
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
17 63-2675—04
OPERATION
Fan Sequence Operations (ISU 347, 348, 349)
If heat pump or conventional application modes are
enabled in ISU 170, then ISU 347 is not available for fan
ramp algorithm. The fan operates as a default ON/AUTO
selection that works the same way as our CommercialPRO
TB7220 thermostat. There is only one fan relay output that
is activated.
If PTAC or fan coil thermostat application modes are
enabled in ISU 170, then ISU 347 fan ramp algorithm is
available for installer setup selection. The fan ramp
algorithm will automatically calculate the appropriate fan
speed that is needed to meet the proportional band
requirements to speed up setpoint satisfaction. When the
setpoint is satisfied it will revert to the lowest fan speed
setting to conserve energy.
The thermostat comes factory default with the fan
ramping algorithm enabled (ISU 347). This gives the user
the ability to select Auto-Lo-Med-Hi option in ISU 348 or
Auto only option in ISU 348. Auto sets the thermostat into
the fan ramping algorithm mode and automatically sets
the sufficient speed for PI control. Auto also automatically
shuts the fan off when there is not a call for heating or
cooling. If the user decides to disable ISU 347, then the
fan will only have Lo-Med-Hi option available.
If ISU 347 is not enabled, then ISU 348 does not appear as
a user selection choice.
If ISU 347 is enabled, then ISU 349 is available as a
selection choice. The user can select either a 2 hour or 4
hour timer fan reset function. The fan will reset from a
constant on speed to Auto mode after the time period
expires. If ISU 347 is not enabled, then ISU 349 does not
appear as a user selection choice.
Equipment Sequence Operations (ISU 170)
Heat Pump and Conventional
Heat Pump and conventional use a single fan speed. The
single fan speed label is the G terminal relay output.
Display on the thermostat for these modes will give the
Fan On/Auto option. There is no fan ramping algorithm,
ISU 347, 348, 349 are not available.
PTAC
PTAC modes 10 and 11 will have the same selection
options available as the heat pump selection options. The
only difference is that the PTAC options have a Lo and Hi
speed fan output instead of single speed output and that
it follows the fan sequencing described above with ISU
347, 348, 349.
4 Pipe
4 pipe is treated similar to 1H/1C conventional. It follows
the fan sequencing described above with ISU 347, 348, 349.
2 Pipe
There are two different 2 pipe modes - 2 pipe only and 2
pipe with reheat.
2 pipe only - 2 pipe modes do not contain the ability to
have automatic changeover. They are manual changeover
only. The thermostat will have a priority when choosing a
system mode (heat or cool). When ISU #340 has a 2 pipe
changeover sensor enabled, the thermostat screen system
mode will lock on heat or cool (whatever the changeover
sensor is communicating to the thermostat). If ISU #340
does not have a changeover sensor enabled, then the
system mode from the thermostat screen can manually be
adjusted between heat or cool. It follows the fan
sequencing described above with ISU 347, 348, 349.
2 pipe with reheat - 2 pipe modes do not contain the
ability to have automatic changeover. They are manual
changeover only. The thermostat will have a priority when
choosing a system mode (heat or cool). When ISU #340
has a 2 pipe changeover sensor enabled, the thermostat
screen system mode will lock on heat only. When the 2
pipe changeover sensor is sensing cool mode, the user
can adjust to heating mode which will bring on the
auxiliary heat. If ISU #340 does not have a changeover
sensor enabled, then the system mode from the
thermostat screen can manually be adjusted between
heat or cool. It follows the fan sequencing described above
with ISU 347, 348, 349.
Operating Sequence
The thermostat energizes specific terminal(s), depending
on the demand for heating, cooling or fan. The thermostat
screen shows the time, inside temperature, system and
fan selections. Additional indicators are shown when the
heating, cooling or fan is energized. See Tables 8 and 9 for
specification information.
Table 8.
Sequence of Operation for Conventional Systems
.
a
If Installer Setup System type is set to two stages of cooling.
bG energizes only if Installer Setup 0180 is set to Electric.
Table 9. Sequence of Operation for Heat Pump Systems.
aConfigure O/B in Installer Setup. Based on last piece of
equipment called (cooling = O; heating = B).
bIf Installer Setup System Type is set to 2Heat/1Cool Heat
Pump with Auxiliary Heat.
System
Setting
Fan
Setting
Call for
Action
Energize
Terminals
Screen
Message
Off Auto — — —
Cool Auto — — —
Cool
or Auto
Auto Stage 1
Cooling
Y, G Cool On
Heat Auto — — —
Heat
or Auto
Auto Stage 1
Heating W, GbHeat On
System
Setting
Fan
Setting
Call for Action
Energize
Terminals
Screen
Message
Off Auto — O/Ba—
Cool
Cool
or Auto
Auto Stage 1 Cooling Y, G, O/BaCool On
Heat Auto — O/Ba—
Heat
or Auto
Auto Stage 1 Heating Y, G, O/BaHeat On
Stages 1 and 2
Heating Y, W1b, G,
O/Ba
Auxiliary
Heat On