Rishabh RISH LM 1340 User manual

RISH LM 1340
Operating Manual


Installation & Operating Instructions
DIGITAL MULTIFUNCTION INSTRUMENT
Section Contents
1. Introduction
2. Measurement and Energy/Counter Screens
2.1 Current Reversal Screen
Phase Rotation Error Screen 2.2
2.3 Phase Absent Screen
2.4 Individual Harmonics
2.5 Load Health Monitor Screen
2.5.1 Load Health Monitor Fault Screens
2.6 Pre-Paid Energy Menu
2.7 Timer 1 & Timer 2 Screens
2.8 Run Hour
2.9 Hour On
2.10 Interruption Number of
3. Programming
3.1 Password Protection
3.2 Menu Selection
3.2.1 System Parameter Selection
3.2.1.1 System Type
3.2.1.2 Potential Transformer Primary Value
3.2.1.3 Potential Transformer Secondary Value
3.2.1.4 Current Transformer Primary Value
3.2.1.5 Current Transformer Secondary Value
3.2.1.6 System Frequency
3.2.1.7 Demand Integration Time
3.2.1.8 Auto Scrolling
3.2.1.9 Low Current Noise Cutoff
3.2.1.10 No. of Poles
3.2.1.11 Energy Output
3.2.1.12 Energy Digit Reset Count
3.2.1.13 Energy Rate
3.2.1.14 Impulse Rate
3.2.1.15 Version Information
3.2.1.16 Quit System Parameters DMAN-00IM-0922 Rev.B - 04/2022
1

3.2.2 Communication Parameter Selection
3.2.2.1 Address Setting
3.2.2.2 RS 485 Baud Rate
3.2.2.3 RS 485 Parity
3.2.2.4 Quit Communication Parameters
3.2.3 IP Parameter Selection
3.2.3.1 IP Address Setting
3.2.3.2 Subnet mask Setting
3.2.3.3 Default gateway Setting
3.2.3.4 Server Port Setting
3.2.3.5 Quit IP Parameters
3.2.4 Reset Parameter Selection
3.2.4.1 Resetting Parameter
3.2.5 Output Option Selection
3.2.5.1 Relay Selection
3.2.5.1.1 Relay 1 or 2 Output Selection Menu
3.2.5.1.1.0 None Ouput
3.2.5.1.1.1 Pulse Output
3.2.5.1.1.1.1 Parameter Selection
3.2.5.1.1.1.2 Pulse Duration
3.2.5.1.1.1.3 Pulse Rate
3.2.5.1.1.1.4 Quit Pulse Output
3.2.5.1.1.2 Limit Output
3.2.5.1.1.2.1 Limit Output Parameters
3.2.5.1.1.2.2 Alarm Configuration
3.2.5.1.1.2.3 Trip Point
3.2.5.1.1.2.4 Hysterisis
3.2.5.1.1.2.5 Energy Trip Point
3.2.5.1.1.2.6 Logic Operation Selection
3.2.5.1.1.2.7 Relay Configuration
3.2.5.1.1.2.8 Limit Output ON Delay
3.2.5.1.1.2.9 Limit Output OFF Delay
3.2.5.1.1.2.10 Quit Limit Output
3.2.5.1.1.3 Timer
3.2.5.1.1.3.1 Number of Cycles
3.2.5.1.1.3.2 Timer Configuration
3.2.5.1.1.3.3 On Delay
3.2.5.1.1.3.4 Off Delay
2

3.2.5.1.1.3.5 Quit Timer Output
3.2.5.1.1.4 Health Monitor Output
3.2.5.1.1.4.1 Health Monitor Configuration
3.2.5.1.1.5 Pre Paid Energy Output
3.2.5.1.1.5.1 Parameter Selection
3.2.5.1.1.5.2 Unit Cost
3.2.5.1.1.5.3 Topup Recharge
3.2.5.1.1.5.4 New Recharge
3.2.5.1.1.5.5 Quit Pre Paid Energy Output
3.2.6 Health Monitor Parameters Selection
3.2.6.1 Unbalance Voltage Limit
3.2.6.2 Unbalance Current Limit
3.2.6.3 Under Frequency Limit
3.2.6.4 Under Voltage Limit
3.2.6.5 Over Voltage Limit
3.2.6.6 Over Current Limit
3.2.6.7 Quit Health Monitor
3.2.7 Digital Input Parameter
3.2.7.1 De-Bounce Time
3.2.7.2 Digital Input 1 Mode Selection
3.2.7.3 Digital Input 1 Pulse Multiplier
3.2.7.4 Digital Input 2 Mode Selection
3.2.7.5 Digital Input 2 Pulse Multiplier
3.2.7.6 Quit Digital Input
3.2.8 Tariff Parameter
3.2.8.1 Number of Tariff Selection
3.2.8.2 Tariff Mode Selection
3.2.8.3 Tariff Energies Selection
3.2.8.4 Quit Tariff
3.2.9 Display Parameters
3.2.9.1 Feature Selection Menu
3.2.9.1.1 Backlit
3.2.9.1.2 User Assignable Screens
3.2.9.1.2.1 Screen Number Selection
3.2.9.1.2.2 User Screens Selection
3.2.9.1.2.3 Quit User Screens
3.2.9.1.3 Contrast
3

