REMKO ATR-4 User manual

REMKO ATR-4
Electronic
Clock Thermostat
Edition GB - H12
Operation
Technology
Original
REMKO
REMKO - powerful like a bear


3
Operating Instructions
This electronic clock thermostat is used for room temperature-dependent,
two-point control of heating and cooling units in dry and closed rooms.
Read these instructions carefully before setting up/operating the unit!
Our guarantee becomes null and void if the unit is used improperly or if
modifications are made to the supplied unit.
Electronic Clock Thermostat
REMKO ATR-4
Important!
Always keep these operating instructions near or on the unit.
Contents Page
Functionality 4
Operating Controls 4
Comfort Temperature 4
Cooling Temperature 5
Frost Protection Temp. 5
Hand Button 5
Off 5
Reset 5
Setting the Clock 6
Contents Page
Selecting the Operating Mode 6
Setting the Timer 7
Setting the Control Parameters 8
Setting the Functions 8+9
Installation Instructions 10
Mounting 11
Wiring Diagram 12
Customer Data 13
Technical Data 14

4
Functionality
•The ATR-4 electronic clock thermostat records the room temperature ei-
ther using an internal NTC temperature sensor or an external KTY tem-
perature sensor.
•The output is activated via an isolated change-over contact.
•The digital weekly clock timer controls temperature in automatic mode
(comfort temperature or cooling temperature). It has 16 programs that can
be used to program up to 112 activation times. The timer has a power re-
serve of 15 minutes.
•The mode can be selected using the program buttons (4): Automatic,
Heating, Cooling, Frost Protection and Off modes are available.
•An indicator (5) on the left-hand side of the display shows the operating
mode.
Comfort Temperature
The desired comfort temperature (5 to 40 °C) is set on the upper rotating
knob (2). It is displayed on the right-hand side of the display instead of the
current temperature. Three seconds after the knob has been turned, the unit
automatically displays the current temperature again.
Operating Controls
1. Reset button
2. Adjustment wheel (Comfort temp.)
3. Adjustment wheel (Cooling temp.)
4. Program buttons
5. Operating status indicators
6. Operating mode indicators
G
Note: A change to the comfort temperature makes it necessary to
change the cooling temperature by the same amount because
the cooling temperature is relative to the comfort temperature.
Conversely, a change in the cooling temperature does not re-
quire a change in the cover temperature.

5
GNote: To protect against frost, the cooling temperature may not be set
below + 5 °C.
Cooling Temperature
The cooling temperature can be set on the lower adjustment knob (3). It is
displayed absolutely on the right half of the display. Three seconds after the
knob is turned, the unit automatically displays the current temperature again.
Frost Protection Temperature
The frost protection temperature is fixed at 5 °C. By pressing the two pro-
gram buttons + and –, the frost protection temperature can be selected.
The frost protection level is not accessible via the timer program or in cool-
ing mode.
The current target value can be queried by pressing the SET program but-
ton. After three seconds, the current temperature is displayed again.
Off
By pressing the two program buttons ¹and +at the same time, the operat-
ing mode is no longer displayed on the right-hand side of the display. The
unit continues to record the current temperature but all control functions are
completely switched off.
Hand Button
The >button makes it possible to change the current temperature mode
(comfort temperature / cooling temperature) in automatic mode. The se-
lected temperature mode is displayed by indicators on the right-hand side of
the display. This function is deleted for the next program point.
Reset
There are two different reset options:
1. Start up reset:
The RESET button (3) makes possible to restart the unit after operation has
been to interrupted due to a malfunction. The clock must be reset but the
program and parameter settings are retained.
2. Global reset
To force the unit to restart with the factory settings, the buttons RESET, +
and – must be pressed at the same time. After the RESET button is re-
leased, the buttons +and – must be held down until the version number
(r 10...) appears on the display.
GNote: Any previously entered individual timer program and any pa-
rameter settings are lost.

