RITE-HITE Revolution HVLS Fan User manual

Manual Part #: 54450031
Model: REVOLUTION, ROGUE
Publication: AMEN00064 2019-03-07
Revolution®HVLS Fan
Rogue®HVLS Fan
Installation/Service/Owner's Manual
This manual covers units shipped February 2019 to date.
Language: English (Hazards: English, French)
NOTICE TO USER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Required Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Fan Clearance, Air Intake. . . . . . . . . . . . . . . . . . . . . . . . .5
Step 1 – Mounting Preparation . . . . . . . . . . . . . . . . . . . . .6
Step 2 – Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Step 3 – Motor Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Step 4 – Safety Cables (INCLUDED WITH KIT). . . . . . . .10
Step 5 – Stabilization Cables (INCLUDED WITH KIT) . . . 11
Step 6 – Attach Blades . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Step 7 – Level Hub . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Step 8 – Fan Electrical Installation (TYPICAL) . . . . . . . .12
Step 9 – Control Box. . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Step 10 – Label Plate . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Step 11 – Motor Cover . . . . . . . . . . . . . . . . . . . . . . . . . .13
Fan Guarding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
ELECTRICAL
Motor Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Conduit Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Control Box Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
EMC Compliance (OPTIONAL) . . . . . . . . . . . . . . . . . . . .16
MAINTENANCE
Planned Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . .17
TROUBLESHOOTING
Run / Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
PARTS
Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Extension Tube Assemblies, Cables . . . . . . . . . . . . . . .21
Motor Cover, Motor Assembly . . . . . . . . . . . . . . . . . . . .22
Blades. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Hub. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Controls 2.0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Fan‑Commander 2.0
Required to operate the fan(s) (ordered separately).
Use Fan‑Commander 2.0 manual with this manual
for complete installation and operation instructions.

2 Publication: AMEN00064 2019‑03‑07
Revolution®HVLS Fan • Rogue®HVLS Fan Installation/Service/Owner's Manual Rite‑Hite®
NOTICE TO USER
READ AND SAVE THESE INSTRUCTIONS.
Thank you for purchasing a Rite‑Hite product.
The Revolution and Rogue Fans are high‑volume/low‑speed
(HV/LS) industrial fans that provide more consistent air
circulation and ventilation with better energy eciency than
traditional high-speed ceiling fans or industrial oor fans.
The English version of this manual shall prevail over any
error in, or conicting interpretation of, any translations.
Rite‑Hite reserves the right to substitute and/or modify
parts and drawings (electrical and architectural) from
those contained in this manual. Separate prints may be
included with the unit.
For best results, have this product serviced by an
authorized Rite‑Hite representative.
A Planned Maintenance Program (P.M.P.), customized
to your specic operation is available and recommended.
For a P.M.P., contact your local Rite‑Hite representative
or Rite‑Hite technical support at (U.S.) 888‑456‑3625
or 1‑414‑973‑3625, (S.A.) +55 21 99616 4421,
(E.U.) +49‑5693 98700.
The Rite‑Hite®products in this manual are covered by one or more of
the following U.S. patents: 7658232, 8622712, 8142156, D631536,
7726945 and may be covered by additional pending U.S. and foreign
patent applications.
Manufactured by Rite‑Hite Engineered Solutions Group, Inc.
FCC Compliance
NOTE:This equipment has been tested and found to comply with the
limits for a Class A digital device, pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area
is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
NOTE: Changes or modications not expressly approved by the party
responsible for compliance could void the user's authority to operate the
equipment.
Contains FCC ID: MCQ‑XB900HP
Contains IC: 1846A‑XB900HP
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, including
interference that may cause undesirable operation.
SAFETY
Safety Identifications
!DANGER
Indicates a hazardous situation which, if not
avoided, will result in death or serious injury.
Indique une situation dangereuse qui, si elle n’est
pas évitée, peut entraîner la mort ou de graves
blessures.
WARNING / AVERTISSEMENT
Indicates a hazardous situation which, if not
avoided, could result in death or serious injury.
Indique une situation dangereuse qui, si elle n’est
pas évitée, peut entraîner la mort ou des blessures
graves.
!CAUTION / ATTENTION
Indicates a hazardous situation which, if not
avoided, could result in minor or moderate injury.
Indique une situation dangereuse qui, si elle n’est
pas évitée, peut entraîner des blessures légères à
modérées.
NOTICE
Indicates a situation which can cause damage to the
equipment, personal property and/or the environment,
or cause the equipment to operate improperly.
NOTE:A note is used to inform you of important
installation, operation, or maintenance information.

