RIEKER Flex H6EX-B User manual

Current 0..24mA
Voltage 0..10V
Digital RS485
Dual Axis
Up to 360º
Inclinometers for
Hazardous Locations
2021
Flex™ H6EX-B Installation Manual

H6EX-B Installation Manual
Rev B
Page 1 of 8
RIEKER INC • 34 MOUNT PLEASANT ROAD • ASTON • PA • 19014 • USA
610-500-2000
fax: 610-500-2002
support@riekerinc.com
www.riekerinc.com
The information and material presented may not be published, broadcast, rewritten, or redistributed without the expressed written consent of Rieker®Inc.
This document is an Ex Controlled Document and may not be modified without prior Notifying and Certifying Body approval.
©2020-2021 Rieker®All Rights Reserved.
FORM NUMBER: H6EX0011_10/20 UPDATED: 4/29/2021
Table of Contents
Table of Contents .................................................................................................. 1
List of Figures....................................................................................................... 1
Sensor Description ................................................................................................. 2
Hazardous Location Information ................................................................................. 2
Applicable Standards .............................................................................................. 3
Normal Locations ............................................................................................... 3
Hazardous Locations............................................................................................ 3
EMC ............................................................................................................... 3
H6EX-B Instructions for Safety ................................................................................... 4
Putting into Service............................................................................................. 4
Use ................................................................................................................ 4
Assembling and Dismantling ................................................................................... 4
Maintenance ..................................................................................................... 4
Installation and Mounting: ..................................................................................... 5
Adjustment ...................................................................................................... 6
Markings ............................................................................................................. 7
Revision History .................................................................................................... 8
List of Figures
FIGURE 2: H6EX-B DIMENSIONS AND MOUNTING (INCHES [MM]) ...................................................................................... 5
FIGURE 3: H6EX-B AXIS ORIENTATIONS.......................................................................................................................... 6
FIGURE 4: TOP SURFACE MARKINGS FOR MODEL AND HAZARDOUS LOCATION INFORMATION ................................................... 7
FIGURE 5: FRONT SURFACE MARKINGS FOR SERIAL NUMBER............................................................................................... 7
FIGURE 6: FACTORY CONFIGURED DEFAULTS LABEL ........................................................................................................... 7

H6EX-B Installation Manual
Rev B
Page 2 of 8
RIEKER INC • 34 MOUNT PLEASANT ROAD • ASTON • PA • 19014 • USA
610-500-2000
fax: 610-500-2002
support@riekerinc.com
www.riekerinc.com
The information and material presented may not be published, broadcast, rewritten, or redistributed without the expressed written consent of Rieker®Inc.
This document is an Ex Controlled Document and may not be modified without prior Notifying and Certifying Body approval.
©2020-2021 Rieker®All Rights Reserved.
FORM NUMBER: H6EX0011_10/20 UPDATED: 4/29/2021
Sensor Description
The H6EX-B sensor is an inclinometer that provides high accuracy, dual axis inclination over a range of ±180°
for Hazardous Locations. It is ATEX/IECEx & MET (US)/CSA approved for use in the following hazardous
locations:
•Class I & II, Division 2
•Zone 2 & 22.
The sensor incorporates MEMS accelerometers referenced to gravity with integrated temperature compensation
over the full operating range of -40° to +85°C for absolute accuracy. It has both digital (RS485) and analog
(current or voltage) output options available. Each output is linear with respect to the input angle directly.
The digital RS485 output uses two-wire, half duplex communication, along with a Rieker specific protocol. This
protocol can be used to measure the angle of both axes, as well as configure many of the parameters of the
sensor.
The H6EX-B provides two continuous, fully configurable, analog outputs. These outputs are individually settable
to current from 4mA to 20mA or voltage from 0V to 10V, are settable to any axis, and are factory or user
configurable to match any angle range and min/max analog values.
Hazardous Location Information
The H6EX-B is approved to:
US and Canada (Gas):
Class I, Division 2, Groups A, B, C, D T4
US and Canada (Dust):
Class II, Division 2, Groups F, G
Certificate Numbers:
ATEX/IECEx: SEV 18 ATEX 0217
IECEx SEV 18.0042
US/CAN: MET E114209
The H6EX-B sensor is suitable for all areas except mining where gas and dust are not likely to occur in normal
operation, but if so, will persist for a short period only. It is suitable for explosive gas Groups IIA to IIC & A to D
and dust IIIC & F to G, and has temperature group T4 for gas & T135°C for dust. It also has an extended
operating temperature range of -40°C to +85°C.
WARNING: If the equipment is used in a manner not specified by the manufacturer, the protection provided by
the equipment may be impaired.
AVERTISSEMENT: Si l’équipement est utilisé de façon non spécifiée par le fabricant, la protection assurée par
l’équipement peut être altérée.