6
Setting the Clock
The clock can be set once the ¹program button
has been held down for 3 seconds or after the
unit restarts following a reset. If the clock has not
yet been reset, it blinks on the display.
When you press the SET program button, you are taken to the desired set-
ting option (Hours -> Minutes -> Day of the week). The selected option
blinks on the display.
By pressing one of the program buttons +or –, the value of the selected op-
tion can be changed and the selection confirmed by pressing the SET but-
ton.
After confirming the day of the week, the clock starts accurate to the sec-
ond. The unit returns to the operating mode from which the “Set Clock“
menu was accessed. If no button is pressed within 1 minute, the current
time automatically appears again.
Selecting the Operating Mode
The main operating modes are selected by
pressing one of the three program buttons on the
left. You can select from the following modes:
Automatic ¹, Comfort á(continuous) and Cool-
ing (continuous).
The Off and Frost protection Tmodes can be set by pressing the top and
middle or bottom and middle program buttons on the left at the same time.
The selected operating mode is displayed by indicators on the right-hand
side of the display. In the Automatic operating mode, one of the two indica-
tors also shows the currently valid temperature control (Comfort or Cooling).
No indicator is displayed in the Off operating mode.
Display Button Explanation
1. ¹Change time setting
2. 20:30 +/- Hours blinking; change setting with [-]
3. 10:00 SET Confirm entry
4. 10:00 +/- Minutes blinking; change setting with [+]
5. 10:16 SET Confirm entry
6. * +/- Day blinking; change setting with [+/-]
7. * SET Confirm entry and end programming
Programming Example: Monday, set 10:16

7
Entering a Timer Program
Programming example:
Change P02 to: MO - SA, starting at 18:30; night operation; (P02)
Display Button Explanation
1. PROG Set timer program (change)
2. 22:00 P01 +/- Program selection P01 blinking; change setting with [+]
3. 22:00 P02 SET Confirm entry
4. 22:00 +/- Time setting blinking; change setting with [-]
5. 18:30 SET Confirm entry
6. ' ' ' ' ' +/- Days of the week blinking; change setting with [+]
7. ' ' ' ' ' SET Confirm entry
8. SET Arrow blinking next to night operation; keep setting
9. P02 PROG P02 blinking; end programming with [PROG]
The timer program can be entered after the PROG
program button was pressed briefly. The program
point number appears on the display (PO1 to P16),
the corresponding time and day of the week on
which the respective temperature mode (Comfort
temperature or Cooling temperature; sea indicator on the right) will go into
effect.
When you press the SET program button, you are taken to the desired set-
ting option (Program point number -> Time -> Day -> Temperature mode).
Each selected setting option blinks on the display.
By pressing the +or – program buttons, the value of the selected option can
be changed and your selection confirmed by pressing the SET button.
If you press the PROG program button while the program point number is
blinking, the unit returns to the operating mode from which the “Enter Time
Program” menu was accessed.
Inactive program points are identified by a - -:- - instead of the time.
The following are standard presets made at the factory:
Mo – So: starting at 06:00 o’clock Comfort temperature
Mo – Fr: starting at 22:00 o’clock Cooling temperature
Sa – So: starting at 23:00 o’clock Cooling temperature
There are several options for setting the days of the week:
Individual days Different activation times
Monday - Friday Same activation times
Monday - Saturday Same activation times
Monday - Sunday Same activation times
Saturday - Sunday Same activation times