Publication: AMEN00064 2019‑03‑07 3
Rite‑Hite®Installation/Service/Owner’s Manual Revolution®HVLS Fan • Rogue®HVLS Fan
SAFETY
Lockout Procedure
Barricade work area and post safety warnings.
Power supply/control must:
• Be disconnected or locked in OFF
position using a lockout device approved
by local codes.
• Have signage that:
−Clearly states repairs are being made.
− Identies person responsible for lockout condition.
NOTE:Only this person should be able to remove
warnings and lockout device.
−Withstands environmental conditions (weather, wet,
and damp, etc.) and remains readable.
General
DANGER
Installation to be completed in accordance with the
National Electric Code, ANSI/NFPA 70‑1999, and
local codes.
L'installation doit être eectuée conformément au
Code national de l'électricité, à la norme ANSI/NFPA
70‑1999, et aux codes locaux.
DANGER
A qualied electrician should install the wiring in
accordance with local electrical codes.
Use lockout procedures to prevent death or severe
personal injury.
L'installation du câblage doit être eectuée par un
électricien qualié, conformément aux normes
électriques nationales et locales.
An de réduire le risque de blessures graves ou
mortelles, utilisez des procédures de verrouillage.
!CAUTION / ATTENTION
Barricade the work area until the unit(s) have
been completely installed.
Barricader la zone de travail jusqu'à ce que
l'unité(s) ont été complètement installé.
!WARNING / AVERTISSEMENT
Rotating fan blades can cause serious injury.
Les lames rotatif du ventilateur peut causer des
blessures graves.
170619

4 Publication: AMEN00064 2019‑03‑07
Revolution®HVLS Fan • Rogue®HVLS Fan Installation/Service/Owner's Manual Rite‑Hite®
INSTALLATION
Components
Before installation, verify all components were received.
Notify your Rite‑Hite representative if parts are missing
or damaged.
• 1 box: Motor, hub assembly, remote mounted control
switch and disconnect switches. ≈ 160lb [73kg]
• 1 box: Mounting hardware and cables. ≈ 50lb [23kg]
• 1 box: Control box. ≈ 35lb [16kg]
• Revolution Fan: 4 blades
• Rogue Fan: 2 blades
Required Tools
27/16in wrenches
(1 can be socket/driver)
21/2in wrenches
29/16in wrenches
23/4in wrenches
1 Vice grip
2Flat screwdrivers (large and small)
1Small standard screwdriver
1Medium Phillips screwdriver
1Torque wrench, minimum 200‑ft‑lb (270 Nm), 1/2in drive
11/2in to 3/4in socket adapter
11/2in socket extender
1Metric 7mm deep well socket – or Driver
11/4in cable cutter
4Crimp on ring terminals, M4 (#8) stud, for motor wiring
1Torpedo level
1Drill and 1/2in drill bit. If mounting to support angles that
span building joists
Specifications
Diameter (Ø) 8ft, 12ft, 16ft, 20ft and 24ft
[2440mm, 3660mm, 4880mm,
6100mm and 7320mm]
Blades Aluminum
Blade Finish Mill-nish standard,
custom colors optional
# of Blades 2 (Rogue) or 4 (Revolution)
Watts 75 (@ 10Hz) to 1750 (@ 60Hz) Typical
Frequency 50/60 Hz
Coverage Up to 22,000sq ft [2046m2] 85ft [26m] from the fan’s
center in all directions
Decibels 40 to 63 dBA depending on fan speed
(measured 20ft [6100mm] below and 20ft [6100mm]
from the fan’s center)
Air Speed Up to 7mph [3m/s] at full speed
Controls Variable speed
Mounting
Heights
10ft - 80ft [3m - 24m] from nished oor to bottom of
blade
Fan Ø RPM Weight
8ft [2440mm] 30‑150 268lb [122kg]
12ft [3660mm] 18‑96 276lb [125kg]
16ft [4880mm] 15‑74 284lb [129kg]
20ft [6100mm] 12‑59 292lb [132kg]
24ft [7320mm] 10‑52 300lb [136kg]
Revolution and Rogue
2 HP (1.5 kW)
Supply Voltage
200‑240V
1ɸ
200‑240V
3ɸ
400‑480V
3ɸ
Fan Input Current (Amps) 13 7 3.5
Control Box Fuse Rating
(Amps) 20 15 10
Minimum Service Amps 20 15 10
Maximum Number of Fans per Branch Circuit
Branch
Circuit
Amps
15 NA 1 3
20 1 2 4
25 1 2 5
30 1 3 6
35 2 4 8
40 2 4 9

