2CAUA-COOLING-COIL (03-22) 166152-A
GENERAL INFORMATION—CONTINUED
Unpacking and Inspection
If, upon removing it from its crate, the unit has been found to have incurred any damage in shipment, document
the damage with the transporting agency and contact an authorized Factory Distributor. If you are an authorized
Distributor, follow the FOB freight policy procedures.
Pre-Installation Checklist
Check the rating plate for the specifications and electrical characteristics to be sure that they are compatible with
the installation.
Read these instructions and become familiar with the installation requirements. If you do not have knowledge of
local requirements, check with the local gas company or any other local agencies who might have requirements
concerning this installation.
Make preparations for necessary supplies, tools, and manpower. Installation should be done by an HVAC technician
qualified in refrigerant system installation.
Verify that the package of parts required to install the heat section condensate drain is either already installed
or at the job site.
Locate the thermostatic expansion valve(s) that are shipped loose. ACU unit size 060 has either one or two valves,
unit size 072 has one valve, and unit sizes 090–180 have two valves.
If a reducer is required to connect the thermostatic expansion valve to the distributor, the required reducers are
shipped with the valves.
Refer to Table 2 to verify that the thermostatic expansion valve(s) are correct for the installation.
Table 2. Thermostatic Expansion Valve (TXV) Kit Components and Connection Sizes
Cased
Cooling Coil
Kit PN
Component Distributor
Connection
on Coil
Liquid Line Connection*Suction Line
Tubing
Model Unit
Size
Evap
Coil
Reducer TXV Inlet** Outlet
Circuit
ABABABABABAB
PN*** Connection Size (Inches)
ACUA
060 258856 257328 216428 — 234052 — 5/8 — 5/8 — 7/8 — 7/8 —
258858 258846 —220552 220553 5/8 1/2 5/8 5/8 7/8
072 258857 257329 220555 — 7/8 — 5/8 — 7/8 — 7/8 —
090 258860 257538 216428 220554 5/8 5/8 7/8 7/8
258861 257330 — 216428 220553 234052 5/8 7/8
ACUB
090 258860 257539 216428 220554 5/8 5/8 7/8 7/8
258861 257331 — 216428 220553 234052 5/8 7/8
120 258862 257540 216428 234052 5/8 5/8 7/8 7/8
258863 257332 — 220553 220555 5/8 7/8 5/8 7/8
150 258864 257541 — 220555 7/8 5/8 7/8 7/8
258865 257333 216428 — 220554 220557 5/8 7/8 1-3/8 7/8
ACUC
120 258862 257542 216428 234052 5/8 5/8 7/8 1-3/8
258863 257334 — — 220553 220555 5/8 7/8 5/8 7/8 1-3/8 7/8
150 258864 257543 — — 220555 7/8 7/8 5/8 7/8 1-3/8
258866 257335 216428 216432 220554 220557 5/8 1-1/8 1-3/8 7/8
180 258867 257544 216432 220557 1-1/8 1-1/8 5/8 7/8 1-3/8
258868 257336 216428 216432 234052 220557 5/8 1-1/8 1-3/8 7/8
*Circuit A is bottom connection. Circuit B is top connection.
**Liquid line tubing size.
***Refer to Table 3 for specifications.