Rheem Universal GD100-250 User manual

Printed in USA
FOR YOUR SAFETY!
— Do not store or use gasoline or other flammable
vapors or liquids or other combustible materials in
the vicinity of this or any other appliance. To do so
may result in an explosion or fire.
— WHAT TO DO IF YOU SMELL GAS
•Do not try to light any appliance.
•Do not touch any electrical switch; do not use any
phone in your building.
•Immediately call your gas supplier from a neigh-
bor's phone. Follow the gas supplier's instructions.
•If you cannot reach your gas supplier, call the fire
department.
•Do not return to your building until authorized by
the gas supplier or fire department.
— Improper installation, adjustment, alteration, service
or maintenance can cause injury, property damage
or death. Refer to this manual. Installation and ser-
vice must be performed by a qualified installer, ser-
vice agency or the gas supplier.
WARNING: If the information in these instructions are not followed exactly, a fire or explosion may result
causing property damage, personal injury or death.
NOTICE: This water heater is designed for use in a commercial application and the installation and maintenance of it should be per-
formed by a qualified, licensed service personnel. If the foregoing assumption is not appropriate, then we recommend that you obtain
and retain our Residential Use & Care Manual which contains additional consumer warnings and information.
!
!
!
AP13968 (06/06)
WITH INSTALLATION INSTRUCTIONS FOR THE CONTRACTOR
Commercial Induced Draft Water Heater
USE & CARE MANUAL
MULTI-FLUE COMMERCIAL MODELS
CALIFORNIA PROPOSITION 65 WARNING: This product contains chemicals known to the State of California to cause cancer, birth
defects or other reproductive harm.
!
Do Not Destroy this Manual. Please read carefully and
keep in a safe place for Future Reference.
Recognize this symbol as an Indication of Important
Safety Information!
!!
D
E
S
I
G
N
C
E
R
T
I
F
I
E
D
®
CERTIFIED
R

Safety Information
Safety Precautions . . . . . . . . . . . . . . . . 3-4, 12
Introduction
Local Installation Regulations . . . . . . . . . . . . 5
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation
Inspect Shipment . . . . . . . . . . . . . . . . . . . . . . 6
Water Connections . . . . . . . . . . . . . . . . . . . . 6
Gas Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Typical Installation . . . . . . . . . . . . . . . . . . . . . 7
Venting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installation Checklist . . . . . . . . . . . . . . . . . . . . 9
Operation
Lighting Procedure . . . . . . . . . . . . . . . 10 & 11
Temperature Settings . . . . . . . . . . . . . . . . . . 12
Emergency Cut Off . . . . . . . . . . . . . . . . . . . . 14
Troubleshooting
System Sentinel Diagnosis . . . . . . . . . 15 - 20
Customer Service
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
How to Obtain Service Assistance. . . . . . . . 24
TABLE OF CONTENTS
Your safety and the safety of others are very impor-
tant. There are many important safety messages in
this manual and on your appliance. Always read
and obey all safety messages.
TThhiissiisstthheessaaffeettyyaalleerrttssyymmbbooll..RReeccooggnniizzeetthhiissssyymmbboollaass
aanniinnddiiccaattiioonnooffIImmppoorrttaannttSSaaffeettyyIInnffoorrmmaattiioonn!!TThhiissssyymm--
bboollaalleerrttssyyoouuttooppootteennttiiaallhhaazzaarrddsstthhaattccaannkkiilllloorrhhuurrttyyoouu
aannddootthheerrss..
All safety messages will follow the safety alert sym-
bol and either the word “DANGER”, “WARNING”,
“CAUTION” or “NOTICE”.
These words mean:
DANGER An imminently hazardous
situation that will result in
death or serious injury.
WARNING A potentially hazardous
situation that could result
in death or serious injury
and/or damage to property.
CAUTION A potentially hazardous
situation that may result in
minor or moderate injury.
Notice: Attention is called to observe
a specified procedure or
maintain a specific condition.
!
!
!
!
