
6
SECTION 3 GENERAL REQUIREMENTS (UK)
This appliance must be installed by a competent per-
son in accordance with the Gas Safety (Installation &
Use) Regulations.
3.1 RELATED DOCUMENTS
The installation of this boiler must be in accordance with
the relevant requirements of the Gas Safety (Installation
& Use) Regulations, the local building regulations, the
current I.E.E. wiring regulations, the bylaws of the local
water undertaking, the Building Standards (Scotland)
Regulation, and Building Standards (Northern Ireland)
Regulations.
It should be in accordance also with any relevant
requirements of the local authority and the relevant
recommendations of the following British Standard
Codes of Practice.
ATTENTION
The use of PPE (Personal Protective Equipment) such
as but not limited to gloves, mask, safety glasses, etc.
is strongly recommended whenever carrying out the
installation, repair, or maintenance of this appliance –
please pay particular attention to:
• Sharp edges that may be encountered when:- han-
dling or lifting the appliance, removing parts, etc.
during installation and maintenance.
• Airborne particles that may be released and/or
disturbed when cleaning or removing components
during maintenance.
• Water treatment chemicals that could have been
added to the system water may spill from the appli-
ance and or components during maintenance.
Please refer to an appropriate Health and Safety docu-
ment such as HSE L23 (UK) or S.I. 299 (Ireland), for
more detailed advice on safe working practices and
procedures.
3.2 LOCATION OF APPLIANCE
The appliance may be installed in any room or internal
space, although particular attention is drawn to the
requirements of the current I.E.E. wiring regulations,
and in Scotland, the electrical provisions of the Build-
ing Regulations, with respect to the installation of the
appliance in a room or internal space containing a
bath or shower.
When an appliance is installed in a room or internal
space containing a bath or shower, the appliance or
any control pertaining to it must not be within reach
of a person using the bath or shower.
The location chosen for the appliance must permit the
provision of a safe and satisfactory ue and termination.
The location must also permit an adequate air supply
for combustion purposes and an adequate space for
servicing and air circulation around the appliance.
Where the installation of the appliance will be in an
unusual location special procedures may be neces-
sary, BS 6798 gives detailed guidance on this aspect.
A compartment used to enclose the appliance must be
designed and constructed specically for this purpose.
An existing compartment/cupboard may be utilised
provided that it is modied to suit.
Details of essential features of compartment/cupboard
design including airing cupboard installations are given
in BS 6798. This appliance is not suitable for external
installation.
3.3 GAS SUPPLY
The gas meter – as supplied by the gas supplier – must
be checked to ensure that it is of adequate size to deal
with the maximum rated input of all the appliances that
it serves. Installation pipes must be tted in accord-
ance with BS 6891.
Pipe work from the meter to the appliance must be
of adequate size. Pipes of a smaller size than the ap-
pliance gas inlet connection must not be used. The
installation must be tested for soundness in accord-
ance with BS6891.
If the gas supply serves more than one appliance, it
must be ensured that an adequate supply is main-
tained to each appliance when they are in use at the
same time.
3.4 FLUE SYSTEM
The terminal should be located where the dispersal
of combustion products is not impeded and with due
regard for the damage and discoloration that may occur
to building products located nearby. The terminal must
not be located in a place where it is likely to cause a
nuisance (see g. 4).
In cold and/or humid weather, water vapour will con-
dense on leaving the terminal; the effect of such pluming
must be considered.
If installed less than 2m above a pavement or platform
to which people have access (including balconies or
at roofs) the terminal must be protected by a guard
of durable material. The guard must be tted centrally
over the terminal. Refer to BS 5440 Part 1, when the
terminal is 0.5 metres (or less) below plastic guttering
or 1 metre (or less) below painted eaves.
3.5 AIR SUPPLY
The following notes are intended for general guidance
only.
This appliance is a room-sealed, fan-ued boiler, con-
sequently it does not require a
Permanent air vent for combustion air supply.
When installed in a cupboard or compartment, ventila-
tion for cooling purposes is also not required.
3.6 WATER CIRCULATION
Detailed recommendations are given in BS 5449 Part
1 and BS 6798. The following notes are for general
guidance only.
3.6.1 PIPEWORK
It is recommended that copper tubing to BS 2871 Part
1 is used in conjunction with soldered capillary joints.
Where possible pipes should have a gradient to ensure
air is carried naturally to air release points and that
water ows naturally to drain cocks.
BS 5440 PART 1 FLUES
BS 5440 PART 2 FLUES & VENTILATION
BS 5449 PART 1 FORCED CIRCULATION HOT WATER SYSTEMS
BS 6798 INSTALLATION OF BOILERS OF RATED INPUT NOT EXCEEDING 60kW
BS 6891 LOW PRESSURE INSTALLATION PIPES