Rockwell Automation Allen-Bredley Dynamix 2500 User manual

User Manual
Run Up Coast Down Extension Module for the
Dynamix 2500 Data Collector
Catalog Number
1441-DYN25-MRUC

Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from
your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Allen-Bradley, Rockwell Software, Rockwell Automation, Emonitor, Dynamix, Enpac, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death,
property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the
consequence
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
surfaces may reach dangerous temperatures.
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.

Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 3
Table of Contents
Preface
Optional Extension Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Chapter 1
Installing Optional Extension
Modules
Install an Extension Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Uninstall Extension Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Manage Extension Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Extension Module Battery Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . 13
Chapter 2
Run Up/Coast Down Extension
Module
Set Up Run Up/Coast Down Measurements . . . . . . . . . . . . . . . . . . . . . . . 17
Collect Run Up/Coast Down Measurements. . . . . . . . . . . . . . . . . . . . . . . 19
Displaying Measurements by Using a Bode Plot. . . . . . . . . . . . . . . . . . . . . 22
Set Up the Bode Plot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Display the Bode Plot. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Displaying Measurements Using a Nyquist Plot. . . . . . . . . . . . . . . . . . . . . 25
Set Up the Nyquist Plot. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Display the Nyquist Plot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Displaying Measurements in Table Format . . . . . . . . . . . . . . . . . . . . . . . . . 28
Set Up the Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Display the Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Displaying Measurements Using a Waterfall. . . . . . . . . . . . . . . . . . . . . . . . 31
Set Up the Waterfall. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Display the Waterfall Plot. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Displaying Measurements Using a Spectrogram. . . . . . . . . . . . . . . . . . . . . 36
Set Up the Spectrogram Plot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Display the Spectrogram Plot. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Save Run Up/Coast Down Measurements . . . . . . . . . . . . . . . . . . . . . . . . . 40
Recall a Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Review Run Up/Coast Down Measurements. . . . . . . . . . . . . . . . . . . . . . . 43
Screen Capturing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Delete Run Up/Coast Down Files. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Index

4Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Table of Contents
Notes:

Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 5
Preface
This manual covers the Dynamix 2500 data collector Run Up Coast Down
(RUCD) extension module.
When using the Dynamix 2500 Data Collector Run Up Coast Down Extension
Module, you can do the following:
•Record and analyze data from intermittent events and transient vibration
signals from non-steady state machines.
•Analyze a machine’s critical speeds and resonant frequencies.
Optional Extension
Modules
These are the optional extension modules for the Dynamix 2500 data collector:
•1441-DYN25-4C, 4-channel Activation (1)
The 4-channel activation lets you take 3- or 4- channel magnitude, time
waveform, spectra, and Offroute measurements.
•1441-DYN25-MBMP Bump Test
The Bump test (or hammer test) determines the natural frequencies of a
machine or a structure.
•1441-DYN25-MBAL Balancing
The Balancing test resolves single-plane, two-plane, and static-couple
balances with high precision.
•1441-DYN25-MFRF Frequency Response Function
The FRF test lets you determine the natural frequencies of a machine as
well as sophisticated information about the frequency response of the
structure being tested.
•1441-DYN25-MREC Time Recorder
The Time Recorder test uses a the instrument as a data recorder for real-
time data acquisition and analysis.
•1441-DYN25-MRUC Run Up Coast Down
The RUCD test records and analyzes data from intermittent events and
transient vibration signals from non-steady state machines.
See Additional Resources on page 6 for a listing of available publications.
(1) This is an activation license for the Dynamix 2500 data collector.

6Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Preface
Additional Resources
These documents contain additional information concerning products from
Rockwell Automation.
You can view or download publications at http://www.rockwellautomation.com/
literature. To order paper copies of technical documentation, contact your local
Allen-Bradley distributor or Rockwell Automation sales representative.
Resource Description
Dynamix 2500 Data Collector User Manual,
publication 1441-UM001 Describes the Dynamix 2500 data collector
which provides predictive maintenance by
using noise and vibration analysis.
Dynamix 2500 Data Collector Bump Test Extension
Module User Manual, publication 1441-UM002 Describes how determine natural (or resonant)
frequencies of a machine or structure.
Dynamix 2500 Data Collector Frequency Response
Function Extension Module User Manual,
publication 1441-UM003
Describes how to determine the natural
frequencies of a machine or structure using
modal hammer.
Dynamix 2500 Data Collector Balancing Extension
Module User Manual, publication 1441-UM004 Describes the direct method to balance your
rotating machinery in one or two planes.
Dynamix 2500 Data Collector Time Recorder
Extension Module User Manual,
publication 1441-UM005
Describes how to use the data collector as a
data recorder for real-time data acquisition,
post processing, and analysis.
Emonitor User’s Guide, publication
EMONTR-UM001
Describes data management for predictive
maintenance services.
Dynamix 2500 Data Collector Kit Release Notes,
publication 1441-RN001 Provides important information on the latest
updates, for example, firmware, certifications,
warnings, and hardware changes for the data
collector.
Dynamix 2500 Data Collector Optional Extension
Modules Release Notes, publication 1441-RN002 Provides important information on how to
install the Optional Extension Modules onto
the Dynamix 2500 data collector.
Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1 Provides general guidelines for installing a
Rockwell Automation industrial system.
Product Certifications website, http://www.ab.com Provides declarations of conformity,
certificates, and other certification details.

Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 7
Chapter
1
Installing Optional Extension Modules
The data collector uses the Extension Manager to install and uninstall extension
modules. These extension modules are licensed and ordered separately from the
basic entry level product.
The installation Secure Digital (SD) cards that you receive work with any
Dynamix 2500 data collector. Once you have installed an extension module, the
card is locked so that it can be used only with that instrument.
You can uninstall extension modules if required. When uninstalling an extension
module, you have the option to free up the license so you can install the extension
module on another instrument. This makes the extension module available to be
transferred between units.
Install an Extension
Module
Follow these instructions to install an extension module.
1. Open the base cover at the bottom of the Dynamix 2500 data collector.
2. Place the extension module SD card contact side-up into the unit until it is
firmly seated in place.
3. Close the base cover.
Topic Page
Install an Extension Module 7
Uninstall Extension Modules 9
Manage Extension Modules 12
Extension Module Battery Status Indicators 13
IMPORTANT
One installation SD card is required for each instrument that needs to
be upgraded.
IMPORTANT
When ever you re-run the OS Loader software, you will re-load only the
main OS firmware. The OS loader will backup licence files and data, but
not the optional extension modules. Once you have updated the OS
firmware, install the latest version of your optional extension modules.
See the Dynamix 2500 Data Collector User Manual, 1441-UM001, for
more information.

8Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Chapter 1 Installing Optional Extension Modules
4. Apply power to the data collector.
5. From the Main Menu, select Setup Utility and press Enter.
6. Press 0 (Shift) to display the second set of functions.
The Extension Manager function remains on the screen for about
3secondsafterreleasing0(Shift).
7. Press F1 (Extn Mgr).
The Extension Manager screen appears showing the current extension
module installations.
8. Press 0 (Shift) to display the Install extension function.
9. Press F2 (Install) to install the new extension module.
Extension Manager

Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 9
Installing Optional Extension Modules Chapter 1
When the installation is complete, a confirmation prompt appears.
10. Press F4 (OK).
The new extension module appears in the list.
11. Press F4 (Esc) to exit the Extension Manager screen.
Uninstall Extension
Modules
Follow these instructions to uninstall an extension module.
1. Press 0 (Shift) from the Setup Utility screen to display the Extension
Manager function.
The Extension Manager function remains on the screen for about three
seconds after releasing 0 (Shift).
2. Press F1 (Extn Mgr).
Extension Manager

10 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Chapter 1 Installing Optional Extension Modules
The Extension Manager screen appears.
3. Select the extension module you want to uninstall and press F3 (Select).
F3 (Select) toggles the selection on and off.
This screen lists the
extension modules
currently installed and the
on the unit.

Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 11
Installing Optional Extension Modules Chapter 1
A checkmark appears next to that extension module.
4. Press F1 (Uninstall).
A confirmation message appears.
5. Make sure your installation card is inserted into the instrument.
6. Press F2 (Yes) to uninstall the extension module.
7. Press F4 (Esc) to exit the Extension Manager screen.
IMPORTANT
The extension module is uninstalled and the license on the card is
released so that the card can be used to install the extension
module on another Dynamix 2500 data collector.
If the installation card is not inserted in the instrument and no
card, you are is found or the card does not have the extension
module license for the unit, you are prompted to insert the correct
installation card or continue without freeing the license.

12 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Chapter 1 Installing Optional Extension Modules
Manage Extension
Modules
The Dynamix 2500 data collector lets you to hide installed extension modules
from the Main Menu. You may need to hide an advanced extension module icon
from an inexperienced user, for example, RUCD and FRF.
Follow these instructions to hide or show an extension module icon on the Main
Menu.
1. Press 0 (Shift) on the Setup Utility screen to display the Extension
Manager function.
The Extension Manager function should remain on the screen for
approximately three seconds after releasing 0 (Shift).
2. Press F1 (Extn Mgr).
The Extension Manager screen appears. The Extension Manager displays a
list of installed extensions module.
The F2 (Hide) toggles between Hide and Show depending if the selected
extension module is hidden or not.
IMPORTANT
Once an extension module is hidden, its icon is not represented on the
Main Menu or displayed in the Dynamix 2500 data collector About
screen.
TIP
You have to exit and re-enter the Extension Manager after hiding an
extension module to have the Show function appear.
The extension modules that
are hidden are shown in
[square brackets].

Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 13
Installing Optional Extension Modules Chapter 1
3. Select the extension module that you want to hide or show and press F2
(Show/Hide).
4. Press F4 (Esc) to exit the Extension Manager.
Extension Module Battery
Status Indicators
The battery status icons show the strength of the battery.
TIP
If you want to show or hide multiple extension modules
simultaneously, select each extension module and press F3
(Select).
A checkbox appears next to each selected extension module. If
you select multiple extension modules and some are hidden
while others are shown, F2 (Show/Hide) reflects the status of the
selected extension module.
Table 1 - Extension Module Battery Icon Descriptions
Battery Icon Meaning
Battery status is good: >30% life remaining.
Battery status is low: >10% life remaining.
Battery status is very low: <10% life remaining.
Battery is charging.

14 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Chapter 1 Installing Optional Extension Modules
Notes:

Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 15
Chapter
2
Run Up/Coast Down Extension Module
The Run Up/Coast Down (RUCD) extension module is an optional module for
the Dynamix 2500 data collector. You install the extension module with the
RUCD Secure Digital (SD) card.
See Installing Optional Extension Modules on page 7 for installation
instructions.
The Run Up/Coast Down extension module lets the data collector record and
analyze data from intermittent events and transient vibration signals from
non-steady state machines.
The Run Up/Coast Down extension module is used to record and analyze data
from machines where noise or vibration levels are changing with speed or time
such as during a run up (increase in speed), coast down (decrease in speed), or
other applications causing transient phenomena. You use the data to analyze a
machine’s critical speeds and resonant frequencies.
Topic Page
Set Up Run Up/Coast Down Measurements 17
Collect Run Up/Coast Down Measurements 19
Displaying Measurements by Using a Bode Plot 22
Displaying Measurements Using a Nyquist Plot 25
Displaying Measurements in Table Format 28
Displaying Measurements Using a Waterfall 31
Displaying Measurements Using a Spectrogram 36
Save Run Up/Coast Down Measurements 40
Recall a Setup 41
Review Run Up/Coast Down Measurements 43
Screen Capturing 45
Delete Run Up/Coast Down Files 45