READ THE SAFETY INFORMATION
Maintenance
Routine Preventive Maintenance . . . . . . . . .14
Burners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Venting System . . . . . . . . . . . . . . . . . . . . . . . 13
Anode Inspection . . . . . . . . . . . . . . . . . . . . . 14
Seasonal Operation . . . . . . . . . . . . . . . . . . . 14
Tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

3
To meet commercial water use needs, the thermostat on this water
heater is adjustable up to 180°F. However, water temperatures over
125°F. can cause severe burns instantly or death from scalds. This
is the preferred starting point for setting the control for supplying
general purpose hot water.
Safety and energy conservation are factors to be considered when
setting the water temperature on the thermostat. The most energy
efficient operation will result when the temperature setting is the
lowest that satisfies the needs consistent with the application.
Maximum water temperatures occur just after burner has shut off.
To find hot water temperature being delivered, turn on a hot water
faucet and place a thermometer in the hot water stream and read
the thermometer.
General Safety Precautions
!
The following chart details the relationship of water temperature
and time with regard to scald injury and may be used as a guide in
determining the safest water temperature for your applications.
The temperature of the water in the heater can be regulated by
setting the temperature dial on front of the thermostat. To comply
with safety regulations the thermostat was set at its lowest setting
before water heater was shipped from the factory. The illustration
below illustrates the thermostat and how to adjust the water tem-
perature.
Hotter water increases the Potential for Hot Water SCALDS.
NOTICE: Mixing valves are available for reducing point of use
water temperature by mixing and cold water in branch water lines
Contact a licensed plumber or the local plumbing authority for fur-
ther information.
DANGER
!
HOT
Water temperature over 125°F can
cause severe burns instantly or
death from scalds.
Children, disabled and elderly are
at highest risk of being scalded.
See instruction manual before
setting temperature at water
heater.
Feel water before bathing or
showering.
Temperature limiting valves are
available, see manual.
BURN
Temperature Time to Produce Serious Burn
120° F More than 5 minutes
125° F 11/2to 2 minutes
130° F About 30 seconds
135° F About 10 seconds
140° F Less than 5 seconds
145° F Less than 3 seconds
150° F About 11/2 seconds
155° F About 1 second
Table courtesy of Shriners Burn Institute
TIME / TEMPERATURE RELATIONSHIPS IN SCALDS
DANGER
!
120
140
°
F
1
8
0
1
6
0
1
4
0
1
3
0
1
2
0
1
1
0
1
0
0
THERMOSTAT
°
C
8
0
7
0
6
0
5
0
4
0
To adjust the water temperature, insert a small
straight screwdriver into slotted screw in hole in
front of thermostat and turn wheel to desired
setting. Thermostat is adjustable up to 180º F.
CAUTION!! - Hotter water increases the risk of SCALDING!
White-Rodgers
Honeywell
NOTICE: Each water heater will contain one (1) of the above ther-
mostats.

4
General Safety Precautions
Be sure to read and understand the entire Use & Care Manual before attempting to install or operate this water heater. Pay particular
attention to the following General Safety Precautions. Failure to follow these warnings could result in a fire or explosion, causing prop-
erty damage, bodily injury or death . Should you have any problems understanding the instructions in this manual, STOP, and get help
from a qualified installer or service technician or the gas supplier.
DANGER
!
DANGER
!
Failure to properly vent the water heater to the outdoors
as outlined in the Venting Section of this manual can
result in unsafe operation of the water heater. To avoid the
risk of fire, explosion, or asphyxiation from carbon
monoxide, never operate this water heater unless it is
properly vented and has an adequate air supply for proper
operation. Be sure to inspect the vent system for proper
installation at initial start-up; and at least annually there-
after. Refer to Maintenance section of this manual for
more information regarding vent system inspections.
DANGER
!
LIQUEFIED PETROLEUM MODELS — Propane, or LP gas,
must be used with great caution.
• It is heavier than air and will collect first in lower areas
making it hard to detect at nose level.
•Make sure to look and smell for LP leaks before
attempting to light appliance. Use a soapy solution to
check all gas fittings and connections. Bubbling at a
connection indicates a leak that must be corrected.
When smelling to detect an LP leak, be sure to sniff
near the floor too.
• Gas detectors are recommended in LP applications
and their installation should be in accordance with the
manufacturer's recommendations and/or local laws,
rules, regulations or customs.
• It is recommended that more than one method be used
to detect leaks in LP applications.