8
Setting the Functions
When you press the PROG program button for 6
seconds, you are taken to a menu where various
basic functions can be set. The functions are
shown on the left-hand side of the display and
the corresponding value or status on the right.
When you press the SET program button, you are taken to the desired set-
ting option. The setting option blinks on the display.
By pressing the +or – program buttons, the value of the selected setting op-
tions can be changed and your selection confirmed by pressing the SET
button.
After confirming the last function, the unit returns to the operating mode from
which the “Setting the Functions” menu was accessed.
The individual parameters mean the following:
Setting the Control Parameters
When you press the PROG program button for 6
seconds, you are taken to a menu where various
basic functions can be set. The functions are
shown on the left-hand side of the display and
the corresponding value or status on the right.
When you press the SET program button, you are taken to the desired set-
ting option. The setting option blinks on the display.
By pressing the +or – program buttons, the value of the selected setting op-
tions can be changed and your selection confirmed by pressing the SET
button.
After confirming the last function, the unit returns to the operating mode from
which the “Setting the Control Parameters” menu was accessed.
The individual parameters mean the following:
When used as a two-point control mechanism:
Parameter Default setting Minimum value Maximum value
Activation difference ± 1.0 K ± 0.1 K ± 3.0 K
Per proportional control ± 3.0K ± 1.0 K ± 10.0 K
Pulse width
5 min
1 min 15 min
When used as a pulsating control mechanism:

9
I E (internal / external sensor)
If the external sensor is selected but there is not
KTY temperature sensor connected, 65.0 °C ap-
pears on the display. The clock thermostat is not
controlling the output.
Preset: Alternative:
I
(internal)
E
(external)
Loc (button lock)
The button lock is displayed by the key symbol.
The button lock prevents the temperatures from
being changed using the rotating knobs. After the
button lock has been released, any temperature
changes are transferred. The button lock is acti-
vated by pressing the PROG program button for 6
seconds.
Preset: Alternative:
oFF
(inactive)
on
(active)
H C (Heating / Cooling display)
In Heating mode, the controlled relay on the left-
hand side of the display shows an arrow pointing
up (r). In Cooling mode, it displays an arrow
pointing down (s) .
Preset: Alternative:
HE
(heating)
Co
(cooling)
2PPu (2-point / Pulsating function display)
When the control function is switched from 2-
point to pulse and vice versa, this results in the
corresponding parameters being calculated on
the basis of the default settings. These settings
are explained under “Setting the Control Pa-
rameters”. If necessary, the values must be
changed as described in this section.
Preset: Alternative:
2-P
(2-point)
PuL
(pulsating)
SEnS (Sensor comparison display)
Constant temperature values should be available
for the sensor comparison. In addition, the sensor
comparison should be performed at normal room
temperatures (approx. 20 °C). For a comparison,
the current temperature displayed by the unit and
the temperature on the sensor must be known.
The difference between these two values can be
set within a ± 3.0K limit under the SEnS menu
item.
Example: The unit displays 20.7 °C. The tem-
perature measuring unit displays a temperature of
19.9 °C on the sensor. – 0.8 must be set under
the SEnS menu item.
Preset: Limits:
0.0 K ± 3.0K

10
For the authorised electrical installation personnel!
•Connection and service may only be performed by authorised electri-
cal personnel!
•Prior to performing any work on the unit, all power lines must be free
of electrical current and secured against switching on again!
•Connection is to be performed in accordance with the wiring diagram
on page 12.
•The unit may only be connected to lines that are permanently attached
in closed, dry rooms.
•When installing the unit, make sure that the electrical lines, for exam-
ple, power supply and relay connection lines, cannot come into con-
tact with low-current supply lines, such as sensor lines (minimum dis-
tance 4 mm for basic isolated line conductors).
•Make sure that there is adequate protection to prevent connection
conductors from becoming loose that meets the requirements of EN
60730 Part 1. This can be achieved, for example, by securing the lines
with cable bindings.
•Compliance with VDE 0100, EN 60730, Part 1, as well as all regula-
tions of the local EVU must be assured.
•If the unit does not function as expected, first check the power supply
and that the unit has been properly connected.
•To prevent problems, the external sensor lines may not be laid to-
gether with the other power conducting lines. A minimum distance of 4
mm must be maintained for basic isolated conductors.
•Use the sensor lines in accordance with the requirements. Observe
the maximum line length and required minimum cross-sections!
GWarning: The unit can be damaged if it is connected improperly! We
are not liable for damages that are the result of incorrect
connection and/or improper use!
Installation Instructions
Max. line length Line cross-section (Cu)
30 m 0.50 mm²
45 m 0.75 mm²
60 m 1.00 mm²
90 m 1.50 mm²