Publication: AMEN00064 2019‑03‑07 5
Rite‑Hite®Installation/Service/Owner’s Manual Revolution®HVLS Fan • Rogue®HVLS Fan
INSTALLATION
Fan Clearance, Air Intake
Beam Kit Mounted
Fan Drop
Height
18
"
[460 mm]
Extra Air Intake
Height
B
A
Shown: Beam mount
Roof Surface
Mounting Surface
Bottom of Beam Mounting Surface
!
18.00"
[460 mm]
Fan Drop
Height
Extra Air Intake
Height
B
A
Mounting Surface
Shown: Truss mount
!
Roof Surface
Roof surface
Mounting surface
Fan drop
height
18in
[460mm]
Bottom of beam mounting surface
C
A
B
Truss Kit Mounted
Fan Drop
Height
18
"
[460 mm]
Extra Air Intake
Height
B
A
Shown: Beam mount
Roof Surface
Mounting Surface
Bottom of Beam Mounting Surface
!
18.00"
[460 mm]
Fan Drop
Height
Extra Air Intake
Height
B
A
Mounting Surface
Shown: Truss mount
!
Roof Surface
Mounting Surface
Fan drop
height
18in
[460mm]
C
Roof Surface
A
B
A = Mounting Surface to Obstruction Maximum
with 18in [460mm] Drop Tube
B = Blade Tip at Rest to Obstruction
Minimum
Beam Kit Truss Kit
Fan Drop Height = 56.5in [1440mm] Fan Drop Height = 48.00in
[1220mm]
Fan Ø Standard; Low Headroom Standard Low Headroom Standard Low Headroom
8ft [2440mm] 34in [870mm] 36in [920mm] 25in [640mm] 28in [40mm] 12in [310mm] 12in [310mm]
12ft [3660mm] 33in [840mm] 36in [920mm] 24in [610mm] 28in [37mm] 12in [310mm] 12in [310mm]
16ft [4880mm] 30in [770mm] 35in [890mm] 21in [540mm] 26in [41mm] 14in [360mm] 14in [360mm]
20ft [6100mm] 28in [720mm] 34in [870mm] 19in [490mm] 25in [10mm] 15in [390mm] 15in [390mm]
24ft [7320mm] 25in [640mm] 32in [820mm] 16in [410mm] 24in [39mm] 16in [410mm] 16in [410mm]
C = Extra Air Intake – Extra Height Above the Mounting Surface
Fan Ø
Beam Kit – Drop Tube Truss Kit – Drop Tube
No Drop Tube 18in [457mm] 30in [762mm] No Drop Tube 18in [457mm] 30in [762mm]
8ft [2440mm] None None None 2in [60mm] None None
12ft [3660mm] 5in [130mm] None None 16in [410mm] None None
16ft [4880mm] 20in [510mm] 7in [180mm] None 30in [770mm] 14in [360mm] 3in [80mm]
20ft [6100mm] 34in [870mm] 21in [540mm] 9in [230mm] 45in [1150mm] 27in [690mm] 17in [440mm]
24ft [7320mm] 49in [1250mm] 36in [920mm] 24in [610mm] 59in [1500mm] 41in [1050mm] 32in [820mm]
NOTE:"Figure 1" is shown with standard headroom.
Figure 1

6 Publication: AMEN00064 2019‑03‑07
Revolution®HVLS Fan • Rogue®HVLS Fan Installation/Service/Owner's Manual Rite‑Hite®
INSTALLATION
Step 1 – Mounting Preparation
WARNING / AVERTISSEMENT
Mount directly to a structural framing member to
reduce risk of re, electric shock or injury.
Monter directement sur un membre de charpente
pour réduire les risques d’incendie,
d’électrocution ou de blessure.
NOTICE
For optimal/unrestricted air movement follow these
guidelines:
If the ceiling support structure is a;
• Open‑web design, take all hanging dimensions
from the underside of the ceiling.
• Solid beam or solid channel, take all measurements
from the bottom of the beam for the hanger dimension.
If the roof is pitched, this must be accounted for above
the tips of the blades.
Fan Weight and Torque
NOTICE
The weight of the fan that will be suspended from the
ceiling is ≈ 300lb [136.4kg] and will generate torque of
up to 300ft-lb [407Nm].
Step 2 – Mounting
I‑Beam (TYPICAL)
I-BEAM MOUNTING
(TYPICAL)
CEILING TRUSS MOUNTING
(OPTIONAL)
LAMINATED BEAM KIT
(OPTIONAL)
1. Mount fan directly to building support I‑beam
(6in – 13.5in [150mm – 350mm] wide) with provided
brackets.
2. Clamp the brackets around the beam using the holes
in the upper beam mounting bracket that are closest
to the edge of the beam.
NOTE:When the beam is larger than the bracket
(greater than 13.5in [350mm] wide), clamp the bracket
on 1 edge of the beam and drill holes through the
beam to bolt the other side securely. Use only Grade 8
hardware.
3. Use a level to ensure the extension tube is hanging
vertical.
Figure 2

Publication: AMEN00064 2019‑03‑07 7
Rite‑Hite®Installation/Service/Owner’s Manual Revolution®HVLS Fan • Rogue®HVLS Fan
Step 2 – Mounting Continued
Ceiling Truss Kit (OPTIONAL)
WARNING / AVERTISSEMENT
Always mount the fan to 2 joists. 1 joist will not
provide the rigidity and support necessary for the
fan during operation, and may cause the fan to fall
and cause injury.
Toujours monter le ventilateur sur deux solives.
Une seule solive n’apportera pas la rigidité et le
soutien nécessaire au ventilateur en marche ; cela
pourrait entrainer la chute du ventilateur et causer
des blessures.
I-BEAM MOUNTING
(TYPICAL)
CEILING TRUSS MOUNTING
(OPTIONAL)
LAMINATED BEAM KIT
(OPTIONAL)
B
B
A
C
D
A. Angles/Support
(3in x 3in x 1/4in [75mm x 75mm x 7mm] recommended)
B. Building Joists or Trusses
C. Extension tube
D. Brackets
1. Mount the angles to the building trusses/joists:
• So fan can be hung using standard I‑Beam mounting
bracket Figure 2 (page 6) with a gap between the
angles for the 3in x 3in [75mm x 75mm] drop tube.
• Securely so the angles cannot move.
2. Use a level to ensure the extension tube is hanging
vertical.
NOTE:
• I‑beam ceiling brackets are not provided when a
Ceiling Truss Kit is ordered.
• Several mounting positions have been cut into the
angles for exibility in positioning the fan.
Figure 3
INSTALLATION