IF LP GAS IS PRESENT OR SUSPECTED:
•
DO NOT
attempt to find the cause yourself;
•
DO NOT
try to light any appliance;
•
DO NOT
touch any electrical switch;
•
DO NOT
use any phone in your building.
• Leave the house immediately and make sure your fami-
ly and pets leave also.
• Leave the doors open for ventilation and contact the
gas supplier, a qualified service agency or the fire
department.
• Keep the area clear until the service call has been
made, the leak is corrected, and a qualified agency has
determined the area to be safe.
Gasoline, as well as other flammable materials and liquids
(adhesives, solvents, etc.), and the vapors they produce,
are extremely dangerous. DO NOT handle, use or store
gasoline or other flammable or combustible materials any-
where near or in the vicinity of a water heater. Be sure to
read and follow the warning label pictured below and
other labels on the water heater, as well as the warnings
printed in this manual. Failure to do so can result in prop-
erty damage, bodily injury, or death.
Both LP and natural gas have an odorant added to help
detection. Some people may not physically be able to
smell or recognize this odorant. If unsure or unfamiliar
about the smell associated with LP or natural gas, ask the
gas supplier. Other conditions, such as "Odorant Fade",
which causes the odorant to "fade", or diminish in intensi-
ty can also hide or camouflage a gas leak.
!
Water heaters utilizing Liquefied Petroleum gas (LP) are
different from natural gas models. A natural gas heater will
not function safely on LP gas and vice versa. No attempt
should ever be made to convert a heater from natural gas
to LP gas. To avoid possible equipment damage, personal
injury or fire: DO NOT connect this water heater to a fuel
type not in accordance with unit data plate. Propane for
propane units. Natural gas for natural gas units. These
units are not certified for any other type fuel.
LP appliances should not be installed below-grade (for
example, in a basement) if such installation is prohibited by
federal, state and/or local laws, rules, regulations or cus-
toms.
!
DANGER
!
FLAMMABLES
Flammable Vapors
Vapors from flammable
liquids will explode and
catch fire causing death or
severe burns.
Do not use or store flammable
products such as gasoline,
solvents or adhesives in the
same room or area near the
water heater.
Keep flammable products:
1. far away from heater,
2. in approved containers,
3. tightly closed and
4. out of children's reach.
Water heater has a main
burner and pilot flame.
The pilot flame:
1. which can come on at
any time and
2. will ignite flammable
vapors.
Vapors:
1. cannot be seen,
2. are heavier than air,
3. go a long way on the
floor and
4. can be carried from
other rooms to the pilot
flame by air currents.
Installation:
Do not install water heater
where flammable products will
be stored or used unless the
main burner and pilot flames
are at least 18" above the
floor.This will reduce, but not
eliminate, the risk of vapors
being ignited by the main
burner or pilot flame.
Read and follow water heater warnings and instructions. If owners
manual is missing, contact the retailer or manufacturer.

5
Read and Review this entire Manual with special emphasis on
Pages 6-9 prior to any installation work.
LLOOCCAALLIINNSSTTAALLLLAATTIIOONNRREEGGUULLAATTIIOONNSS
This water heater must be installed in accordance with these in-
structions, local codes, utility company requirements and/or, in the
absence of local codes, the latest edition of the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and
Propane Installation Code.
LLOOCCAATTIIOONN
AA..The water heater should be installed in a clean, dry location as
close as practical to the gas vent terminals. Long hot water lines
should be insulated to conserve water and energy. The water
heater and water lines should be protected from exposure to freez-
ing temperatures.
BB..A gas fired water heater should not be installed in a space where
liquids which give off flammable vapors are to be used or stored.
Such liquids include gasoline, LP gas (butane and propane), paint
or adhesives and their thinners, solvents or removers. Because of
natural air movement in a room or other enclosed space, flammable
vapors can be carried some distance from where their liquids are
being used or stored. The open flame of the water heater’s inter-
mittent pilot or main burner can ignite these vapors causing an
explosion or fire which may result in severe burns or death to those
in range, as well as property damage. For these reasons, instal-
lation of a gas fired water heater in a garage is not desirable.
