Multi-Loop Digital Temperature Controller MA901
Input
Alarm (Up to 3 points) (Optional)
Performance
Control
Number of Inputs
8 points
Input
a) Thermocouple : K, J, R, S, B, E,T, N (JIS/IEC), PLII (NBS)
W5Re/W26Re (ASTM), U, L (DIN)
•Influence of external resistance : Approx. 0.2µV/Ω
•Input break action : Up-scale
b) RTD : Pt100 (JIS/IEC), JPt100 (JIS)
•Influence of input lead resistance : Approx.0.01[%/Ω] of reading
•Maximum 10Ωper wire
•Input break action : Up-scale
•Input is not isolated.
c) DC voltage : 0 to 5V, 1 to 5V, 0 to 10V
•Input break action : Down-scale
•Input is not isolated.
SamplingTime
1 sec
Input Filter
First order lag digital filter
Time constant 1 to 100 sec. (OFF when 0 is set)
PV Bias
- span to +span (Within -1999 to 9999)
Measuring Accuracy
a) Thermocouple
±(0.3% of reading + 1 digit) or ±2˚C (4˚F) whichever is larger
•Accuracy is not guaranteed between 0 and 399˚C (0 and 799˚F)
for type R, S and B.
•Accuracy is not guaranteed less than -100.0˚C ( -158.0˚F) for type
K, J, T and U.
b) RTD
±(0.3% of reading + 1 digit) or ±0.8˚C (1.6˚F) whichever is larger
c) DC voltage
±(0.3% of span + 1 digit)
Insulation Resistance
More than 20MΩ(500V DC) between measured terminals and ground
More than 20MΩ(500V DC) between power terminals and ground
Dielectric Strength
1000V AC for one minute between measured terminals and ground
1500V AC for one minute between power terminals and ground
Control Method
PID control (with autotuning function)
•Available for reverse and direct action. (Specify when ordering.)
Major Setting Range
Set value : Same as input range.
Proportional band
:
1 to span (ON/OFF action when P=0)
•Differential gap at ON/OFF action is 2˚C (˚F) or 0.2%.
Integral time : 1 to 3600sec.(P + D action when I=0)
Derivative time : 1 to 3600sec.(P + I action when D=0)
Anti-Reset Windup(ARW)
:1 to 100% of heat side proportional band
(Integral action is OFF when ARW=0)
Proportional cycle time : 1 to 100 sec.
Operation Mode
Available for switching each channel to be normal (control), alarm
monitoring (control output OFF, alarm action enabled) and unused.
Control Output
Relay output :
Form A contact, 250V AC 3A (resistive load)
Voltage pulse output : 0/12V DC
(Load resistance : More than 600Ω)
Current output : 4 to 20mA DC or 0 to 20mA DC
(Load resistance : Less than 600Ω)
Triac output : Rating : 0.5A
(An ambient temperature is less than 40˚C)
•Measurement terminals and output terminals are not isolated.
•Alarm 1 output (Standard), Alarm 2, 3 (Optional)
Temperature Alarm
a) Type : Deviation High, Low, High/Low, Band,
P
rocess High, Low
Set value High, Low, Fail
b) Differential gap : 2˚C (˚F) or 2.0˚C (˚F) (Temperature input)
0.2% (Voltage, current input)
Control Loop Break Alarm
(LBA)
a) LBA time setting : 0.1 to 200.0 min.
b) LBA deadband : 0 to 9999 ˚C [˚F] or 100% of span
(OFF by setting zero)
•Output from Alarm 1 terminal.
Heater Break Alarm
(For single phase)
a) CT type : CTL-6-P-N (30A), CTL-12-S56-10L-N (100A)
b) Display range : 0.0 to 100.0A
c) Accuracy : ± 5% of input value or ± 2A
(whichever is larger)
•
Output from Alarm 2 terminal.
Alarm Output
a) Alarm Output 1 to 3
Relay output, Form A contact 250V AC 1A (resistive load)
Communications (Optional)
Waterproof/Dustproof
(Optional)
a)
Communication method :
RS-232C (3-wire), RS-422A (4-wire)
RS-485 (2-wire)
b)
Communication speed :
2400, 4800, 9600, 19200 BPS
c) Bit format
Start bit : 1
Data bit : 7 or 8 •For MODBUS 8 bit only
Parity bit : Even, odd or without parity
Stop bit : 1 or 2
d) Communication code : ASCII(JIS) 7-bit code
e) Maximum connection : RS-232C : 1 unit
RS-422A, RS-485 : 31 units
(Address can be set from 0 to 99.)
Contact Input (Optional)
Number of Inputs
: 5 points
Contact InputType
a) RUN/STOP switching (OPEN : STOP, CLOSE :RUN)
b) Memory area selection :
Area selection : 3 points (BCD input 0 to 7)
Data set : 1 point
Input Rating
Non-voltage contact input (OPEN :500kΩor more, CLOSE : 10Ωor less)
IP65
•Waterproof/dustproof protection only effective from the front in panel
mounted installations.
Specifications
2MA901_03E