8 Publication: AMEN00064 2019‑03‑07
Revolution®HVLS Fan • Rogue®HVLS Fan Installation/Service/Owner's Manual Rite‑Hite®
INSTALLATION
Step 2 – Mounting Continued
Laminated Beam Kit (OPTIONAL)
I-BEAM MOUNTING
(TYPICAL)
CEILING TRUSS MOUNTING
(OPTIONAL)
LAMINATED BEAM KIT
(OPTIONAL)
1. Through bolt the laminated beam brackets with 1
bracket on each side of the laminated (or concrete)
beam (Figure 4).
2. Attach the standard ceiling mounting bracket to this
bracket in the normal manner.
Alternative Methods
(4) 1/2X1-1/2 in. Grade 8
bolts & nuts (not provided).
TRUSS KIT SOLD SEPARATELY
Truss Kit
sold separately
(4) 1/2X1-1/2 in. Grade 8
bolts & nuts (not provided).
TRUSS KIT SOLD SEPARATELY
(4) 1/2in x 1‑1/2in
Grade 8 bolts and nuts
(supplied by others)
Figure 4 Figure 5
Figure 6

Publication: AMEN00064 2019‑03‑07 9
Rite‑Hite®Installation/Service/Owner’s Manual Revolution®HVLS Fan • Rogue®HVLS Fan
INSTALLATION
Step 3 – Motor Bracket
The motor bracket attaches to the extension tube with (2)
1/2in x 4‑1/2in Grade 8 bolts, washers, and locknuts.
1. Position the motor bracket so that 1 angle is on each
side of the extension tube.
2. Insert the bolts through the holes in the angles at the
top of the motor bracket and through the extension
tube and back through the second angle.
3. Tighten both locknuts securely.
When an extended down tube is used:
The smaller square tubing (3in x 3in [75mm x 75mm]) will
telescope inside the larger square tubing (3.5in x 3.5in
[90mm x 90mm]). The brackets on the top of the motor
bracket are bolted in slots to allow the larger tube to bolt
to the top of the motor. The 3in x 3in [75mm x 75mm] tube
should always bolt to the ceiling bracket.
When fan assembly is mounted directly to the ceiling
bracket (without an extension tube):
Use (4) 1/2in x 1‑1/2in Grade 8 bolts (supplied by others)
to attach the ceiling bracket.

10 Publication: AMEN00064 2019‑03‑07
Revolution®HVLS Fan • Rogue®HVLS Fan Installation/Service/Owner's Manual Rite‑Hite®
Step 4 – Safety Cables (INCLUDED WITH KIT)
WARNING / AVERTISSEMENT
Always use safety cables. They protect against a
fan fall in the event of a bolted joint loosening.
Toujours utiliser des câbles de sécurité. Ils
protègent contre la chute d’un ventilateur dans le
cas d’un relâchement de l’assemblage boulonné.
A
B
C
1. Wrap a safety cable around the bolted brackets at the
ceiling and through the top of the extension tube (A).
2. If installing with adjustable‑length extension tubes,
use a third safety cable to secure the center bolted
joint of the extension tubes (B).
3. Wrap a second safety cable through the bottom
of the extension tube and through the top of the
motor housing (C).
4. Secure the safety cables with the provided clamps.
Figure 7
INSTALLATION

Publication: AMEN00064 2019‑03‑07 11
Rite‑Hite®Installation/Service/Owner’s Manual Revolution®HVLS Fan • Rogue®HVLS Fan
INSTALLATION
Step 5 – Stabilization Cables (INCLUDED WITH KIT)
WARNING / AVERTISSEMENT
Always use stabilization cables. They protect the
fan from tilting and allowing the blades to impact
a ceiling joist or object.
Toujours utiliser des câbles de stabilisation. Ils
empêchent le ventilateur de basculer et ses pales
d’entrer en contact avec une solive du plafond ou
un objet.
Stabilization cables anchor the fan for situations like cross
winds or impacts that could tilt the fan, causing the blades
to impact a ceiling joist or other object. Use these cables
to attach the fan bracket to the ceiling.
1. For greatest support, attach the stabilization cables
to the ceiling at 90° to each other and as far away as
possible from the point where the fan is mounted.
2. Secure the stabilization cables to the ceiling with 2
cable clamps, and tighten with a turnbuckle.
3. Cut stabilization cable to length as required.
4. Ensure that stabilization cables are attached in a
position that does not allow the blades to hit the
stabilization cables when the fan is operating.
5. Tighten the turnbuckle 1 turn past hand‑tight.
6. Install stabilization cable clamp nuts away from
turnback.
Step 6 – Attach Blades
A
B
C
D
E
Clean each blade with a paper towel to remove
ngerprints and dirt before the blades are installed.
To attach each fan blade to the fan hub:
1. Use a step ladder or lift as required.
2. Raise the blade (A) above the arm of the hub (B) and
allow the slot of the blade to slide onto the hub (C).
3. Insert (provided) 1in bolt (D). Use a torque wrench
(E) with a 3/4in drive extension to tighten the bolt to
200 ft-lb. [271 Nm].
Step 7 – Level Hub
1. Hold a level across the center of the hub
(all directions).
2. Make fine adjustments with the (turnbuckle clamped)
stabilization cables.
3. Run / Test (page 17) the unit, then re‑adjust fan
level and cable tension.
Figure 8