16 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Chapter 2 Run Up/Coast Down Extension Module
The application acquires a simultaneous noise or vibration signal and a
tachometer signal.
This example setup includes the following:
• Accelerometer attached to connector A of the Dynamix 2500 data
collector
• Optical tachometer signal connected to the POWER/USB/TRIGGER
cable
• Tripod for tachometer signal stability
• Speed reference trigger
• Small piece of reflective tape on the part of the shaft canserve as a reference
trigger or you can simply pass the laser over a notch in the shaft
This graphic illustrates a typical Run Up/Coast Down setup.
Figure 1 - Run Up/Coast Down Setup
The recorded data is saved in the form of a Microsoft .wav time waveform file.
You can analyze this file and viewed in a variety of different formats including:
•BodePlot
•NyquistPlot
• Table
•Waterfall
•Spectrogram
32147-M
Accelerometer
Tripod
Tachometer
Reflective Tape

Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 17
Run Up/Coast Down Extension Module Chapter 2
Set Up Run Up/Coast Down
Measurements
The first step in the Run Up/Coast Down extension module is to setup how the
measurements are taken by the data collector.
1. Select RUCD on the Main Menu and press the Enter.
The RUCD screen appears.
2. Select Setup and press Enter to set up the Run Up/Coast Down
parameters.
The RUCD - Setup screen appears.
3. Select a parameter and press the Right arrow to open a list of values.
4. Select or type the parameter value.
5. Press Left arrow to save your selection.
6. Press F2 (Save) to save the current settings to a file.
See Save Run Up/Coast Down Measurements on page 40 for details.

18 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Chapter 2 Run Up/Coast Down Extension Module
Use these descriptions to help you configure the parameters in the Run Up/Coast
Down Setup screen.
Table 2 - Run Up/Coast Down Setup Parameters
Parameter Description Values/Comments
Transducer Specifies the type of sensor used on Connector A, this is typically
Accel (g).
The specified sensor type determines available options and
engineering units for subsequent setup fields.
Accel ICP (g) (default)
Accel (g)
Accel ICP (m/s2)
Accel (m/s2)
Vel ICP (mm/s)
Vel (mm/s)
Vel ICP (ips)
Vel (ips)
Disp (mils)
Disp (µm)
Volts AC
User (EU)
Sens (mV/EU) The transducer sensitivity in millivolts (MV) per engineering units
(EU). 1…2000 (mV/EU)
100 (default)
Range (EU) The expected maximum amplitude range value for the incoming input
signal.
The range should accommodate for unexpected events. If you are
unsure about the range value, set the range 10 to 20 times higher
than expected.
.1 EU
.2 EU
.5 EU
1 EU
2 EU (default)
5 EU
10 EU
20 EU (default)
50 EU
100 EU
200 EU
500 EU
1000 EU
2000 EU
Max M/c Speed The maximum speed that the shaft will reach in rpm.
This is used with Max No Orders to determine the sampling rate.
10…60000 rpm
3600 rpm (default)
Max No Orders The maximum number of shaft orders of interest during analysis.
This is used with Max M/c Speed to determine the sampling rate.
1 to 166
32 (default)
Mode The method for initiating the data collection.
•Runup - The data collection starts when the machine speed
rises above Start Spd.
•Coast down -The data collection starts when the machine
speed falls below Stop Spd.
•Manual - Manually start data collection by pressing F4 (Start).
No tachometer signal is required for this mode.
Runup (default)
Manual
Coastdown

Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 19
Run Up/Coast Down Extension Module Chapter 2
Collect Run Up/Coast Down
Measurements
This section describes the Run Up/Coast Down status indicators and how to
collect Run Up/Coast Down data.
Once you have configured the parameters, you can begin collecting data. The
data is automatically recorded as a .wav file, which can then be analyzed using
several different types of plots.
1. Using the a tachometer cable, connect the reference input device to the
POWER/USB/TRIGGER connector and the transducer to connector A.
2. Align the reference input device (tachometer, optical tachometer, or
strobescope) to capture shaft speed.
Pulses/Rev The number of tachometer signal pulses per revolution of the
reference shaft.
To acquire a suitable tachometer signal, the tachometer signal must
be approximately 1.5 volts peak-to-peak. The adverse effect of
excessively short tachometer pulse widths can be addressed by
setting the Max No Order to a higher value to increase the sampling
rate.
.1…1000
1 (default)
This number can be a multiple or a non-
integer to accommodate, for example, gear
ratios.
Start Spd (RPM) Sets the speed at which the unit should start collecting data.
•If Mode is set to Runup, this value must be less than the Stop
Spd.
•If Mode is set to Coast down, this value must be greater than
the Stop Spd.
This parameter is not available if Mode is set to Manual.
10…3600 rpm
60 rpm (default)
Stop Spd (RPM) Sets the speed at which the unit should stop collecting data.
•If Mode is set to Runup, this value must be greater than the
Start Spd.
•If Mode is set to Coast down, this value must be less than Start
Spd.
This parameter is not available if Mode is set to Manual.
10…3600 rpm
300 rpm (default)
Save To Sets the location where data is saved.
Save the data to the SD or PC card if the .wav files will be large. Your
selection affects the maximum recording time.
Internal (default)
SD Card
Max Acq Time (s) The number of seconds to record the time waveform.
This limit applies only if the run up or coast down takes longer than
the time set here.
1…1131.65 s
1131.65 s (default)
Table 2 - Run Up/Coast Down Setup Parameters
Parameter Description Values/Comments
Table 3 - RUCD Status Indicators
Indicator Status Description
Red Solid An overload error (clipping or streaming error) has
occurred during data collection.
Amber Solid An error has occurred during data collection The status
indicator turns off when the error condition disappears.
Green Flashing Green No errors occurred during data collection.

20 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Chapter 2 Run Up/Coast Down Extension Module
3. Attach a transducer to the bearing house.
4. Start the machine or stop the machine as needed.
5. From the RUDC Setup screen press F3 (Start).
The RUCD - Taking Data screen appears.
The Dynamix 2500 data collector begins collecting run up or coast down
data based on the parameters you selected. The state of the machine is
indicated on the screen.
Data collection is complete when the specified Stp Speed or Maximum
Acquisition Time is reached, or you press F3 (Stop).
State Description
Armed The machine speed has not reached the Start Spd and data collection has
not yet started.
At any time during this state, you can press F3 (Start) to manually start
data collection.
Acquiring The machine speed has reached the Start Spd and data collection has
started.
At any time during this state, you can press F3 (Stop) to manually stop
data collection.
Error-Clipped An error occurred during data collection. If a sensor’s Range setting is too
small to accommodate the signal’s amplitude, a message displays in the
message error.
Press F4 (Back) to return to the RUCD - Setup screen and increase the
Range setting.
Current Speed of Machine
Current Overall
Vibration Reading
Maximum Acquisition Time in the
Armed State
Remaining Recording Time in the
Acquiring State
Message Area
This manual suits for next models
1
Table of contents
Other Rockwell Automation Data Logger manuals
Popular Data Logger manuals by other brands

MadgeTech
MadgeTech AVS140-1 Product user guide

Huawei
Huawei SmartLogger2000-10-B-JP quick guide

MONARCH INSTRUMENT
MONARCH INSTRUMENT Track-It 5396-0337 instruction manual

Lascar
Lascar EL-USB-LITE Installation and operation guide

VOLTCRAFT
VOLTCRAFT VC-655 BT operating instructions

sauermann
sauermann KNT 320 user manual