If a location in a garage is the only alternative, the gas water heater
should be installed so that the open flame of the pilot and main
burner are no less than 18 inches above the garage floor. The
water heater must be located or protected so it is not subject to
physical damage by moving vehicles or area flooding. Raising the
gas fired water heater will reduce BUT NOT eliminate the possibili-
ty of lighting the vapor of any flammable liquids which may be
improperly stored or accidentally spilled.
CC..All models are certified for installation on combustible floors and
in alcoves. The minimum side and top clearance to walls and ceil-
ing for providing protection of combustible materials are shown
on the water heater’s rating label. A front clearance of 18 inches
(46 cm) should be provided for adequate inspection and servicing.
If the water heater must be installed on carpeting, place a metal
or wood panel beneath water heater extending beyond its full
width and depth at least 3 inches (7.6 cm) in all directions. If the
water heater is installed in an alcove, the entire floor must be cov-
ered by the panel.
The water heater should not be located in an area where leakage
of the tank or connections will result in damage to the area adja-
cent to it or to lower floors of the structure. When such areas can-
not be avoided, it is recommended that a suitable catch pan, ade-
quately drained, be installed under the water heater. The pan
MUST NOT restrict the flow of combustion air flow to bottom of
water heater.
NNOOTTIICCEE::AAuuxxiilliiaarryyccaattcchhppaanniinnssttaallllaattiioonnMMUUSSTTccoonnffoorrmmttootthhee
aapppplliiccaabblleellooccaallccooddeess..
DD..RREESSTTAAUURRAANNTTSS—
—If the water heater is to be installed in a restau-
rant or other location where the floor is frequently cleaned, it must
be elevated to provide at least six inches (15 cm) of clearance
from the floor to comply with NSF International recommendations.
A factory-designed leg extension kit is available for this purpose
from the distributor or store where the water heater was purchased.
EE..CCOOMMBBUUSSTTIIOONN&&VVEENNTTIILLAATTIIOONNAAIIRR——Proper operation of the
water heater requires air for combustion and ventilation. If the
water heater is installed in a building of conventional frame, ma-
sonry or metal construction, and there are no other appliances
installed that require an air supply, infiltration air is normally ad-
equate for proper combustion and ventilation, and an outside air
supply for the water heater may not be required. However, if the
water heater is installed in a confined space, or the building is of
unusually tight construction, then an outside air supply must be pro-
vided. Provisions for Combustion and Ventilation air must com-
ply with the applicable codes and standards as defined in the Local
Installation Regulations section on page 5.
FFOORRIINNSSTTAALLLLAATTIIOONNSSIINNTTHHEEUUNNIITTEEDDSSTTAATTEESS::
If the water heater is to be installed in a confined space, defined
as one having a volume of less that 50 cubic feet (1.4 cu. meters)
per 1000 Btu/h of the total input of all appliances within that space,
an air supply must be provided. The air must be supplied through
two permanent openings of equal area, one of which is to be located
approximately 12 inches (30cm) above the floor and the other of
which is to be located approximately 12 inches (30cm) below the
ceiling. The minimum net free area of each opening must be not
less than one square inch per 1000 Btu/h of the total input of all the
appliances in the enclosure or structure, if each of the openings
communicates with other unconfined areas inside the structure.
If the required air is to be supplied directly from outdoors (or a
freely ventilated attic or crawl space), or through vertical ducts,
there must be two openings located as specified above, and each
must have a minimum net free area of not less than one square
inch (6.5 sq. cm) per 4,000 Btu/h of the total input rating of all ap-
pliances in the en-closure.
NNOOTTEE::IIfftthheeooppeenniinnggssaarreettoobbeeccoovveerreeddwwiitthhaapprrootteeccttiivveessccrreeeenn
oorrggrriillll,,tthheenneettffrreeeeaarreeaaoofftthheeccoovveerriinnggmmaatteerriiaallmmuussttbbeeuusseeddiinn
ddeetteerrmmiinniinnggtthheessiizzeeoofftthheeooppeenniinnggssmmeennttiioonneeddaabboovvee..PPrrootteecc--
ttiivveessccrreeeenniinnggffoorrtthheeooppeenniinnggssMMUUSSTTNNOOTTbbeessmmaalllleerrtthhaann11//44iinncchh
((..6644ccmm))mmeesshhttoorreessiissttccllooggggiinnggbbyylliinnttoorrootthheerrddeebbrriiss..