12 Publication: AMEN00064 2019‑03‑07
Revolution®HVLS Fan • Rogue®HVLS Fan Installation/Service/Owner's Manual Rite‑Hite®
INSTALLATION
Step 8 – Fan Electrical Installation (TYPICAL)
Fan Control Box
(14in x 16in x 8in
VFD Enclosure)
Line Voltage
Line Voltage
Fan Motor
Disconnect
Incoming Power from
End User Supplied
Branch Circuit
Protective Device
Motor Voltage
160ft [50m] Max Motor Run
Fan Motor
3ɸ
B
A
A. Mount Fan Control Box (VFD Enclosure) at maintenance accessible height.
B. Mount disconnect at accessible height, according to local code.
Mount Fan Control Box (A) and disconnect (B) safely outside the fan diameter.
Field Wiring
Power/High Voltage
Incoming Power
Terminated at
F1, F2, F3
Fuse Holder.
Incoming Power from
End User Supplied
Branch Circuit
Fan Motor
Disconnect
Fan Control Box
To Fan Motor
Terminal Torque 20lb‑in Max
ACCEPTABLE:
Unshielded Stranded Conductor Types:
THHN/THWN in Metallic Conduit
Shielded Stranded Cable Types:
Belden 29501
AlphaWire V16014
Use copper wire only, minimum 600V 75°C
NOTE:
‑ If fan runs backwards
swap 2 motor wires.
- L3 not used on 1ɸ fans.
Copper conductors only
14‑8 AWG, 75°C min.
Control/Low Voltage
Radio PCB
Jumper Wire
DO NOT Remove
Optional
Temperature
Sensor
Enable Jumper:
Opening the factory installed jumper between
S1 and SC will cause the fan to initiate a
controlled stop. These points may be wired to
a contact from a re system or BMS to stop the
fans during an alarm or water ow event.
OUT
Patch cord
Blue
White
Yellow
Brown
Red
Grey
Orange
Black
Figure 9
Figure 10

Publication: AMEN00064 2019‑03‑07 13
Rite‑Hite®Installation/Service/Owner’s Manual Revolution®HVLS Fan • Rogue®HVLS Fan
INSTALLATION
Step 9 – Control Box
!CAUTION / ATTENTION
Mount control boxes outside of the fan diameter.
A control box mounted above a fan or inside the
fan diameter cannot be locked out safely.
Monter les boîtes de commande en dehors du
diamètre du ventilateur. Une boîte de commande
montée au‑dessus ou dans le champ du
ventilateur ne peut être verrouillée en toute
sécurité.
Mount the 17.6in x 16in x 8.4in [447mm x 406mm x 212mm]
control box:
• Securely to a wall or building column with appropriate
anchors (supplied by others).
• Within 160ft [50m] from the fan it is controlling. The fan
must be visible from the control box mounting location.
Step 10 – Label Plate
1. Attach the label plate mounting brackets to the bottom
of the fan hub:
a. Insert the 4 1/4‑20 x 1.0in bolts with lock washers
through the end with the round hole.
NOTE:Do not tighten completely until the label
plate is attached.
b. Align the bracket so the slotted hole faces outward,
toward the fan blade.
c. Repeat this process for the remaining 3 brackets.
2. Attach the label plate to the label plate brackets:
a. Insert the bolt up through the label plate and
through the label plate bracket.
NOTE:You may need to puncture a small hole
through the label with a sharp object to insert the bolt.
b. Install a 1/4‑20in Nylock nut on the bolt to secure it
in position.
c. Repeat this process to attach the label plate to the
remaining label plate brackets.
3. Tighten all the bolts holding the brackets and label
plate securely.
Step 11 – Motor Cover
Attach the motor cover over the motor bracket:
1. Insert 4 1/4‑20 x 1in bolts with locknut through the
motor cover and motor bracket.
2. Secure bolts with a Nylock nut on the inside.
3. Tighten all 4 bolts securely.
Fan Guarding
After installation, guard the fan when there is potential for
a person or object to contact moving fan blades.
Guarding (supplied by others) can be a:
• Structure near the edge of the blades to deter fork
trucks, objects or people from entering a danger area.
• Cage around the fan blades to protect moving fan
blades.
NOTE:Always mount cage(s) from the ceiling or
columns and independent of the fan.
Figure 11

