Notice
(1) A place where there are mineral oils such as cutting oil.
(2) Places such as the seaside where the water has a lot of salt in the air.
(3) Corrosive gases such as sulfur gas, acidity, or alkalinity exist in hot spring areas.
(4) Where the supply voltage fluctuates seriously and there is a strong electromagnetic
wave.
(5) A place filled with oil, gas, and oils, such as the kitchen.
Foundation installation
The installation foundation of the unit can be made of concrete structure or steel
bracket, and the surface of the foundation is smooth (the foundation design is designed
according to the operation quality of the unit, refer to the technical energy reference table).
Rubber vibration absorber must be placed under the heat pump unit on the foundation, and
then fixed with bolts, adjust the unit installation to be horizontal, tilt < 2 degrees. There shall
be a condensate water outlet of the unit on the ground.
Selection of water tank
If the heat pump water heater was purchased without a water tank, please select the
water tank according to the following requirements. The heat pump water heater can be
equipped with an open water tank and a pressurized water tank.
a. Open water tank:
Water tank can afford the full water pressure.
For appliances having a capacity of more than 15L and which cannot be emptied
through a drain outlet installed in a water pipe, a discharge device shall be fitted with which
a tool can be used to enable them to work. (The discharge unit can be combined with the
pressure release unit)
This unit has the water level control output, no need to add the water level control
equipment.
b. Pressurized water tank:
If no pressure relief device is installed inside the water tank, the pressure relief device
must be installed on the waterway installation, and the parameter is set as 0.7MPa.
Water can flow out of the pressure relief unit's drain pipe, and the drain pipe should be
kept in contact with the atmosphere.
The pressure release device should be operated regularly to remove calcium
carbonate deposits and guarantee the device is not clogged.
The rated pressure of the closed heat pump water heater designed to be connected to
the water source should be at least 0.6MPa.
For appliances having a capacity of more than 15L and which cannot be emptied
through a drain outlet installed in a water pipe, a discharge device shall be fitted with which
a tool can be used to enable them to work. (The discharge unit can be combined with the
pressure release unit).
This unit is equipped with high, medium, and low water level automatic water
replenishment control functions. For the closed water tank, the output line of high, medium,
and low water level control should be short-connected.