3.2.9.1.4 Display Test Screen
3.2.9.1.5 Quit Display Parameters
3.2.10 Factory Reset
3.2.10.1 Factory Reset Selection
3.2.11 Setup Quit
4. Energy Auto-Ranging On Display
4.1 Calculating Display energy (Auto-ranging)
4.2 Entering Energy start count
5. Relay Output
5.1 Pulse Output
5.2 Limit Switch
5.3 Timer Output
5.4 Health Monitor Output
5.5 Pre-Paid Energy Output
6. Phasor Diagram
7. Installation
7.1 EMC Installation Requirements
7.2 Case Dimensions and Panel Cut-out
7.3 Wiring
7.4 Auxiliary Supply
7.5 Fusing
7.6 Earth / Ground Connections
8. Connection Diagrams
9. Optional Pluggable Module
10. Specification
11. Connection for Optional Pulse Output / Digital Input / RS 485 / Ethernet Module
4

1. INTRODUCTION
The Multifunction Instrument is a panel mounted 96 x 96mm DIN Quadratic Digital Panel Meter, which measures
important electrical parameters in 3 ph 4 wire / 3 wire / 1ph Network and replaces the multiple analog panel meters.
It measures electrical parameters like AC voltage, Current, Frequency, Power, Energy (Active / Reactive /
Apparent), phase angle, power factor, individual harmonics & many more. The instrument integrates accurate
measurement technology (All Voltages & current measurements are True RMS upto 31st Harmonic) with LCD
display with backlit.
It can be configured & Programmed at site for the following : PT Primary, PT Secondary, CT Primary, CT
Secondary 3 Phase 3W, 3 Phase 4W, 1 Phase 2W system.
The front panel has four push buttons using which the user can scroll through different screens & configure the
product. The front panel also has Impulse red led, flashing at rate proportional to measured power.
Up Key / System Para Screens
Enter Key / Energy Para Screens
Down Key / Power Para Screens
Voltage / Current Para Screens
Energy/Counter Screen
Measurement Screen
Load Graphics
Impulse LED
5

The absence of lines indicating the percentage implies that the input current is less than 20% of the CT
Primary value.
Phase Sequence Indication
It indicates the rotation of input phasor vectors :
clockwise/ counter-clockwise.
In case the input is absent or the phase sequence is neither L123 nor L321, the phase sequence indication is not
shown.
2. MEASUREMENT AND ENERGY/COUNTER SCREENS
In normal operation, the user is presented with two simultaneous screens:
1. One of the Measurement screens out of the screens of Table 1.1 / 1.3 / 1.4 .
These screens may be scrolled through one at a time in an incremental order by pressing the respective key. Few
important screens are explained in Section 2.1 to 2.7.
2.One of the Energy/Counter screens out of the screens of Table 1.2.
These screens may be scrolled through one at a time in an incremental order only by pressing the “Enter key” to roll
over again in the same order. Few important screens are explained in Section 2.8 to 2.10
Load Graphics
Load Graphics indicates the input current as the percentage of the CT Primary value. This indication is available for
all measurement screens. For example, consider CT Primary to be set at 5A, then the input current of 2.5 A
indicates 50% as shown below.
Clockwise Sequence
for L123.
Counter-Clockwise Sequence,
for L321
XXXX
6