14 Publication: AMEN00064 2019‑03‑07
Revolution®HVLS Fan • Rogue®HVLS Fan Installation/Service/Owner's Manual Rite‑Hite®
ELECTRICAL
Motor Wiring
U
V
W
GND
GND
U V W
U
V
W
GND
U
V
W
GND
U
V
W
GND
GND
GND
GND
GND GND
U
V
W
U
V
W
U
V
W
U
V
W
U V W
LENZE IE3 230V
WYE-WYE
SIEMENS 230V
WYE-WYE
LENZE IE2 230V
DELTA
NORD 230V
WYE-WYE
LENZE IE3 460V
WYE
SIEMENS
460V WYE
LENZE IE2 460V
WYE
NORD 460V
WYE
SIEMENS 575V
WYE
NORD 575V
WYE
<1002M170.SLDDRW.pdf>
NOTE:Use stranded
copper conductors only,
minimum 75 C. To maintain
4X rating, use only UL listed
4X ttings. Do not make
conduit connections through
the top of enclosure. To
reduce risk of electric shock,
an earth ground connection
must be eld installed to the
Green/Yellow control box
ground terminal.
The fan motor will receive three‑phase power from the fan
control box even if single‑phase power is provided to the
control box. Remove the cover from the motor junction
box. Change the wire leads as necessary for high or low
voltage (Figure 12).
NOTICE
Do Not use solid core wiring of any size or insulation
class for controller output/motor leads.
To connect the fan control box to the motor use these
(14AWG Minimum Gauge) acceptable
wire types:
Unshielded cable:
‑ THHN/THWN Minimum 600V 90°C
Shielded XLPE VFD cable:
‑ Belden 29501
‑ AlphaWire V16014
Conduit Restrictions
NOTICE
Power supply lines for a controller May share the
same conduit with Power supply lines for 1 or
more additional controllers.
Power supply lines for a controller and output/motor
leads for the same controller or another controller
May Not share the same conduit.
The conduit with the incoming power and the conduit
with the power going to the motor should be separated
by a minimum of 6in [150mm].
Figure 12

Publication: AMEN00064 2019‑03‑07 15
Rite‑Hite®Installation/Service/Owner’s Manual Revolution®HVLS Fan • Rogue®HVLS Fan
ELECTRICAL
Control Box Wiring
Fuse
Block
Fuse
Block
EMC
Filter
EMC
Filter
Motor
Motor
Motor
• All factory wiring 14 AWG AVLV2/8
• Power wiring to be black
• Ground conductors to be green/yellow
Motor conductors eld
terminated to VFD
terminals using M4 fork
connectors (provided),
torque to 1.5Nm.
NOTE:L3 wire and F3 fuse omitted for
230V single phase input option.
Motor conductors
eld terminated to
VFD terminals using
M4 fork connectors
(provided), torque to
1.5Nm.
Motor conductors
eld terminated to
VFD terminals using
M4 fork connectors
(provided), torque to
1.5Nm.
Standard 3ɸ / 1ɸ
Incoming Power Supply
EMC Option 3ɸ
Incoming Power Supply
EMC Option 1ɸ
Incoming Power Supply
VFD VFD
Figure 13

16 Publication: AMEN00064 2019‑03‑07
Revolution®HVLS Fan • Rogue®HVLS Fan Installation/Service/Owner's Manual Rite‑Hite®
ELECTRICAL
EMC Compliance (OPTIONAL)
The EMC Compliance Option includes an EMC lter on
the line side of the VFD.
To maintain IEC 61800‑3 C1 compliance, you must
observe the following installation guidelines:
• Ensure maximum physical separation between low
voltage control cables and high voltage power cables
(minimum 150mm or 6in).
• Ensure maximum physical separation between motor
cable and all other circuits (minimum 150mm or 6in).
• Use shielded, low capacitance VFD cable with XLPE
(Cross‑linked Polyethylene) insulation. Example
products:
−Belden 29501
−AlphaWire V16014
• Ground the motor cable shield at both ends of the
cable (VFD and motor).
• The total motor cable length must not exceed exceed
65ft [20m].

Publication: AMEN00064 2019‑03‑07 17
Rite‑Hite®Installation/Service/Owner’s Manual Revolution®HVLS Fan • Rogue®HVLS Fan
MAINTENANCE
WARNING / AVERTISSEMENT
Follow lockout procedures before cleaning or re‑torquing the fan.
Suivre les procédures de verrouillage avant le nettoyage ou le resserrage du ventilateur.
Planned Maintenance
PLANNED
MAINTENANCE TASK INSPECT AND PERFORM THE FOLLOWING:
Fan Mounting Re-torque all fasteners (1/2in Grade 8 [98ft-lb or 133Nm], 5/16in Grade 8 [29ft-lb or 39Nm]).
Inspect fan and mounting supports for wear and tear. Tighten any loose hardware.
Cables Re‑torque clamps.
Check for fraying or wear.
Gear Reducer Check for oil leaks. If leaks are present, contact factory.
Check oil level. Add oil if necessary (oil type is marked on the gear case).
Motor Check for dust and dirt. Remove using a brush or compressed air.
Fan Controller Inspect all terminal connections inside the VFD control box. Tighten any loose connections.
TROUBLESHOOTING
Run / Test
Turn the power disconnect switch on the control box to the
ON position. Allow a few seconds for the frequency drive
to power up.
Adjust the fan speed to 60 Hz. Count the number of
revolutions the fan makes in 1 minute. They should be:
24ft [7320mm] Fan ≈ 52 rpm
20ft [6100mm] Fan ≈ 59 rpm
16ft [4880mm] Fan ≈ 74 rpm
12ft [3660mm] Fan ≈ 96 rpm
8ft [2440mm] Fan ≈ 150 rpm
NOTE:If fan does not spin at these speeds,
consult your Rite‑Hite representative.