H6EX-B Installation Manual
Rev B
Page 3 of 8
RIEKER INC • 34 MOUNT PLEASANT ROAD • ASTON • PA • 19014 • USA
610-500-2000
fax: 610-500-2002
support@riekerinc.com
www.riekerinc.com
The information and material presented may not be published, broadcast, rewritten, or redistributed without the expressed written consent of Rieker®Inc.
This document is an Ex Controlled Document and may not be modified without prior Notifying and Certifying Body approval.
©2020-2021 Rieker®All Rights Reserved.
FORM NUMBER: H6EX0011_10/20 UPDATED: 4/29/2021
Applicable Standards
Normal Locations
For use in ordinary/unclassified locations, model H6EX-B has been investigated in accordance with:
•UL/CSA 61010 -1 3rd ed.–Electrical Equipment for Measurement, Control, and Laboratory Use; Part 1
Hazardous Locations
For use in Class I Division 2, Class II Division 2, model H6EX-B has been investigated in accordance with:
•CSA C22.2 No. 213-17: Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III,
Divisions 1 and 2 Hazardous (Classified) Locations, 2017
•UL 121201: Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1
and 2 Hazardous (Classified) Locations, 2017
For use in Zone 2, model H6EX-B has been investigated in accordance with:
•IEC 60079-0:2017, Edition 7.0 (EN 60079-0:2018) –Explosive Atmospheres Part 0: General Requirements
•IEC 60079-7:2017, Edition 5.1 (EN 60079-7:2015/A1:2018) - Explosive Atmospheres Part 7: Equipment
protection by increased safety “e”
For use in Zone 22, model H6EX-B has been investigated in accordance with:
•IEC 60079-0:2017, Edition 7.0 (EN 60079-0:2018) –Explosive Atmospheres Part 0: General Requirements
•IEC 60079-31:2013, 2nd edition (EN 60079-31:2014) -Explosive Atmospheres Part 31: Equipment Dust
Ignition Protection by Enclosure “t”
EMC
•EN 61326-1:2013 –Electrical equipment for measurement, control and laboratory use —EMC
requirements
•47 CFR Ch. 1 –FCC Part 15 Class A –Radio Frequency Devices –Subpart B –Unintentional Radiators
•ICES-003 –Issue 6 January 2016 Class A –Interference-Causing Equipment Standard –Digital Apparatus

H6EX-B Installation Manual
Rev B
Page 4 of 8
RIEKER INC • 34 MOUNT PLEASANT ROAD • ASTON • PA • 19014 • USA
610-500-2000
fax: 610-500-2002
support@riekerinc.com
www.riekerinc.com
The information and material presented may not be published, broadcast, rewritten, or redistributed without the expressed written consent of Rieker®Inc.
This document is an Ex Controlled Document and may not be modified without prior Notifying and Certifying Body approval.
©2020-2021 Rieker®All Rights Reserved.
FORM NUMBER: H6EX0011_10/20 UPDATED: 4/29/2021
H6EX-B Instructions for Safety
Putting into Service
The H6EX-B may be powered by +12-24VDC. The connector wiring table is below:
TABLE 1: H6EX-B MALE 8-PIN INPUT CONNECTOR WIRING
PIN
FUNCTION
1
SUPPLY VOLTAGE +12..24VDC
2
POWER / SIGNAL COMMON
3
RS-485 D+
4
RS-485 D-
5
NO CONNECTION
6
ANALOG OUTPUT 1
7
ANALOG OUTPUT 2
8
NO CONNECTION
TABLE 2: CURRENT SENSE
Rsense is dependent upon supply voltage and cable/wire
resistance. Ensure the following equation is met:
𝑅𝑠𝑒𝑛𝑠𝑒 ≤𝑉
𝑠𝑢𝑝𝑝𝑙𝑦 − 2.5
0.020 − 𝑅𝑤𝑖𝑟𝑒
QUICK REFERENCE
SUPPLY VOLTAGE
SENSE RESISTOR
12V
200-350 OHMS
WARNING: EXPLOSION HAZARD. DO NOT CONNECT OR DISCONNECT WHEN ENERGIZED.
AVERTISSEMENT –RISQUE D’EXPLOSION. NE PAS BRANCHER NI DÉBRANCHER SOUS TENSION
Notes:
A. All grounding path connections should be secure, permanent, visible, and accessible. The grounding path
resistance from the farthest barrier to the grounding electrode should not exceed 1 ohm.
B. The installation must be in accordance with the National Electrical Code, NFPA 70, Articles 504 and 505,
Canadian Electrical Code C22.1 Section 18, and ANSI/ISA-RP12.06.01.
C. The H6EX-B Sensor’s Chassis Ground is NOT the same as the signal ground for the current output return.
The analog output return must be connected to the POWER/SIGNAL COMMON (pin 2).
Use
The sensor is designed to measure dual-axis inclination and output an analog and/or digital signal.
Assembling and Dismantling
The H6EX-B shall not be serviced, dismantled, or re-assembled by the user.
Maintenance
No maintenance is required.