11
Mounting
The clock thermostat is suitable for mounting on many European lower wall
sockets as well as for conventional wall-mounting with wall cable slot.
When mounting on the wall, make sure that only the part intended for the
cable slot is separated from the bottom of the housing.
If the entire panel is removed, it is possible that the housing no longer com-
pletely closes.
MO DI MI D O FR SA S O
MODI MI DO FR SA SO
G
Note: The electronic clock thermostat must be mounted on the wall in
such a way that it can measure the average room temperature.
Drafts and proximity to windows and doors or sources of heat,
etc. are to be avoided.
GNote: The electronic clock thermostat should be attached to inner walls
approx. 1.5 m above the floor.

12
Wiring Diagram ATR- 4
GNote: The control line for the thermostat connection of the REMKO
heater is made at terminals 1 and 3.
For cooling units, to terminals 1 and 2.
GCaution: There must be a power current of ∼230 V/50 Hz at terminals
6 and 7 at all times for the unit to function
We reserve the right to make technical changes
∼230 V/50 Hz
Unit connection
External sensor

13
Program point Time Day(s) Level
PO1
PO2
PO3
PO4
PO5
PO6
PO7
PO8
PO9
P10
P11
P12
P13
P14
P15
P16
The following tables can be used to enter individual customer data:
Customer Data
Timer program:
Control parameters:
Activation difference
or:
Proportional control
Pulse duration
Functions:
Sensor comparison
Heating / Cooling
2-point / Pulse operation
Internal / External sensor
Button lock

14
Technical Data
Type ATR-4
Temperature range + 5... + 40 °C
Temperature cooling 2... 10 K, adjustable
Temperature sensor NTC (internal)
or KTY (external)
Sensor tolerance ± 1 K
Activation difference ± 0,1... ± 3,0K, adjustable
Proportional control 1...10 K, adjustable
Pulse duration 1...15 min, adjustable
Temperature activation Target value 0.5 K
Current value 0.1 K
Target temperature setting Rotating knobs
Program points 16
Clock timer Electronic weekly clock timer
Power reserve 1) approx. 15 minutes
Display LC display
Operating current 230 V AC (± 10%)
Power consumption approx. 2VA
Relay contact 1 isolated change-over contact
Max. supply of switch current 10(4)A, 230 V AC
Electrical connections Screw terminals
Electrical lifespan 0.5 x 105 operating cycles
Max. ambient temperature 0...+ 50 °C
Storage temperature - 10... + 70 °C
Housing: Material plastic
Protection type IP 20
Protection class II in accordance with DIN EN 60335-1
Dimen. W x H x D 132 x 82 x 32 mm
Attachment Wall-mounted
Weight approx. 250 g
Ref. No. 1011340
1) The power reserve only refers to the time.
All other parameters remain permanently saved.


REMKO GmbH & Co. KG
Klima- und Wärmetechnik
D-32791 Lage •Im Seelenkamp 12
D-32777 Lage •PO Box 1827
Phone +49 (5232) 606 - 0
Fax +49 (5232) 606260
E-Mail: info@remko.de
Internet: www.remko.de
Table of contents
Other REMKO Thermostat manuals
Popular Thermostat manuals by other brands

RCS
RCS TZ16 Installation and operation manual

Johnson Controls
Johnson Controls GLAS Technical bulletin

Ocean Breeze
Ocean Breeze QU-800 user manual

IDEAL
IDEAL Vogue S15 user guide

White Rodgers
White Rodgers 1F86-444 Installation and operation instructions

Pepco
Pepco Web-Programmable Thermostat Homeowner's manual

American Standard
American Standard asystat 570 owner's guide

iolloi
iolloi TH213-ES010 user guide

Honeywell
Honeywell FOCUSPRO TH6320R operating manual

Eurotronic
Eurotronic SPARmatic premium user manual

BECA ENERGY CONTROLS
BECA ENERGY CONTROLS BHT-1000 user guide

American Standard
American Standard Ceratherm T203.740 installation instructions