18 Publication: AMEN00064 2019‑03‑07
Revolution®HVLS Fan • Rogue®HVLS Fan Installation/Service/Owner's Manual Rite‑Hite®
TROUBLESHOOTING
Motor
WARNING / AVERTISSEMENT
Follow lockout procedures and isolate power from
fan controls.
Suivre les procédures de verrouillage et isoler
l’alimentation des contrôles du ventilateur.
Meter
Disconnect Motor Cable from Control Box
Ground Wire
U Phase
V Phase
W Phase
F
a
n
M
o
t
o
r
C
a
b
l
e
1. Disconnect fan motor cable from u, v, w, and ground
terminals (GND).
2. Using electrical meter, measure resistance (ohms, Ω)
between phase wand Phase V.
Record the 6 resistance values:
Phase W to V Ω Phase W to GND Ω
Phase W to U Ω Phase V to GND Ω
Phase V to U Ω Phase U to GND Ω
Phase to phase values should be equal. (±5%).
Phase to ground values should be innite.
(Open circuit ‑ meter display “OL”)
If phase‑phase values are not equal. Or, if
phase‑ground resistance is measured:
• Disconnect motor cable from motor.
• Repeat measurements at motor wiring terminals.
Motor Wobble
Verify:
Figure 14
• All hardware is tight.
• Stabilization Cables are taut.
• The motor bracket is installed vertically.

Publication: AMEN00064 2019‑03‑07 19
Rite‑Hite®Installation/Service/Owner’s Manual Revolution®HVLS Fan • Rogue®HVLS Fan