RS485 Connection Indication
Digital Input Indication
Digital Output Indication
It indicates that the serial communication between the instrument a nd th e
computer / control / automation system is activated through the RS485 output of the instrument by
glowing continuously. In case the communication is not active, the indication is not shown.
DI1 is configured in Status Mode and is present.
DO1 is energized.
The Digital Input (DI) symbols indicate the following :
These symbols indicate the following :
Tariff Energies Indication
This Instrument comes with 2 tariff based on Digital Input 1 (DI1) for 6
selectable energies each. In the image given here, it indicates that the
instrument is currently displaying the selected energy parameter (System
Import Active Energy) of Tariff 2. Refer TABLE 1.2 for navigation of Tariff
Energies. These energies are available in Energy Parameter Screens on
display.
XXXXXXXX
1. Status of external contacts when DI is configured in Status Mode.
DI1 is configured in Status Mode and is absent.
DI2 is configured for measurement of external pulses.
2. DI is configured for Pulse Mode.
1. Status of the output contacts (Relay).
DO1 is de-energized.
DO1 is configured for Pulse Output.
2. Relay is selected in Pulse Mode.
7

TABLE 1 : Measurement & Energy/Counter Screens
No. Parameters On Display On Modbus
3P 4W 3P 3W 1P 2W 3P 4W 3P 3W 1P 2W
System Voltage/ Current/ Active Power
System VA-VAr-Watt
System VA-VAr-Power Factor
System VA-VAr-Degree
System RPM - Frequency
System %THD Voltage-Current
System VA-A Demand
System Capacitive-Inductive VAr Demand
System Import-Export Watt Demand
System Max VA-A Demand
System Max Capacitive-Inductive VAr Demand
System Max Import-Export Watt Demand
System Max Voltage-Current-Power
System Min Voltage-Current-Power
System Max VA-VAr-Watt Power
System Min VA-VAr-Watt Power
System Max VA-VAr-Power Factor
System Min VA-VAr-Power Factor
System Max VA-VAr-Degree
System Min VA-VAr-Degree
System Max Voltage-Current-Frequency
System Min Voltage-Current-Frequency
Timer 1 No. of Cycles-ON Delay-OFF Delay
Timer 2 No. of Cycles-ON Delay-OFF Delay
Health Monitor Menu
Pre Paid Energy Menu
System Displacement Power Factor
System Reactive Power Factor
System LF Factor SgnQ(1-(P/S))
Old Sys Max Import-Export Watt Demand
Old Sys Max Capacitive-Inductive VAr Demand
Old Sys Max VA-A Demand
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Table 1.1 System Parameters Screens :
Parameter
8

Parameter
No. Parameters On Display On Modbus
3P 4W 3P 3W 1P 2W 3P 4W 3P 3W 1P 2W
System Voltage Unbalance
System Current Unbalance
System Distortion VAr
System Fundamental Var
System Max Reactive PF
System Min Reactive PF
System Max LF Factor SgnQ(1-(P/S))
System Min LF Factor SgnQ(1-(P/S))
33
34
35
36
37
38
39
40
Table 1.1 System Parameters Screens Continued...
NOTE : The Display screens of Table 1.1 can be scrolled through Up Key.
Parameter
No. Parameters On Display On Modbus
3P 4W 3P 3W 1P 2W 3P 4W 3P 3W 1P 2W
System Active Energy Import(Overflow)
System Active Energy Import
System Active Energy Export(Overflow)
System Active Energy Export
System Reactive Capacitive energy (Overflow)
System Reactive Capacitive energy
System Reactive Inductive energy (Overflow)
System Reactive Inductive energy
System Apparent energy(Overflow)
System Apparent energy
L1-L2-L3 Active Energy Import(Overflow)
L1-L2-L3 Active Energy Import
L1-L2-L3 Active Energy Export(Overflow)
L1-L2-L3 Active Energy Export
L1-L2-L3 Reactive Capacitive energy (Overflow)
L1-L2-L3 Reactive Capacitive energy
L1-L2-L3 Reactive Inductive energy (Overflow)
L1-L2-L3 Reactive Inductive energy
L1-L2-L3 Apparent energy(Overflow)
L1-L2-L3 Apparent energy
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Table 1.2 Energy Parameters Screens :
9

Parameter
No. Parameters On Display On Modbus
3P 4W 3P 3W 1P 2W 3P 4W 3P 3W 1P 2W
Run hour
On hour
No. of interrupts
Sys Total Active Energy Overflow Count
Sys Total Active Energy
Sys Total Reactive Energy Overflow Count
Sys Total Reactive Energy
L1-L2-L3 Total Active Energy Overflow Count
L1-L2-L3 Total Active Energy
L1-L2-L3 Total Reactive Energy Overflow Count
L1-L2-L3 Total Reactive Energy
Tariff 1 Energy 1
Tariff 1 Energy 2
Tariff 1 Energy 3
Tariff 1 Energy 4
Tariff 1 Energy 5
Tariff 1 Energy 6
Tariff 2 Energy 1
Tariff 2 Energy 2
Tariff 2 Energy 3
Tariff 2 Energy 4
Tariff 2 Energy 5
Tariff 2 Energy 6
Old Energy Unit
Old System Active Energy Import(Overflow)
Old System Active Energy Import
Old System Active Energy Export(Overflow)
Old System Active Energy Export
Old System Reactive Capacitive energy (Overflow)
Old System Reactive Capacitive energy
Old System Reactive Inductive energy (Overflow)
Old System Reactive Inductive energy
Old System Apparent energy(Overflow)
Old System Apparent energy
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
Table 1.2 Energy Parameters Screens Continued...
10