For additional information regarding combustion and ventilation
air supply requirements, refer to the latest edition of the Ameri-
can National Standard / National Fuel Gas Code, ANSI Z223.1
FFOORRIINNSSTTAALLLLAATTIIOONNSSIINNCCAANNAADDAA::
While the requirements for U.S. installations outlined above are
generally true in Canada, precise requirements for combustion
and ventilation air supplies are detailed in the CAN/CGA B149 In-
stallation Codes; under “Venting Systems and Air Supply for Ap-
pliances”. To ensure that the water heater is properly installed,
those requirements must be followed.
Large exhaust fans can lower the air pressure inside a building
or room and interfere with proper venting and operation. Com-
mercial kitchens or other locations that must maintain a high flow
of exhaust air should have the water heater installed in a sepa-
rate room with combustion and ventilation air supplied directly
from outside as described above.
FF..C
COORRRROOSSIIVVEEAATTMMOOSSPPHHEERREESS——The heater should not be in-
stalled near an air supply containing halogenated hydrocar-
bons. For example, the air in beauty shops, dry cleaning es-
tablishments, photo processing labs, and storage areas for
liquid and powdered bleaches or swim pool chemicals often
Introduction
CAUTION
!

contain such hydrocarbons. The air there may be safe to
breathe, but when it passes through a gas flame, corrosive
elements are released that will shorten the life of any gas burn-
ing appliance. Propellants from common spray cans or gas
leaks from refrigeration equipment are highly corrosive after
passing through a flame. The limited warranty is voided when
failure of water heater is due to a corrosive atmosphere. (Ref-
erence is made to the limited warranty for complete terms and
conditions.)
The manufacturer’s warranty does not cover any damage or
defect caused by installation, or attachment, or use of any special
attachment such as energy saving devices (other than those
authorized by the manufacturer) into, onto, or in conjunction with
the water heater. The use of such unauthorized devices may
shorten the life of the water heater and may endanger life and
property. The manufacturer disclaims any responsibility for such
loss or injury resulting from the use of such unauthorized devices.
11..IINNSSPPEECCTTSSHHIIPPMMEENNTT——for possible damage. The manufacturer’s
responsibility ceases upon delivery of goods to the carrier in good
condition. Any claims for damage, shortage in shipments, or non
delivery must be filed immediately against carrier by consignee.
22..TTHHEERRMMAALLEEXXPPAANNSSIIOONN——DDeetteerrmmiinneeiiffaacchheecckkvvaallvveeeexxiissttssiinn
tthheeiinnlleettwwaatteerrlliinnee..It may have been installed in the cold water
line as a separate back flow preventer, or it may be part of a
pressure reducing valve, water meter or water softener. A check
valve located in the cold water inlet line can cause what is re-
ferred to as a ””cclloosseeddwwaatteerrssyysstteemm””. A cold water inlet line with
no check valve or back flow prevention device is referred to as
an ”open” water system.
As water is heated, it expands in volume and creates an increase
in the pressure within the water system. This action is referred
to as ””tthheerrmmaalleexxppaannssiioonn””. In an ”open” water system, expand-
ing water which exceeds the capacity of the water heater flows
back into the city main where the pressure is easily dissipated.
A ””cclloosseeddwwaatteerrssyysstteemm””, however, prevents the expanding water
from flowing back into the main supply line, and the result of
””tthheerrmmaalleexxppaannssiioonn””can create a rapid, and dangerous pres-
sure increase in the water heater and system piping. This rapid
pressure increase can quickly reach the safety setting of the re-
lief valve, causing it to operate during each heating cycle. Ther-
mal expansion, and the resulting rapid, and repeated expansion
and contraction of components in the water heater and piping
system can cause premature failure of the relief valve, and pos-
sibly the heater itself.Replacing the relief valve wwiillllnnoottcorrect
the problem!
The suggested method of controlling thermal expansion is to install
an expansion tank in the cold water line between the water heater
and the check valve. The expansion tank is designed with an air cush-
ion built in that compresses as the system pressure increases,
thereby relieving the over pressure condition and eliminating the re-
peated operation of the relief valve. Other methods of controlling ther-
mal expansion are also available. Contact your installing contractor,
water supplier, or plumbing inspector for additional information re-
garding this subject.
