5
In a mulple temperature system ulizing a thermostac mixing valve or a third party motorized mixing control, a low
loss header plumbing kit (part number 804000061) must be used.
ATTENTION
How to decide if a low loss header plumbing kit is required or not for the E50C boiler?
The following instrucons will guide you through how to determine if the E50C boiler can be used for your applicaon
and then how to correctly pipe your system for use with the E50C boiler.
How to conrm your system is suitable for use for the E50C:
1) Is the system a single zone or mulple zone system?
Answer: The E50C boiler can be used for both types of systems.
2) If the system has mulple zones; can zone valves and/or circulators be used?
Answer: The E50C boiler (as shipped from the factory) should only be ulized in systems with zone
valves. Systems which ulize mulple zone circulators instead of zone valves must be coupled
to a Rinnai boiler that has a low loss header as standard equipment or a low loss header
plumbing kit part number: 804000061 must be purchased and connected to the E50C boiler.
The following models are supplied with a low loss header from the factory: E75C, E110C, Q85S,
Q130S, QP85, and QP130. Rinnai strongly recommends the use of full port ball valve type
zone valves to allow for the best performance of the boiler and system.
3) What is the pressure drop across the longest loop/zone in the system or what is the total pressure drop in the
single zone system?
Answer: See table 1 and/or gure 1 to determine if the boiler circulator has enough feet of head to
properly pump the enre system without the addion of a low loss header plumbing kit.
4) What type heat emiers can be ulized?
Answer: The E50C boiler can be ulized with some types of heat emiers without a low loss header
plumbing kit as long as the total system ow requirements and pressure drop requirements are
observed, which means no more than 4.5 gpm of ow and 4.6 feet of head (2.0psi) of pressure
drop through the longest loop in the system.
5) When doing a boiler replacement in a single zone with a system (loop) circulator how do you know if a low loss
header is needed?
Answer: The rst thing that should be done when installing the E50C boiler is to calculate the pressure
drop through the loop. Do not include the exisng pump in the pressure drop calculaon. If
the pressure drop in the loop is less than 4.6 feet of head, then the exisng pump should be
removed and the boiler can be piped directly to the system. If the pressure drop is greater
than 4.6 feet of head, then a low loss header plumbing kit should be installed in between the
boiler and the system pump as shown in drawing number 7.
If the E50C boiler is installed in a system with zone valves and the constant recirculaon funcon is acvated, then a
dierenal pressure bypass valve or a low loss header plumbing kit is required to be installed.
Frequently Asked Quesons
When installing the E50C boiler in systems with dissimilar metals, Rinnai strongly recommends the use of dielectric
unions in between the boiler and the system.
ATTENTION