Old L1-L2-L3 Active Energy Import(Overflow)
Old L1-L2-L3 Active Energy Import
Old L1-L2-L3 Active Energy Export(Overflow)
Old L1-L2-L3 Active Energy Export
Old L1-L2-L3 Reactive Capacitive energy (Overflow)
Old L1-L2-L3 Reactive Capacitive energy
Old L1-L2-L3 Reactive Inductive energy (Overflow)
Old L1-L2-L3 Reactive Inductive energy
Old L1-L2-L3 Apparent energy(Overflow)
Old L1-L2-L3 Apparent energy
Old Sys Total Active Energy Overflow Count
Old Sys Total Active Energy
Old Sys Total Reactive Energy Overflow Count
Old Sys Total Reactive Energy
Old L1-L2-L3 Total Active Energy Overflow Count
Old L1-L2-L3 Total Active Energy
Old L1-L2-L3 Total Reactive Energy Overflow Count
Old L1-L2-L3 Total Reactive Energy
Old Run Hour
Old On Hour
Old no. of interrupts
Digital Input 1 Pulse Counter
Digital Input 2 Pulse Counter
Digital Input 1 Pulse Counter Overflow Count
Digital Input 2 Pulse Counter Overflow Count
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
Parameter
No. Parameters On Display On Modbus
3P 4W 3P 3W 1P 2W 3P 4W 3P 3W 1P 2W
NOTE : 1) The Display screens of Table 1.2 can be scrolled through Enter Key.
2) Energy on Display is Auto-Ranging For details refer Section 4.1.
Table 1.2 Energy Parameters Screens Continued...
11

NOTE : The Display screens of Table 1.3 can be scrolled through Down Key.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
L1 VA-VAr-Watt
L2 VA-VAr-Watt
L3 VA-VAr-Watt
L1-L2-L3 Power Factor
L1-L2-L3 Degree
System VA-VAr-Watt
System VA-VAr-PF
L1 Max VA-VAr-Watt
L1 Min VA-VAr-Watt
L2 Max VA-VAr-Watt
L2 Min VA-VAr-Watt
L3 Max VA-VAr-Watt
L3 Min VA-VAr-Watt
L1-L2-L3 Max Power Factor
L1-L2-L3 Min Power Factor
L1-L2-L3 Max Degree
L1-L2-L3 Min Degree
L1-L2-L3 Displacement Power Factor
L1-L2-L3 Reactive Power Factor
L1-L2-L3 LF Factor SgnQ(1-(P/S))
L1-L2-L3 Distortion VAr
L1-L2-L3 Fundamental VAr
L1-L2-L3 Max Reactive Power Factor
L1-L2-L3 Min Reactive Power Factor
L1-L2-L3 Max LF Factor SgnQ(1-(P/S))
L1-L2-L3 Min LF Factor SgnQ(1-(P/S))
On Display On Modbus
3P 4W 3P 3W 1P 2W 3P 4W 3P 3W 1P 2W
Table 1.3 Power Parameters Screens :
Parameter
No. Parameters
12

13
Table 1.4 Voltage/Current Parameters Screens :
Parameter
No. Parameters On Display On Modbus
3P 4W 3P 3W 1P 2W 3P 4W 3P 3W 1P 2W
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
L1-L2-L3 Voltage
L12-L23-L31 Voltage
L1-L2-L3 Current
Neutral Current
L1-L2-L3 Voltage %THD
L1-L2-L3 Current %THD
Current Reversal
Phase Rotation Error
Phase Absent Indication
System Voltage-Current-Frequency
L1-L2-L3 Max Voltage
L1-L2-L3 Min Voltage
L12-L23-L31 Max Voltage
L12-L23-L31 Min Voltage
L1-L2-L3 Max Current
L1-L2-L3 Min Current
Individual Harmonics V (upto 31st)
Individual Harmonics A (upto 31st)
NOTE : The Display screens of Table 1.4 can be scrolled through V/A Key.