If a recirculation line is installed, the return connection should be
made to a tee close to the inlet connection on the water heater.
A check valve should always be installed in the recirculation line
to prevent cold water from entering.
33..WWAATTEERRCCOONNNNEECCTTIIOONNSS——This water heater may be connected
individually, in multiples with others, or with an external hot water
storage tank.
Inlet water connections are made to the lower coupling on the heater,
and outlet water connections are made to the upper coupling or, if
desired on models so equipped, the optional top connections may
be utilized.
Each water heater is supplied with the necessary diffuser tubes,
to make the water connections that will ensure proper performance.
If special instructions are required for any specific water heater,
they will be included with the diffuser tube.
Cap or plug unused connections. Use only clean, new galvanized
steel, copper or approved plastic pipe for water connections. Local
codes or regulations shall govern the exact type of material to be
used. The installation of unions on the inlet and outlet water lines
and a shut-off valve in at least the cold water inlet line is recom-
mended, so the water heater may be easily disconnected for ser-
vicing. Dielectric unions are not required for protection of water
heater.
When this water heater is supplying general purpose hot water
requirements for use by individuals, a thermostatically controlled
mixing valve is recommended to reduce the risk of scald injury.
Contact a licensed plumber or the local plumbing authority for fur-
ther information.
Thermometer(s) should be installed so that they indicate the tem-
perature of the water at or near the outlet of the water heater and
storage tank(s) if provided. See Fig. 4 on page 7.
44..RREELLIIEEFFVVAALLVVEE——A new factory installed combination pressure
and temperature relief valve, complying with the Standard for Re-
lief Valves and Automatic Gas Shutoff Devices for Hot Water Sup-
ply Systems, ANSI Z21.22, or Standard CAN1-4.4, Temperature,
Pressure, Temperature and Pressure Relief Valves and Vacuum
Relief Valves is provided with the water heater. No valve is to be
placed between the relief valve and the water heater. For a cir-
culating tank installation, the separate storage tank(s) must have
similar protection. The pressure rating of the relief valve must not
exceed 150 psi (160 psi for ASME models), the maximum working
pressure as marked on front of the water heater.
The Btu/h rating of the relief valve must equal or exceed the Btu/h
input of the water heater as marked on its rating plate.
Connect the outlet of the relief valve to a suitable open drain. The
discharge line must pitch downward from the valve to allow com-
plete draining (by gravity) of the relief valve and discharge line, and
be no smaller than the outlet of the valve. The end of the discharge
line should not be threaded or concealed and should be protect-
ed from freezing. No valve of any type, restriction or reducer cou-
pling should be installed in the discharge line. Local codes shall
govern the installation of relief valves.
55..GGAASSSSUUPPPPLLYY——The inlet gas pressure to the water heater must
not exceed 10.5” w.c. (2.6 kPa) for Natural gas. For purposes of
input adjustment, the minimum inlet gas pressure (with main burn-
er on) is shown on the rating plate. Check to see if high or low gas
pressure is present and then contact the gas company for correc-
tion.
The gas line should be of adequate size to prevent undue pressure
drop. Sizing based upon Table 1 (on pg. 9) is recommended. No
additional allowance is necessary for an ordinary number of fit-
tings.
6
Installation

7
Installation
SYSTEMSENTINEL
POWER
THERMOSTAT
IGNITION
PILOTVALVE
MAINVALVE
ECO
®
SYSTEMSENTINEL
POWER
THERMOSTAT
IGNITION
PILOTVALVE
MAINVA LV E
ECO
®
Figure 4. — Typical Gravity Circulating System
Hot Outlet
2"
Check Valve
Check Valve
Recirculation Loop
Storage
Tank
Optional
Return
Outlet
Cold Water
Inlet
Shut-Off
Valve
Discharge Pipe to Suitable Open Drain
Discharge Pipe to Suitable Open Drain
Air Gap 6"
Gas Valve
Cap
Sediment Trap
Ground Joint Union
Thermostat
To Gas
Supply
Manual
Gas
Shut-Off
Temperature & Pressure Relief Valve
(See Local Code)
Temperature & Pressure Relief Valve
(See Local Code)
Temperature & Pressure Relief Valve
(See Local Code)
Discharge Line
to Suitable Open Drain
Temperature & Pressure
Relief Valve
Hot
Outlet
Cold
Inlet
Shut-Off
Valve
Recirculation Loop
Recirculator
To
Gas
Supply
Manual
Gas
Shut-Off
Ground Joint Union
Thermostat
Manifolds
Circulator
Control
(Optional)
Cap
Gas Valve
Check Valve
Check Valve
Circulator*
* Circulator may be wired to run
continuously without the Control
Air Gap 6"
Sediment Trap
Figure 5. — Typical Forced Circulation Tank System with Factory Supplied Jacketed & Insulated Storage Tanks.
