Rheem Raypak 4-20mA EMS User manual

Eective: 07-30-21
Replaces: 11-20-07
P/N 241323 Rev. 3
INSTALLATION AND OPERATING
INSTRUCTIONS
4-20mA EMS
Interface
Adds 4-20mA Setpoint
capability to
TempTracker Mod+
Control System
IMPORTANT SAFETY INSTRUCTIONS. READ AND FOLLOW ALL
INSTRUCTION. SAVE THESE INSTRUCTIONS.
NOTE: These instruction are for the use of qualied individuals specially trained and experienced in the
installation and maintenance of this type of equipment and related system components. Installation and service
personnel are required by some states to be licensed. Persons not qualied shall not attempt to install, service,
or maintain this equipment.
These instructions should be maintained in legible condition and kept adjacent to the vunit or in a safe place for
future use.
4-20 mA EMS
4-20mA INPUT
+Signal GND
123
RS485
EXTENSION
CONNECTORS
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED

2
Revision 3 reects the following changes:
Reformatted to current standards.
TABLE OF CONTENTS
1. WARNINGS ............................................................ 3
Pay Attention to these Terms .................................. 3
2. INTRODUCTION..................................................... 3
3. WIRING .................................................................... 3
Wiring the EMS Signal ............................................ 3
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED

3
• The 4-20mA EMS Interface can provide the DC
current for the 4-20mA input signal. If using the
4-20mA EMS Interface to provide the power, attach
the (+) side of the EMS/BMS signal to the 4-20mA
EMS Interface terminal marked +. Attach the (-) side
of the EMS/BMS signal to the 4-20mA EMS Interface
terminal marked SIGNAL as shown in Figure 2.
4-20 mA EMS
4-20mA INPUT
+Signal GND
123
RS485
EXTENSION
CONNECTORS
(-)
(+)
EMS/BMS Input
Figure 2. TempTracker Provides Current for 4-20 mA
Signal
Connect the TempTracker Mod+, 4-20mA EMS interface
and up to two Extension Panels in the order shown in
Figure 3 for proper operation using the 6-wire phone
cables provided.
EMS 4-20mA input scale is shown in Figure 4.
1. INTRODUCTION
The 4-20mA EMS Interface (sales order option B-39,
kit 012019) provides the TempTracker. Mod+ control
with the capability of receiving an external Setpoint as a
4-20mA signal through Energy Management or Building
Management Systems (EMS/BMS). The External
Setpoint is a temperature input and can also function as a
Shutdown signal.
2. WIRING
Wiring the EMS Signal
• The signal must be a two-wire 4-20mA.
• A system sensor must be installed to the TempTracker
Mod+ control.
• The External Setpoint must be set up correctly (See
TempTracker Mod+ documentation). These settings
will allow the TempTracker Mod+ to read and monitor
the system temperature and also monitor the 4-20mA
input to remotely adjust the setpoint to the desired
value.
• If the EMS/BMS or other equipment signal provides
the DC current, attach the (+) side of the EMS/BMS
signal to the 4-20mA EMS Interface terminal marked
SIGNAL. Attach the (-) side of the EMS/BMS signal
to the 4-20mA EMS Interface terminal marked GND
as shown in Figure 1.
4-20 mA EMS
4-20mA INPUT
+Signal GND
123
RS485
EXTENSION
CONNECTORS
(-)
(+)
EMS/BMS Input
Figure 1. External Device (e.g. BMS) Provides Current for
4-20 mA Signal
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED

4
Figure 3. Connecting 4-20mA EMS Interface to TempTracker Mod+ with Two Extension Panels using RS485
TEMPTRACKER MOD+ EXTENSION A*
TEMPTRACKER MOD+ EXTENSION B *
TEMPTRACKER MOD+
--------
SYSTEM
A
B
C
D
12
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
345
6
78
9
10 11
12
13 15
14 17
16 18 20
19 21 24
23 29
25 27
26 28 32
30 31
LN
-+
+
TT
OO
RS-485
mA
GND VLT
SYS ABCD
PWR
CUR / VLT
A
-+
+
mA
GND VLT
-+
+
mA
GND VLT
+
22
-
GND VLT
+
mA
TEMP
OUTDOOR
OO
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
PROVE
/DHW
SHUTDOWN
/SETBACK
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 30VA MAX
INPUT RATINGS:
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
CAUTION
: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
F
H
J
Power
CAUTION:
Risk of Electric Shock.
More than one disconnect switch may be required
to de-energize the equipment before servicing.
PWR
L N
1 2
E
3 4
F
5 6
G
7 8
H
9 10
I
11 12
EXTENSION
MODULE
RS-485
Ext A
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
Use Copper Conductors Only.
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
C US
E
G
I
Comm
Ext B
K
M
O
L
N
P
1514
VLTmA
CUR / VLT
181716
VLTmAGND
CUR / VLT
212019
VLTmAGND
CUR / VLT
242322
VLTmAGND
CUR / VLT
13
GND
16
GND
19
GND
22
GND
J
11 12
K
MO
LN
P
E F G H
K
M
L
N
2726
VLTmA
CUR / VLT
302916
VLTmAGND
CUR / VLT
25
GND
28
GND
I J
OP
F
H
J
Power
CAUTION:
Risk of Electric Shock.
More than one disconnect switch may be required
to de-energize the equipment before servicing.
PWR
L N
1 2
E
3 4
F
5 6
G
7 8
H
9 10
I
11 12
EXTENSION
MODULE
RS-485
Ext A
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
Use Copper Conductors Only.
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
C US
E
G
I
Comm
Ext B
K
M
O
L
N
P
1514
VLTmA
CUR / VLT
181716
VLTmAGND
CUR / VLT
212019
VLTmAGND
CUR / VLT
242322
VLTmAGND
CUR / VLT
13
GND
16
GND
19
GND
22
GND
J
11 12
KMO
LNP
E F G H
KM
LN
2726
VLTmA
CUR / VLT
302916
VLTmAGND
CUR / VLT
25
GND
28
GND
I J
OP
4-20 mA EMS
4-20mA INPUT
+Signal GND
123
RS485
EXTENSION
CONNECTORS
4-20MA EMS INTERFACE
* WHEN USED
60
(15.5)
80
(26.7)
100
(37.8)
120
(48.9)
140
(60)
160
(71.1)
180
(82.2)
200
(93.3)
220
(104.4)
MILLI-AMP SIGNAL
4
6
8
10
12
14
16
18
20
SET POINT TEMPERATURE °F (°C)
Figure 4. Default EMS 4-20mA Input Scale (70°–220°F)
NOTE: Scale is user-adjustable to match system design characteristics.
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED

5
Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468
NOTES:
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
Other Rheem Recording Equipment manuals