20 Publication: AMEN00064 2019‑03‑07
Revolution®HVLS Fan • Rogue®HVLS Fan Installation/Service/Owner's Manual Rite‑Hite®
PARTS
Mounting
Swivel Bracket
4
3
2
1
4
3
5
SWVL BRKT
14501306 BRKT,ASSY,SWVL,HOUSING,FAN,GY
ITEM
QTY
DESCRIPTION
1 2
SCR,HHMS,1/2-13X4-1/2,GR8,ZNC
2 2
BRKT,MNT,HOUSING,SWVL,FAN,GY
3 12
WSHR,FLAT,1/2X1-3/8X7/64,ZNC
4 6
NUT,HEX,NYL LOCK,1/2-13,GR8,Z
5 4
SCR,HHMS,1/2-13X2,GRD8,ZNC
# QTY DESCRIPTION PART #
– 1 BRKT,ASSY,SWVL,HOUSING,FAN,GY 14501306
1 2 SCR,HHMS,1/2‑13X4‑1/2,GR8,ZNC –
2 2 BRKT,MNT,HOUSING,SWVL,FAN,GY –
3 12 WSHR,FLAT,1/2X1‑3/8X7/64,ZNC –
4 6 NUT,HEX,NYL LOCK,1/2‑13,GR8,Z –
5 4 SCR,HHMS,1/2‑13X2,GRD8,ZNC –
I‑Beam Kit
17
18
19
20
16
15
21
CEILING BRKT
14501233 BRKT,ASSY,SWVL,CLNG,FAN,GY
ITEM
QTY
DESCRIPTION
15 1
BRKT,WLDMNT,SWVL,FAN,GY
16 1
LABEL,DECAL,INSTL,SUPPORT,FAN
17 4
NUT,HEX,NYL LOCK,1/2-13,GR8,Z
18 8
WSHR,FLAT,1/2X1-3/8X7/64,ZNC
19 2
PLATE,CLAMP,MNT,FAN,GY
20 2
PLATE,SHIM,MNT,FAN,GY
21 4
SCR,HHMS,1/2-13X2,GRD8,ZNC
# QTY DESCRIPTION PART #
– 1 BRKT,ASSY,SWVL,CLNG,FAN,GY 14501233
15 1 BRKT,WLDMNT,SWVL,FAN,GY –
16 1 LABEL,DECAL,INSTL,SUPPORT,FAN –
17 4 NUT,HEX,NYL LOCK,1/2‑13,GR8,Z –
18 8 WSHR,FLAT,1/2X1‑3/8X7/64,ZNC –
19 2 PLATE,CLAMP,MNT,FAN,GY –
20 2 PLATE,SHIM,MNT,FAN,GY –
21 4 SCR,HHMS,1/2‑13X2,GRD8,ZNC –
Truss Kit
6
7
8
9
11
12
10
13 14
TRUSS KIT
55290016 MOUNT,ASSY,TRUSS,FAN,GY
ITEM
QTY
DESCRIPTION
6 2
BRKT,MNT,TRUSS,FAN,GY
7 1
LABEL,DECAL,INSTL,SUPPORT,FAN
8 2
BRKT,CLAMP,TRUSS,FAN,GY
9 2
PLATE,CLAMP,TRUSS,FAN,GY
10 2
ROD,THRD,1/2-13X10",FLTD,STNLS
11 4
WSHR,FLAT,1/2X1-3/8X7/64,ZNC
12 4
NUT,HEX,NYL LOCK,1/2-13,GR8,Z
13 2
CABLE,AIRCRAFT,GLV,1/4,84"
14 4
CLAMP,CABLE,ZINC,1/4,SNGL SAD
6
7
8
9
11
12
10
13 14
TRUSS KIT
55290016 MOUNT,ASSY,TRUSS,FAN,GY
ITEM
QTY
DESCRIPTION
6 2
BRKT,MNT,TRUSS,FAN,GY
7 1
LABEL,DECAL,INSTL,SUPPORT,FAN
8 2
BRKT,CLAMP,TRUSS,FAN,GY
9 2
PLATE,CLAMP,TRUSS,FAN,GY
10 2
ROD,THRD,1/2-13X10",FLTD,STNLS
11 4
WSHR,FLAT,1/2X1-3/8X7/64,ZNC
12 4
NUT,HEX,NYL LOCK,1/2-13,GR8,Z
13 2
CABLE,AIRCRAFT,GLV,1/4,84"
14 4
CLAMP,CABLE,ZINC,1/4,SNGL SAD
6
7
8
9
11
12
10
13 14
TRUSS KIT
55290016 MOUNT,ASSY,TRUSS,FAN,GY
ITEM
QTY
DESCRIPTION
6 2
BRKT,MNT,TRUSS,FAN,GY
7 1
LABEL,DECAL,INSTL,SUPPORT,FAN
8 2
BRKT,CLAMP,TRUSS,FAN,GY
9 2
PLATE,CLAMP,TRUSS,FAN,GY
10 2
ROD,THRD,1/2-13X10",FLTD,STNLS
11 4
WSHR,FLAT,1/2X1-3/8X7/64,ZNC
12 4
NUT,HEX,NYL LOCK,1/2-13,GR8,Z
13 2
CABLE,AIRCRAFT,GLV,1/4,84"
14 4
CLAMP,CABLE,ZINC,1/4,SNGL SAD
# QTY DESCRIPTION PART #
– – MOUNT,ASSY,TRUSS,FAN,GY 55290016
6 2 BRKT,MNT,TRUSS,FAN,GY –
7 1 LABEL,DECAL,INSTL,SUPPORT,FAN –
8 2 BRKT,CLAMP,TRUSS,FAN,GY –
9 2 PLATE,CLAMP,TRUSS,FAN,GY –
10 2 ROD,THRD,1/2‑13X10",FLTD,STNLS –
11 4 WSHR,FLAT,1/2X1‑3/8X7/64,ZNC –
12 4 NUT,HEX,NYL LOCK,1/2‑13,GR8,Z –
13 2 CABLE,AIRCRAFT,GLV,1/4,84" –
14 4 CLAMP,CABLE,ZINC,1/4,SNGL SAD –
Laminated Beam Kit
25
23
24
BEAM
23
22
26
BEAM KIT
14501239 BRKT,ASSY,MNT,LAM BEAM,FAN,GY
ITEM
QTY
DESCRIPTION
22 3
SCR,HHMS,1/2-13X8,GRD8,ZNC
23 6
WSHR,FLAT,1/2X1-3/8X7/64,ZNC
24 2
BRKT,MNT,LMNTD BEAM,FAN,GY
25 3
NUT,HEX,NYL LOCK,1/2-13,GR8,Z
26 1
LABEL,DECAL,INSTL,SUPPORT,FAN
# QTY DESCRIPTION PART #
– 1 BRKT,ASSY,MNT,LAM BEAM,FAN,GY 14501239
22 3 SCR,HHMS,1/2‑13X8,GRD8,ZNC –
23 6 WSHR,FLAT,1/2X1‑3/8X7/64,ZNC –
24 2 BRKT,MNT,LMNTD BEAM,FAN,GY –
25 3 NUT,HEX,NYL LOCK,1/2‑13,GR8,Z –
26 1 LABEL,DECAL,INSTL,SUPPORT,FAN –
This manual suits for next models
1
Table of contents
Other RITE-HITE Fan manuals
Popular Fan manuals by other brands

Johnson
Johnson Alhambra Instructions for use

Monte Carlo Fan Company
Monte Carlo Fan Company 4VOR60XXD Series user guide

Westinghouse
Westinghouse WSFT1201M instruction manual

Dr.Prepare
Dr.Prepare DCCFA1 quick start guide

Hunter
Hunter 21704 Parts guide

STG-BEIKIRCH
STG-BEIKIRCH M3 Series Technical information and operating instruction