NOTES:
1.) Heater's Outlet Piping must have upward
slope, otherwise use Circulator
2.) If Vertical Tank is used, follow same lay-
out.
3.) The gas supply piping must be adequate-
ly supported and aligned to minimize
loads (forces) on the water heater’s gas
valve and burner system.
NOTES:
1.) The gas supply piping must be
adequately supported and aligned to
minimize loads (forces) on the water
heater’s gas valve and burner system.
Vacuum Relief Valve
(Not Supplied)
If required, install per local codes
and valve manufacturer’s
instructions.
Vacuum Relief Valve
(Not Supplied)
If required, install per local codes
and valve manufacturer’s
instructions.

A ground joint union and manual shutoff valve should be installed
in the gas line near the water heater so that the burner assembly
may be easily removed. The shut-off valve must be readily ac-
cessible for turning on or off. See Fig. 4 on page 7.
A sediment trap must be installed at the bottom of the gas line.
See Fig. 4 on page 7.
66..LLEEAAKKTTEESSTTIINNGG——The water heater and its gas connections MUST
be leak tested at normal operating pressure before it is placed in
operation. Turn ON the manual gas shut-off valve near the water
heater. Use a soapy water solution to test for gas leaks at all con-
nections and fittings. Bubbles indicate a gas leak that must be
corrected. The water heater factory connections to the gas valve
should also be leak tested after placing the water heater in oper-
ation.
NEVER use open flame to test for gas leaks, as bodily injury or
property damage could result.
PPRREESSSSUURREETTEESSTTIINNGGTTHHEEGGAASSSSUUPPPPLLYYSSYYSSTTEEMM——The water
heater and its manual gas shut-off valve MUST be disconnected
from the gas supply piping system during any high pressure
testing of that system at pressures in excess of 1/2 psi
(14” w.c. / 3.5 kPa).
The water heater MUST be isolated from the gas piping system
by closing the manual gas shut-off valve during any pressure test-
ing of the gas supply piping at pressures equal to or less than
1/2 psi (14” w.c. / 3.5 kPa).
NNOOTTIICCEE::TThhiisswwaatteerrhheeaatteerruusseessCCaatteeggoorryy11,,TTyyppeeBBAApppplliiaannccee..DDoouu--
bblleewwaallllvveennttiinnggiisspprreeffeerrrreedd..
77..VVEENNTTIINNGG——The responsibility for providing a vent of adequate ca-
pacity and in good usable condition is that of the installing contrac-
tor. There is a limit to the Btu/h capacity of any given vent or chim-
ney style and height. For installations in the United States, capaci-
ty tables are printed in Appendix “G” of the National Fuel Gas Code
(ANSI Z223.1). For installations in Canada, this information is con-
tained in Appendix B of CAN/CGA B-149 Installation Codes
As an alternate method for sizing a vent connected to more than one
appliance, the effective area of the vent shall be not less than the
area of the largest vent connector plus 50% of the areas of addi-
tional draft hood outlets.
Any horizontal run of vent connector connecting the to the gas vent
or chimney, must have an upward slope of at least 1/4” per foot of
length. Single wall vent connectors must be at least 6” from adja-
cent unprotected combustible surfaces. Joints of vent connectors
should be securely fastened by sheet metal screws or other ap-
proved method. Provide support for vent, or vent connectors to keep
weight off of the water heater.
