RECOVERY CAPACITIES
MODE TEMPERATURE RISE - DEGREES F - GA ONS PER HOUR
NUMBER CAPACITY INPUT EFFICIENCY 40° 50° 60° 70° 80° 90° 100° 110° 120° 130° 140°
HE45-100 45 100,000 95% 288 230 192 165 144 128 115 105 96 /A /A
HE45-130 45 130,000 95% 374 299 249 214 187 166 150 136 125 /A /A
HE80-130 80 130,000 95% 374 299 249 214 187 166 150 136 125 /A /A
HE119-130 119 130,000 95% 374 299 249 214 187 166 150 136 125 /A /A
HE45-160 45 160,000 95% 461 368 307 263 230 205 184 167 154 142 132
HE80-160 80 160,000 95% 461 368 307 263 230 205 184 167 154 /A /A
HE119-160 119 160,000 95% 461 368 307 263 230 205 184 167 154 /A /A
HE45-199 45 199,000 95% 573 458 382 327 286 255 229 208 191 176 164
HE80-199 80 199,000 95% 575 460 384 329 288 256 230 209 192 /A /A
HE119-199 119 199,000 95% 575 460 384 329 288 256 230 209 192 /A /A
Recovery rating is based on a recovery efficiency obtained in an UL laboratory.
This model exceeds the minimum AECA energy factor requirements of ASHRAE 90.1b-1992.
Commercial water heaters
from Rheem-Ruud
MAXIMUM DE IVERY (in gallons) (Includes useable storage and recovery for indicated times)
MODE TEMP. 5 10 15 20 30 45 123MIN. TO RECOVER
NUMBER CAPACITY INPUT EFFICIENCY RISE MIN. MIN. MIN. MIN. MIN. MIN. HR. HR. HR. CONTENTS
HE45-100 45 100,000 95% 100° 41 51 60 70 89 118 147 262 377 23
HE45-130 45 130,000 95% 100° 44 56 69 81 106 144 181 331 481 18
HE80-130 80 130,000 95% 100° 68 81 93 106 131 168 206 355 505 32
HE119-130 119 130,000 95% 100° 96 109 121 134 159 196 234 383 533 48
HE45-160 45 160,000 95% 100° 47 62 78 93 124 170 216 400 584 15
HE80-160 80 160,000 95% 100° 71 87 102 117 148 194 240 424 609 26
HE119-160 119 160,000 95% 100° 99 115 130 145 176 222 268 452 637 39
HE45-199 45 199,000 95% 100° 51 70 89 108 146 203 261 490 719 12
HE80-199 80 199,000 95% 100° 75 94 114 133 171 229 286 516 747 21
HE119-199 119 199,000 95% 100° 103 122 141 161 199 257 314 544 774 31
DIMENSIONA INFORMATION (All dimensions shown in inches)
MODE APPROX. SHIPPING
NUMBER HEIGHT WIDTH DEPTH VENT WEIGHT ( BS.)
HE45-100 42 23-1/2 32 2 †175
HE45-130 42 23-1/2 32 2 †175
HE45-160 42 23-1/2 32 3 175
HE45-199 42 23-1/2 32 3 175
HE80-130 72 23-1/2 32 2 †235
HE80-160 72 23-1/2 32 3 235
HE80-199 72 23-1/2 32 3 235
HE119-130 73 27 36 2 †405
HE119-160 73 27 36 3 405
HE119-199 73 27 36 3 405
†Models with inputs of 100,000 kBtu and 130,000 kBtu are certified to vent with 2” Schedule 40 PVC,
CPVC or ABS pipe.
C EARANCES TO COMBUSTIB ES
MODE REAR /
NUMBER SIDES FRONT* TOP
HE45-100 00 0
HE45-130 00 0
HE45-160 00 0
HE45-199 00 0
HE80-130 00 0
HE80-160 00 0
HE80-199 00 0
HE119-130 00 0
HE119-160 00 0
HE119-199 00 0
* 24" service clearance recommended
Rheem-Ruud AdvantagePlu