Specifications
2SRV_01E
Input
Performance
Control
Number of inputs
2 points (V-TIO-A/B)
1 point (V-TIO-C/D)
•
2 points type : Isolated between each channel
(Only thermocouple)
Input
a) Thermocouple, DC low voltage group
Thermocouple : K, J, R, S, B, E, T, N (JIS/IEC),
PLII (NBS), W5Re/W26Re (ASTM)
•Input impedance : Approx. 1MΩ
•Influence of external resistance : Approx.0.15µV/Ω
•Input break action : Up-scale
DC Low voltage : 0-100mV DC
•Input break action : Up-scale
b) RTD group
Pt100 (JIS/IEC), JPt100 (JIS)
•Maximum 10Ωper wire
•Input break action : Up-scale
c) DC High voltage, DC current group
DC High voltage : 0 to 5V DC, 1 to 5V DC, 0 to 10V DC
•Input break action :Value around 0V
DC current : 0 to 20mA DC, 4 to 20mA DC
•Input impedance : 250Ω
•Input break action :Value around 0V
SamplingTime
0.5 sec
PV Bias
-span to +span
Digital Filter
1 to 100 sec. (OFF when 0 is set.)
Measuring Accuracy
Type :K, J,T, E, PLII
Less than -100°C (-148°F) : ±2.0°C (±3.6°F)
-100 to 333°C (-148 to 633.2°F) : ±1.0°C (±1.8°F)
More than 334°C (633.2°F) : ±(0.3% of Reading + 1 digit)
Type :N, S, R, W5Re/W26Re
Less than 667°C (1232.6°F) : ±2.0°C (±3.6°F)
More than 667°C (1232.6°F) : ±(0.3% of Reading + 1 digit)
Type : B
Less than 400°C (752°F) : ±70.0°C (±126°F)
400 to 666°C (752 to 1232.6°F) : ±2.0°C (3.6°F)
More than 667°C (1232.6°F) : ±(0.3% of Reading + 1 digit)
Cold junction temperature compensation error
±1.0°C (1.8°F) [at 23°C±2°C (73.4°F± 3.6°F)]
Within ±1.5°C (± 2.7°F) [Between -10 and 50°C (14 and 122°F)]
b) RTD
Less than 266°C (510.8°F) : ±0.8°C (±1.4°F)
More than 267°C (512.6°F) : ±(0.3% of Reading + 1 digit)
c) DC voltage and DC current
±0.3% of span
Insulation Resistance
More than 20MΩ(500V DC) between each isolation block
Dielectric Strength
More than 600V AC for one minute between each isolation block
Control Method
Brilliant PID control (with autotuning)
•Direct action/Reverse action is selectable.
•ON/OFF action is selectable.
Heat/Cool Brilliant PID control (with autotuning)
•Air cooling/Water cooling is selectable.
Major Setting Range
Set value : Same as input range.
Proportional band :
0 to input span (Temperature)
0.0 to 100.0% of input span (Voltage, Current)
(ON/OFF action when P=0)
Cool side proportional band :
0 to input span (Temperature)
0.0 to 100.0% of input span (Voltage, Current)
Integral time : 1 to 3600 sec.
Derivative time : 0 to 3600 sec.
Control response : Slow, Medium, Fast
Event Inputs (Optional)
Number of Inputs : 1 point
Event InputType
a) RUN/STOP switching (OPEN :STOP, CLOSE : RUN)
b) Alarm interlock release (CLOSE : Interlock release)
Input Rating
Non-voltage contact input (Source type)
OPEN : 500kΩor more, CLOSE : 10Ωor less
Rating voltage : 24VDC, Rating current : Approx.6mA
Output limiter :
-5.0 to +105.0% (High/Low individual setting)
Proportional cycle time : 1 to 100 sec. (Heat/Cool individual setting)
Other setting : Auto/Manual selectable
Control Output
Relay output :
Form A contact, 250V AC 3A (resistive load)
Voltage pulse output : 0/12V DC
(Load resistance : More than 600Ω)
Current output : 0 to 20mA, 4 to 20mA DC
(Load resistance : Less than 600Ω)
Continuous
voltage output
: 0 to 5V, 0 to 10V, 1 to 5V DC
(Load resistance : More than 1kΩ)
Alarms
Event (Alarm ) Output
a)Number of alarms : Up to 2 points / ch
b)Type : Deviation High, Low, High/Low, Band,
Process High, Low
• Hold action is available except for Band.
• Alarm is interlock and delay timer is available.
c)Setting range : Deviation alarm : -span to +span
Deviation High/Low, Band : 0 to span
Process alarm : Same as input range
d)Differential gap : 0 to input span
e)Output : Communication data or event output (Option)
Loop break alarm
(LBA)
a)Number of alarms : 2 points (1 point/ch)
b)LBA time setting : 0 to 7200 sec. (LBA is OFF when 0 is set)
c)LBA deadband : 0 to input span
d)Output : Communication data or event output (Option)
Heater Break Alarm
(HBA)
a)Number of alarms : 2 points (1 point/ch)
b)CT type : CTL-6-P-N (30A), CTL-12-S56-10L-N (100A)
(Specify when ordering)
c)Display range : 0.0 to 100.0A
• Heater break alarm function is OFF when 0.0 setting.
d)Accuracy :
±5% of input value or ±2A (whichever is larger)
e)Output : Communication data or event output (Option)
Communications
a)
Communication method
: Based on RS-485 (2-wire)
b)
Communication speed :
2400, 9600, 19200, 38400 BPS
c)Protocol : ANSI X3.28(1976) 2.5 A4
MODBUS
d)Bit format
Start bit : 1
Data bit : 7 or 8 •For MODBUS 8 bit only
Parity bit : Without, Odd or Even
Stop bit : 1
e)Communication code : ASCII(JIS) 7-bit code
f) Maximum connection : 31 ( Address can be set from 0 to 99.)
Event Outputs (Optional)
Number of Inputs : 2 points
Event OutputType
Temperature alarm output, Heater break alarm output,
Control loop break alarm output, Burnout output,
Temperature rise completion
Output Rating
Relay contact output,
Form A contact, 250V AC 1A (resistive load)
Module type Digital Temperature Controller SRV