2.1 Current Reversal Screen
This screen is one of the Voltage / Current Parameter Screens and is useful to indicate if current in any phase
is reversed or not. If current in any phase gets reversed, then corresponding phase will be indicated on this
screen.
This screen shows that currents in
L1 and L3 are reversed.
This screen shows that currents
in all three phase are correct.
This screen shows that the meter
has no current input.
2.2 Phase Rotation Error Screen
This screen is one of the Voltage / Current Parameter Screens and shows phase rotation information for the
phase sequence R-Y-B (L1-L2-L3).
This screen indicates that
Phase Sequence is
incorrect.
This screen indicates that
Phase Sequence is correct.
This screen indicates that all
three phases (voltages) are
absent.
User must check this screen in order to get correct readings when meter is connected.
This screen indicates that
either one or two of the
three phases (voltages)
are absent.
XXXX
XXXX XXXX
XXXX
XXXX
XXXX
XXXX
14

2.3 Phase Absent Screen
This screen is one of the Voltage / Current Parameter Screens and is useful to indicate if voltage or current in
any phase is absent. Hence, user will know which voltage or current is missing and take corrective action.
This screen indicates that all three
phases (V & I) are absent.
This screen indicates that V2,
I2 and I3 are absent.
This screen indicates that all
three phases are present i.e.
all inputs are present.
2.4 Individual Harmonics
XXXX XXXX XXXX
XXXX XXXX
2.5 Load Health Monitor Screen
The Individual Harmonics can be accessed by
pressing the Enter key followed by the Up and
Down keys taking through the 31 harmonics.
Similarly, pressing the “ ” key at the quit screen
takes the user out of the Individual Harmonics Screen.
XXXX
The Load Health Monitor Menu is one of the System Parameter
Screens and shows the health status of the three phase load. The faults
can be monitored by pressing the Enter Key followed by the Up and
Down keys taking through all the different errors (if any) of the Three
Phase load. Types of Error shown :
1) Phase Fail 2) Unbalanced Voltage
3) Unbalanced Current 4) Phase Reversal
5) Under Frequency 6) Under Voltage
7) Over Current 8) Over Voltage
This screen is one of the Voltage / Current Parameter Screens.
15

This screen indicates that phase
fail fault is present.
This screen indicates that voltage
unbalanced fault is present.
This screen indicates that current
unbalanced fault is present.
XXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
This screen indicates that phase
reverse fault is present.
This screen indicates that under
frequency fault is present.
This screen indicates that under
voltage fault is present.
This screen indicates that over
current fault is present.
This screen indicates that over
voltage fault is present.
XXXX
By pressing the “ ” key at the
quit screen takes the user out
of the Load Health Monitor
Menu Screen.
XXXX
XXXX
2.5.1. Health Monitor Fault Screens
16

2.6 Pre Paid Energy Menu
XXXX
Pre Paid Menu shows Balance
energy & Balance cost for the
energy selected and can be
accessed by pressing the Enter
Key.
This Screen shows Balance
energy of the parameter
selected in the relay 1 output
pre-paid Energy mode.
This Screen shows the Balance
cost of the parameter selected
in the relay 1 output pre-paid
Energy mode.
XXXXXXXXXXXXXXXX
This Screen shows Balance
energy of the parameter
selected in the relay 2 output
pre-paid Energy mode.
This Screen shows the Balance
cost of the parameter selected
in the relay 2 output pre-paid
Energy mode.
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXX
XXXX
Pressing the “ ” key at the
quit screen takes the user out
of the Pre Paid Menu Screen.
This screen is one of the System Parameter Screens.
17

2.7 Timer 1 & Timer 2 Screens
Relay 1 in Timer mode
No. of Cycles = 10
ON Delay = 12 sec
OFF Delay = 5 sec
The screen shows the No. of Cycles, on delay, off delay of the corresponding relay in its timer mode. If the
relay is configured in timer mode, then the timer can be turned ON by long press (about 3sec) of Up key while
present in any of the measurement screens.
Similarly, the Relay can be turned OFF by long press (about 3sec) of Down key while present in any of the
measurement screens.
Relay 1 is not selected in Timer
Configuration.
This screen is shown when relay
is configured as timer by selecting
yes option timer1 can be started.
Timer showing Running when
it is started.
Timer showing Stopped when
not running.
This screen is shown when
timer is started by selecting yes
option timer1 can be stopped.
Relay 1 is not selected in
Timer Configuration.
XXXX XXXX
XXXX XXXX
XXXX XXXX
XXXX
XXXX
This screen is one of the System Parameter Screens.
18
Table of contents