration
Five Year Limited Warranty
Reliance Controls Corporation (“Reliance”) warrants this Protran® Manual Transfer Switch
(“Switch”) to be free from failure to perform as intended due to defects in materials and workmanship
for a period of five (5) years from date of manufacture, provided the Switch has been installed and
used in accordance with manufacturer’s instructions and has not been subjected to misuse,
alteration, accident, or repair not performed by Reliance. If, within such warranty period, the original
purchaser gives written notice to Reliance at the address shown below and the Switch has been
proven to Reliance’s reasonable satisfaction to be defective, then Reliance at its sole option shall
either: (i) supply a replacement component(s) for the defective component(s) or (ii) repair or replace
the Switch. Reliance’s obligation is strictly limited to said repair or replacement of the Switch, and
Reliance shall not be liable for any incidental, special or consequential damages. The cost of labor
to remove or install a replacement component or Switch is not included in this warranty. The
foregoing warranty is exclusive and in lieu of all other expressed or implied warranties, if any,
including but not limited to implied warranties of merchantability and fitness for a particular purpose.
Reliance strongly recommends that the purchaser seek the advice of a licensed electrician to
determine the suitability of this product, and for its proper installation in accordance with all
applicable state and local building codes. This warranty gives you specific legal rights, and you may
have other rights which vary from state to state.
Reliance Controls Corporation
2001 Young Court
Racine, WI 53404
Attn: Warranty Claims Department

HOME CIRCUIT MAPPING CHART
This Toggle Switch on My Generator Transfer Switch
AB C D E F
Controls
these
essential
appliances
I will need
during a
power
outage
So, I need
to turn off
these
other
devices
which are
on the
same
Circuits
AFFIX
POSTAGE
HERE
Reliance Controls Corporation
2001 Young Court
Racine, WI 53404
STAPLE
Table of contents
Other Reliance Switch manuals
Popular Switch manuals by other brands

Velleman
Velleman HQ-Power PSS4005 user manual

Texas Instruments
Texas Instruments ThunderSWITCH II TNETX4090 user manual

Hama
Hama AV-1000 operating instructions

ASTEK
ASTEK A51606-SW quick start guide

Ruijie
Ruijie Reyee RG-ES206GS-P Series Hardware installation and reference guide

Fortinet
Fortinet FortiManager 1000D quick start guide

SimworX
SimworX Pro Series ARB Lever and Brake Bias Set Setup manual

Moxa Technologies
Moxa Technologies EDS-316 Series Quick installation guide

Johnson Pump
Johnson Pump SPX AS888 instruction manual

Minicom
Minicom 0SU52016 owner's manual

ANTAIRA
ANTAIRA LNX-500AG Quick installation guide

Zektor
Zektor HDS4 owner's manual