88..WWIIRRIINNGG——A polarized 120V 50/60 Hz power supply, with suit-
able disconnect means, must be connected to the black and white
leads provided. The current draw by the Induced Draft unit is 2.5
amps. The water heater, when installed, must be electrically
grounded in accordance with local codes, or, in the absence of
local codes, with the National Electrical Code, ANSI/NFPA 70 in
the United States; or CSA C22.1 Electrical Code, in Canada. Refer
to Fig. 14 on page 22 & 23 of this manual for water heater internal
wiring diagrams.
NNOOTTIICCEE::DDOONNOOTTuusseeiinn
ccoonnjjuunnccttiioonnwwiitthhaaGGFFCCII..
8
Installation

9
Installation
AA..WWaatteerrHHeeaatteerrLLooccaattiioonn
❑
Close to area of vent.
❑
Indoors and protected from freezing temperatures.
❑
Proper clearance from combustible surfaces observed and
water heater not installed on carpeted floor.
❑
Air supply free of corrosive elements and flammable vapors.
❑
Provisions made to protect area from water damage.
❑
Sufficient room to service heater.
BB..WWaatteerrSSuuppppllyy
❑
Water heater completely filled with water.
❑
Water heater and piping air vented.
❑
Water connections tight and free of leaks.
❑
Thermal expansion tank (if required).
CC..GGaassSSuuppppllyy
❑
Gas line equipped with shut-off valve, union, and sediment
trap/drip leg.
❑
Approved pipe joint compound used.
❑
Soap and water solution used to check all connections and
fittings for possible gas leak.
❑
Gas Company inspected installation (if required).
❑
Ample sizes of supply pipe.
❑
Gas pressure check based on fuel type.
DD..RReelliieeffVVaallvvee
❑
Discharge line run to open drain.
❑
Discharge line protected from freezing.
EE..VVeennttiinngg
❑
All pipe connections are secure (at inducer, vent terminals
and for each pipe joint connection)
❑
Vent terminal mounted properly.
FF..CCoommbbuussttiioonnAAiirr
❑
Adequate combustion air.
❑
Alternate fresh air source (if required).
❑
Negative air pressure potential.
TABLE 1
Maximum Capacity of Pipe in Cubic Feet of Gas per Hour for Gas Pressures of
0.5 psig or Less and a Pressure Drop of 0.3 Inch Water Column
Based on a 0.60 Specific Gravity Natural Gas; If 1.5 Specific Gravity L.P. Gas is used, multiply capacity by 0.63
Nominal Internal
Iron Pipe Size, Diameter
Inches Inches 10 20 30 40 50 60 70 80 90 100 125 150 175 200
1/2 .622 132 92 73 63 56 50 46 43 40 38 34 31 28 26
3/4 .824 278 190 152 130 115 105 96 90 84 79 72 64 59 55
1 1.049 520 350 285 245 215 195 180 170 160 150 130 120 110 100
1 1/4 1.380 1,050 730 590 500 440 400 370 350 320 305 275 250 225 210
1 1/2 1.610 1,600 1,100 890 760 670 610 560 530 490 460 410 380 350 320
2 2.067 3,050 2,100 1,650 1,450 1,270 1,150 1,050 990 930 870 780 710 650 610
2 1/2 2.469 4,800 3,300 2,700 2,300 2,000 1,850 1,700 1,600 1,500 1,400 1,250 1,130 1,050 980
3 3.068 8,500 5,900 4,700 4,100 3,600 3,250 3,000 2,800 2,600 2,500 2,200 2,000 1,850 1,700
4 4.026 17,500 12,000 9,700 8,300 7,400 6,800 6,200 5,800 5,400 5,100 4,500 4,100 3,800 3,500
LLeennggtthhooffPPiippee,,FFeeeett

10
11..LLIIGGHHTTIINNGGPPRROOCCEEDDUURREE--Lighting procedures are outlined on the label pictured below. This label is also located on the water heater near the thermostat.
NNOOTTIICCEE::TThheeGGaassVVaallvveessuupppplliieeddwwiitthhtthhiisswwaatteerrhheeaatteerrmmaayyvvaarryyffrroommtthheeoonneeppiiccttuurreeddoonntthheellaabbeellbbeellooww,,bbuutttthheeLLiigghhttiinnggIInnssttrruuccttiioonnss